(1) Dining, Recreation and Day Space. The facility layout shall include a minimum total inpatient space for dining, recreation, and day use computed on the basis of 30 square feet per bed.
(a) The facility shall include a minimum of 200 square feet for outpatients and visitors when dining is part of a day treatment program.
(b) If dining is not part of a day treatment program, the facility shall provide a minimum of 100 square feet of additional outpatient day space.
(c) Enclosed storage space for recreation equipment and supplies shall be provided in addition to the requirements of day use.
(2) Recreation and Group Therapy Space. At least two separate social areas, one designed for noisy activities and one designed for quiet activities, shall be provided as follows:
(a) At least 120 square feet shall be provided for each area.
(b) The combined area of the two areas shall be at least 40 square feet per patient.
(c) Activity areas may be utilized for dining activities and may serve more than one adult nursing unit.
(d) Activity areas shall be provided for pediatric and adolescent nursing units which are separate from adult areas.
(e) Space for group therapy shall be provided and activity spaces may be used for group therapy activities.
(3) Examination and treatment rooms shall be provided except when all patient rooms are single-bed rooms.
(a) An examination and treatment room may be shared by multiple nursing units.
(b) If provided, the room shall have a minimum floor area of 110 square feet, excluding space for vestibules, toilet, closets, and work counters, whether fixed or movable.
(c) The minimum allowable floor dimension shall be ten feet.
(d) The room shall contain a lavatory or sink equipped for handwashing, work counter, storage facilities, and a desk, counter, or shelf space for writing.
(4) A consultation room shall be provided.
(a) Rooms shall have a minimum floor space of 100 square feet, and be provided at a room-to-bed ratio of one consultation room for each 12 beds.
(b) They shall be designed for acoustical and visual privacy and constructed using wall construction assemblies with a minimum STC rating of 50.
(c) They shall provide appropriate space for evaluation of patient needs and progress, including work areas for evaluators and work space for patients.
(5) A multipurpose room for staff and patient conferences, education, demonstrations, and consultation, shall be provided.
(a) It shall be separate from required activity areas defined in R432-8-6(2).
(b) If provided in the administration area, it may be utilized for this requirement if it is conveniently accessible from a patient-use corridor.
(6) If child education is provided through facility-based programs, a room shall be provided in the adolescent unit for this purpose. The room shall contain at least 20 square feet per pediatric and adolescent bed, but not less than 250 square feet. Multiple use rooms may be used, but must be available for educational programs on a first priority basis.
(7) Pediatric and adolescent nursing units shall be physically separated from adult nursing units and examination and treatment rooms. In addition to the requirements of R432-8-6(1) through (5), individual rooms or a multipurpose room shall be provided for dining, education, and recreation. Insulation, isolation, and structural provisions shall minimize the transmission of impact noise through the floor, walls, or ceiling of these multipurpose rooms. Service rooms may be shared by more than one pediatric or adolescent nursing unit, but shall not be shared with adult nursing units.
(a) A patient toilet room, in addition to those serving bed areas, shall be conveniently accessible from multipurpose rooms.
(b) Storage closets or cabinets for toys, educational, and recreational equipment shall be provided.