R309-405-4. Assessment of a Penalty and Calculation of Settlement Amounts  


Latest version.
  • (1) Where the Director determines that a penalty may be appropriate, the Director shall propose a penalty amount by sending a notice of agency action to the public water system. The notice of agency action shall provide that the public water system may submit comments and/or information on the proposed penalty to the Director within 30 days. The criteria the Director will use in establishing a proposed penalty amount shall be as follows:

    (a) Major Violations: $600 to $1000 per day for each day of violation. This category includes violations with high potential for impact on drinking water users, major deviations from the requirements of the rules or Safe Drinking Water Act, intentional fraud, falsification of data, violations which result in a public water system being considered by the Environmental Protection Agency to be: "Significant Non-Compliers" (SNC), or violations that may have a substantial adverse effect on the regulatory program. Specific violations that are subject to a major violation category can include the following:

    (i) Violations subject to $1000 per day penalty:

    (A) Any violation defined by R309-220-5 which would trigger a Tier 1 public notification.

    (B) Not having any elements of a source protection plan as required in R309-600 for ground water sources and R309-605 for surface water sources.

    (C) Failure to respond to an Administrative Order issued by the Director.

    (D) Introduction by the water system of a source water that has not been evaluated and approved for use as a public drinking water source under R309-515.

    (E) Construction or use of an interconnection to another public water system which has not been reviewed and approved in accordance with R309-550-9.

    (F) Having over 20 IPS points (Improvement Priority System points based on R309-400, the Water System Rating Criteria) specifically for operating pressures below that required by R309-105-9.

    (G) Having 50 IPS points specifically for an inadequate well seal as required in R309-515.

    (H) Having over 50 IPS points (not including the deficiencies in (F) and (G) above) specifically assessed in the physical facility section of an IPS report.

    (I) Use of a surface water source without proper filtration treatment in accordance with R309-525 or 530.

    (J) Exceeding the rated water treatment plant capacity as determined by review under R309-525 or 530.

    (K) Insufficient disinfection contact time as evaluated under R309-215-7.

    (ii) Violations subject to $800 per day penalty:

    (A) Not having any of the required components of a cross connection control program in place as required by R309-105-12.

    (B) Any violation of the turbidity requirements outlined in R309-215-9(4)(b)(iii -iv) for individual filter turbidities using consecutive readings taken 15 minutes apart.

    (b) Moderate Violations: $400 to $600 per day for each day of violation. This category includes violations with a moderate potential for impact on drinking water users, moderate deviations from the requirements of the rules or Safe Drinking Water Act with some requirements implemented as intended, or violations that may have a significant notable adverse effect on the regulatory program. Specific violations that are subject to a moderate violation category can include the following:

    (i) Violations subject to $600 penalty:

    (A) Any violation defined by R309-220-6 which would trigger a Tier 2 public notification.

    (B) Having a disapproved status on a source protection plan (R309-600 and 605) for a period longer than 90 days.

    (C) Installation or use of disinfection equipment that has not been evaluated and approved for use under R309-520.

    (D) Having measured turbidity spikes of greater than 0.5 or 1.0 NTU in two consecutive fifteen minute readings as defined in R309-215-9(4)(b)(i) or (ii) respectively.

    (E) Insufficient source capacity, storage capacity, or delivery capacity as established by review of the system design under R309-500 through 550.

    (F) Not complying with plan approval requirements as set forth in R309-500. The term infrastructure can include the disinfection process, surface water treatment process, and physical facilities such as water treatment plants, storage reservoirs, sources and distribution piping.

    (c) Minor Violations: Up to $400 per day for each day of violation. This category includes violations with a minor potential for impact on drinking water users, slight deviations from the rules or Act with most of the requirements implemented, or violations that may have a minor adverse effect on the regulatory program. Specific violations that are subject to a minor violation category can include the following:

    (i) Violations subject to $400 per day penalty:

    (A) Any violation defined by R309-220-7 which would trigger a Tier 3 public notification or a violation of the monitoring requirements of R309-515-4(5), except for turbidity monitoring for surface water treatment facilities and violations termed as minor monitoring as outlined in R309-400-3 (minor bacteriological routine monitoring violation, minor bacteriological repeat monitoring violation and minor chemical monitoring violation).

    (B) Failure to upgrade a Preliminary Evaluation Report for a source protection plan as required in R309-600 and 605.

    (C) Failure to update a source protection plan as required in R309-600 and 605.

    (D) Construction or use of a storage reservoir that has not been evaluated for use under R309-545.

    (ii) Violations subject to $200 per day penalty:

    (A) Lacking individual components of a cross connection control program as required by R309-105-12.

    (B) Not having a certified operator on staff as required in R309-300-5(10) after 1 year or 4 operator certification exam cycles.

    (C) Any minor monitoring violation as defined by R309-400-3 (minor bacteriological routine monitoring violation, minor bacteriological repeat monitoring violation and minor chemical monitoring violation).

    (D) Any violation of the turbidity requirements outlined in R309-215-9(4)(b)(i-ii) for individual filter turbidities using consecutive readings taken 15 minutes apart.

    (2) The Director will assess the penalty, if any, after reviewing information submitted by the public water system. The public water system may appeal the assessment of the penalty as provided in R305-7-302.