R309-550-13. Operation and Maintenance


Latest version.
  •   (1) Disinfection After Line Repair.

      The disinfection procedures of Section 4.7, AWWA Standard C651-05 shall be followed if a water main is cut or repaired.

      (2) Cross Connections.

      The water system shall not allow a connection that may jeopardize water quality. Cross connections shall be eliminated by physical separation, an air gap, or an approved and properly operating backflow prevention assembly.

      The water system shall have an ongoing cross connection control program in compliance with R309-105-12.

      (3) ANSI/NSF Standards.

      All pipe and fittings used in routine operation and maintenance shall be ANSI-certified as meeting NSF Standard 61 or Standard 14.

      (4) Seasonal Operation.

      Water systems operated seasonally shall be disinfected and flushed according to AWWA Standard C651-05 for pipelines and AWWA Standard C652-11 for storage facilities prior to each season's use. A satisfactory bacteriologic sample shall be obtained prior to use. During the non-use period, care shall be taken to close all openings into the system.