R432-12-4. General Construction Requirements  


Latest version.
  • (1) Table 1 identifies the levels of care and construction requirements which apply.


    TABLE 1

    CONSTRUCTION REQUIREMENTS SUMMARY


                   LEVEL I LEVEL II LEVEL III LEVEL IV


    No. residents 1-16 4-16 4-16 4-16


    Resident No, they No, they Yes, they Yes, they

    Capable are non are non are are

    of Self ambulatory ambulatory ambulatory ambulatory

    Preservation non-mobile non-mobile mobile mobile

    Unassisted


    Resident restricted, restricted, restricted, not

    Exit Ability physical physical chemical restricted

    in an or mental or mental or physical

    Emergency disability disability restraints

                   and

                   medical

                   condition


    Accessible 100% 10% or 10% 10%

    Rooms 100% if Physical

                               Rehab.

    Construction

    Requirements

    code or NFPA 101 NFPA 101 NFPA 101 Utah Fire

    regulation Prevention

                                                         Board

                                                         Rules

                                                         R710-3;

                                                         IBC

                                                         R-4 occupancy


    fire rating 1 hour 1 hour 1 hour No

    of const requirement


    sprinkler yes yes yes Only if bldg.

                                                        larger than 4,500 SF


    smoke yes yes yes yes

    detector


    manual yes yes yes yes

    fire

    alarm


    above 3 yes yes yes no

    systems

    interconnected


    corridor 8 feet 6 feet 5 feet As required

                                                         by IBC


    resident 44 inch 44 inch 36 inch 36 inch

    room door

    width


    nurse call yes yes optional yes

    system


    (2) General Requirements.

    (a) Level I facilities shall meet the Nursing Facility Construction standards in R432-5.

    (b) Level II and III facilities shall meet the construction and design requirements identified in this section, unless specifically exempted.

    (c) Level IV facilities shall meet the Assisted Living Facility Type I Construction standards in R432-6.

    (d) Level I, II, III and IV facilities shall comply with the Americans with Disabilities Act and Architectural Barriers Act Accessibility Guidelines (ADA/ABA-AG).

    (e) Level I, II and III facilities shall conform to the life safety code requirements of NFPA 101, Chapter 18, which is adopted and incorporated by reference.

    (f) Level IV facilities shall conform to the fire safety provisions of R432-710-3.