R432-5-15. Electric Standards  


Latest version.
  • (1) Operators shall maintain written certification to the Department verifying that systems and grounding comply with NFPA 99 and NFPA 70.

    (2) Approaches to buildings and all spaces within buildings occupied by people, machinery, or equipment shall have fixtures for lighting in accordance with the requirements of the Illuminating Engineering Society of North America (IESNA). Parking lots shall have fixtures for lighting to provide light levels as recommended in IES Recommended Practice RP-20-1998, Lighting for parking facilities by the Illuminating Engineering Society of North America.

    (3) Automatic emergency lighting shall be provided in accordance with NFPA 99 and NFPA 101.

    (4) Each examination and work table shall have access to a minimum of two duplex outlets.

    (5) Receptacles and receptacle cover plates on the emergency system shall be red.

    (6) An on-site emergency generator shall be provided in all nursing care facilities except small ICF/MR health care facilities of 16 beds or less.

    (a) In addition to requirements of NFPA 70, Section 517-40, the following equipment shall be connected to the critical branch of the essential electrical system.

    (i) heating equipment necessary to provide heated space sufficient to house all residents under emergency conditions,

    (ii) duplex convenience outlets in the emergency heated area at the ratio of one duplex outlet for each ten residents,

    (iii) nurse call system,

    (iv) one duplex receptacle in each resident bedroom.

    (b) Fuel storage shall permit continuous operation of the services required to be connected to the emergency generator for 48 hours.

    (c) Skilled nursing facilities that accept residents that are dependant on ventilators or other electrically operated life support equipment shall be equipped with Type I essential electrical systems that meet the requirements of NFPA 99 and NFPA 70, Section 517-30.