R652-122-1500. Minimum Standards for Wildland Firefighting Equipment


Latest version.
  •   (1) The following standards are applicable to equipment used by fire departments representing those counties who have cooperative wildland fire protection agreements with the State of Utah. This includes county fire departments and other fire departments which are contracted with the counties to provide fire protection on private wildland. The Utah Division of Forestry, Fire and State Lands has determined that this standard be met by June 1, 2006.

      (2) Engines and water tenders used on private wildland fires within the county's jurisdiction will meet the standard for the type of equipment plus appropriate hand tools and water handling equipment as determined by the National Wildfire Coordinating Group.


    TABLE 1

    Engines


    Component Type 1 Type 2 Type 3


    Pump Rating (gpm) 1,000+ @ 250+ @ 150+ @

                               150 psi 150 psi 250 psi

    Tank Capacity (gal) 400+ 400+ 500+

    Hose 2.5 inch 1,200 ft 1,000 ft --

    Hose 1.5 inch 400 ft 500 ft 500 ft

    Hose 1 inch -- -- 500 ft

    Ladders 48 ft 48 ft --

    Master Stream (gpm) 500 -- --

    Personnel (minimum) 4 3 2


    Component Type 4 Type 5 Type 6


    Pump Rating (gpm) 50 @ 50 @ 30 @

                               100 psi 100 psi 100 psi

    Tank Capacity (gal) 750+ 400 - 750 150 - 400

    Hose 2.5 inch -- -- --

    Hose 1.5 inch 300 ft 300 ft 300 ft

    Hose 1 inch 300 ft 300 ft 300 ft

    Ladders -- -- --

    Master Stream (gpm) -- -- --

    Personnel (minimum) 2 2 2


    TABLE 2

    Water Tenders


    Component Type 1 Type 2 Type 3


    Tank Capacity (gal) 5,000+ 2,500+ 1,000+

    Pump Capacity (gpm) 300+ 200+ 200+

    Off Load Capacity (gpm) 300+ 200+ 200+

    Max Refill Time (min) 30 20 15

    Personnel

       tactical/nontactical 2/1 2/1 2/1