R432-600-25. Emergency Electric Service  


Latest version.
  •   (1) The clinic shall make provision for emergency electrical power to provide lighting and power to critical areas essential for patient safety in the event of an interruption of normal electrical power service.

      (2) The method utilized for emergency electrical power is subject to Departmental review and approval.

      (3) There shall be provision for emergency exit lighting according to NFPA 101.

      (4) Flashlights shall be available for emergency use by staff.

      (5) All emergency electrical power systems shall be maintained in operating condition and tested as follows:

      (a) Emergency generators shall be tested in accordance with NFPA 99.

      (b) Transfer switches and battery operated equipment shall be functionally tested every 30 days and load tested at least annually, for 90 minutes.

      (6) A written record of inspection, performance, test period, and repair of the emergency electrical system shall be maintained on the premises for review.