R313-15-906. Procedures for Receiving and Opening Packages  


Latest version.
  • (1) Each licensee or registrant who expects to receive a package containing quantities of radioactive material in excess of a Type A quantity, as used in Section R313-19-100, which incorporates 10 CFR 71.4 by reference, shall make arrangements to receive:

    (a) The package when the carrier offers it for delivery; or

    (b) The notification of the arrival of the package at the carrier's terminal and to take possession of the package expeditiously.

    (2) Each licensee or registrant shall:

    (a) Monitor the external surfaces of a labeled package for radioactive contamination unless the package contains only radioactive material in the form of gas or in special form as defined in Section R313-12-3; and

    (b) Monitor the external surfaces of a labeled package for radiation levels unless the package contains quantities of radioactive material that are less than or equal to the Type A quantity, as used in Section R313-19-100, which incorporates 10 CFR 71.4 by reference; and

    (c) Monitor all packages known to contain radioactive material for radioactive contamination and radiation levels if there is evidence of degradation of package integrity, such as packages that are crushed, wet, or damaged.

    (3) The licensee or registrant shall perform the monitoring required by Subsection R313-15-906(2) as soon as practical after receipt of the package, but not later than three hours after the package is received at the licensee's or registrant's facility if it is received during the licensee's or registrant's normal working hours or if there is evidence of degradation of package integrity, such as a package that is crushed, wet, or damaged. If a package is received after working hours, and has no evidence of degradation of package integrity, the package shall be monitored no later than three hours from the beginning of the next working day.

    (4) The licensee or registrant shall immediately notify the final delivery carrier and, by telephone and telegram, mailgram, or facsimile, the Director when:

    (a) Removable radioactive surface contamination exceeds the limits of Section R313-19-100 which incorporates 10 CFR 71.87(i) by reference; or

    (b) External radiation levels exceed the limits of Section R313-19-100 which incorporates 10 CFR 71.47 by reference.

    (5) Each licensee or registrant shall:

    (a) Establish, maintain, and retain written procedures for safely opening packages in which radioactive material is received; and

    (b) Ensure that the procedures are followed and that due consideration is given to special instructions for the type of package being opened.

    (6) Licensees or registrants transferring special form sources in vehicles owned or operated by the licensee or registrant to and from a work site are exempt from the contamination monitoring requirements of Subsection R313-15-906(2), but are not exempt from the monitoring requirement in Subsection R313-15-906(2) for measuring radiation levels that ensures that the source is still properly lodged in its shield.