R432-10-6. Construction Features  


Latest version.
  • (1) Mechanical tests shall be conducted prior to the final Department construction inspection. Written test results shall be retained in facility maintenance files and available for Department review.

    (2) The heating system shall be capable of maintaining temperatures of 80 degrees F. in areas occupied by patients.

    (a) The cooling system shall be capable of maintaining temperatures of 72 degrees F. in areas occupied by patients.

    (b) Furnace and boiler rooms shall be provided with sufficient outdoor air to maintain equipment combustion rates and to limit work station temperatures to a temperature not to exceed 90 degrees F. When ambient outside air temperature is higher, maximum temperature may be 97 degrees F.

    (c) A relative humidity between 30 percent and 60 percent shall be provided in all patient areas.

    (d) The bottom of ventilation supply and return opening shall be at least three inches above the floor.

    (3) All hoods over cooking ranges shall be equipped with grease filters, fire extinguishing systems, and heat actuated fan controls. Cleanout openings shall be provided every 20 feet in horizontal sections of the duct systems serving these hoods.

    (4) Kitchen grease traps shall be located and arranged to permit easy access without the need to enter the food preparation or storage area.

    (5) Hot water systems. Hot water provided in patient tubs, showers, whirlpools, and handwashing facilities shall be regulated by thermostatically controlled automatic mixing valves. Mixing valves may be installed on the recirculating system or on individual inlets to appliances.

    (6) Drainage Systems. Building sewers shall discharge into community sewerage except, where such a system is not available, the facility shall treat its sewage in accordance with local requirements and Department of Environmental Quality requirements.

    (7) Piping and Valve systems. All piping and valves in all systems, except control line tubing, shall be labeled to show content of line and direction of flow. Labels shall be permanent type, either metal or paint, and shall be clearly visible to maintenance personnel.

    (8) Oxygen and suction systems shall be installed in accordance with the requirements of a level 1 system per NFPA 99 and Table 2.1-6 of the Guidelines.

    (9) Electric materials shall be new and listed as complying with standards of Underwriters Laboratories, Inc., or other equivalent nationally recognized standards. The owner shall provide written certification to the Department verifying that systems and grounding comply with NFPA 99 and NFPA 70.

    (10) Approaches to buildings and all spaces within buildings occupied by people, machinery, or equipment shall have fixtures for lighting in accordance with requirements shown in Tables 3A and 3B of Illuminating Engineering Society of North America IESNA, publication RP-29-06, Lighting for Hospitals and Health Care Facilities, 2006 edition. Automatic Emergency lighting shall be provided in accordance with NFPA 99 and NFPA 101.

    (11) Receptacles shall include:

    (a) Each examination and work table shall have access to minimum of two duplex receptacles.

    (b) Receptacle cover plates on electrical receptacles supplied for the emergency system shall be red.

    (12) Emergency Electrical Service shall include:

    (a) An on-site emergency generator shall be provided.

    (b) The following services shall be connected to the emergency generator:

    (i) life safety branch, as defined in section 517-32 of the National Electric Code NFPA 70;

    (ii) critical branch as defined in 517-33 of the National Electric Code NFPA 70;

    (iii) equipment system, as defined in 517-34 of the National Electric Code NFPA 70;

    (iv) telephone;

    (v) nurse call;

    (vi) heating equipment necessary to provide adequate heated space to house all patients under emergency conditions;

    (vii) one duplex receptacle in each patient room;

    (viii) one duplex receptacle at each nurse station;

    (ix) duplex receptacles in the emergency heated area at a ratio of one for each ten patients.

    (c) fuel storage capacity shall permit continuous operation for 48 hours.