R156-56-705. Local Amendments to the IBC.  


Latest version.
  • The following are adopted as amendments to the IBC to be applicable to the following jurisdictions:

    (1) City of Farmington:

    (a) A new Section (F)903.2.14 is added as follows:

    (F)903.2.14 Group R, Division 3 Occupancies. An automatic sprinkler system shall be installed throughout every dwelling in accordance with NFPA 13-D, when any of the following conditions are present:

    1. The structure is over two stories high, as defined by the building code;

    2. The nearest point of structure is more than 150 feet from the public way;

    3. The total floor area of all stories is over 5,000 square feet (excluding from the calculation the area of the basement and/or garage); or

    4. The structure is located on a street constructed after March 1, 2000 that has a gradient over 12% and, during fire department response, access to the structure will be gained by using such street. (If the access is intended to be from a direction where the steep gradient is not used, as determined by the Chief, this criteria shall not apply).

    Such sprinkler system shall be installed in basements, but need not be installed in garages, under eves or in enclosed attic spaces, unless required by the Chief.

    (b) A new Section 907.20 is added as follows:

    907.20 Alarm Circuit Supervision. Alarm circuits in alarm systems provided for commercial uses (defined as other than one- and two-family dwellings and townhouses) shall have Class "A" type of supervision. Specifically, Type "B" or End-of-line resistor and horn supervised systems are not allowed.

    (c) NFPA 13-02 is amended to add the following new sections:

    6.8.6 FDC Security Locks Required. All Fire Department connections installed for fire sprinkler and standpipe systems shall have approved security locks.

    6.10 Fire Pump Disconnect Signs. When installing a fire pump, red plastic laminate signs shall be installed in the electrical service panel, if the pump is wired separately from the main disconnect. These signs shall state: "Fire Pump Disconnect ONLY" and "Main Breaker DOES NOT Shut Off Fire Pump".

    14.1.1.5 Plan Preparation Identification. All plans for fire sprinkler systems, except for manufacturer's cut sheets of equipment shall include the full name of the person who prepared the drawings. When the drawings are prepared by a registered professional engineer, the engineer's signature shall also be included.

    15.1.2.5 Verification of Water Supply:

    15.1.2.5.1 Fire Flow Tests. Fire flow tests for verification of water supply shall be conducted and witnessed for all applications other than residential unless directed otherwise by the Chief. For residential water supply, verification shall be determined by administrative procedure.

    15.1.2.5.2 Accurate and Verifiable Criteria. The design calculations and criteria shall include an accurate and verifiable water supply.

    17.8.4 Testing and Inspection of Systems. Testing and inspection of sprinkler systems shall include, but are not limited to:

    Commercial:

    FLUSH-Witness Underground Supply Flush;

    ROUGH Inspection-Installation of Riser, System Piping, Head Locations and all Components, Hydrostatic Pressure Test;

    FINAL Inspection-Head Installation and Escutcheons, Inspectors Test Location and Flow, Main Drain Flow, FDC Location and Escutheon, Alarm Function, Spare Parts, Labeling of Components and Signage, System Completeness, Water Supply Pressure Verification, Evaluation of Any Unusual Parameter.

    (2) City of North Salt Lake

    A new Section (F)903.2.14 is added as follows:

    (F)903.2.14 Group R, Division 3 Occupancies. An automatic sprinkler system shall be installed throughout every dwelling in accordance with NFPA 13-D, when the following condition is present:

    1. The structure is over 6,200 square feet.

    Such sprinkler system shall be installed in basements, but need not be installed in garages, under eves, or in enclosed attic spaces, unless required by the fire chief.

    (3) Park City Corporation and Park City Fire District:

    (a) Section (F)903.2 is deleted and replaced with the following:

    (F)903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the location described in this section.

    All new construction having more than 6,000 square feet on any one floor, except R-3 occupancy.

    All new construction having more than two (2) stories, except R-3 occupancy.

    All new construction having three (3) or more dwelling units, including units rented or leased, and including condominiums or other separate ownership.

    All new construction in the Historic Commercial Business zone district, regardless of occupancy.

    All new construction and buildings in the General Commercial zone district where there are side yard setbacks or where one or more side yard setbacks is less than two and one half (2.5) feet per story of height.

    All existing building within the Historic District Commercial Business zone.

    (b) In Table 1505.1, the following is added as footnotes d and e:

    d. Wood roof covering assemblies are prohibited in R-3 occupancies in areas with a combined rating of more than 11 using Tables 1505.1.1 and 1505.1.2 with a score of 9 for weather factors.

    e. Wood roof covering assemblies shall have a Class A rating in occupancies other than R-3 in areas with a combined rating of more than 11 using Tables 1505.1.1 and 1505.1.2 with a score of 9 for weather factors. The owner of the building shall enter into a written and recorded agreement that the Class A rating of the roof covering assembly will not be altered through any type of maintenance process.


    TABLE 1505.1.1

    WILDFIRE HAZARD SEVERITY SCALE


         RATING SLOPE VEGETATION

           1 less than or equal to 10% Pinion-juniper

           2 10.1 - 20% Grass-sagebrush

           3 greater than 20% Mountain brush or softwoods



    TABLE 1505.1.2

    PROHIBITION/ALLOWANCE OF WOOD ROOFING


      Rating R-3 Occupancy All Other Occupancies


    less than or

    equal to 11 wood roof covering wood roof covering

                      assemblies per assemblies per

                      Table 1505.1 are Table 1505.1 are

                      allowed allowed


    greater than or

    equal to 12 wood roof covering wood roof covering

                      is prohibited assemblies with a

                                              Class A rating are

                                              allowed


    (c) Appendix C is adopted.

    (4) Sandy City

    (a) Section (F)903.2.14 is added as follows:

    (F)903.2.14 An automatic sprinkler system shall be installed in accordance with NFPA 13 throughout buildings containing all occupancies where fire flow exceeds 2,000 gallons per minute, based on Table B105.1 of the 2006 International Fire Code. Exempt locations as indicated in Section 903.3.1.1.1 are allowed.

    Exception: Automatic fire sprinklers are not required in buildings used solely for worship, Group R Division 3, Group U occupancies and buildings complying with the International Residential Code unless otherwise required by the International Fire Code.

    (b) Appendix L is added to the IBC and adopted as follows:

    Appendix L BUILDINGS AND STRUCTURES CONSTRUCTED IN AREAS DESIGNATED AS WILDLAND-URBAN INTERFACE AREAS

    AL 101.1 General. Buildings and structures constructed in areas designated as Wildland-Urban Interface Areas by Sandy City shall be constructed using ignition resistant construction as determined by the Fire Marshal. Section 502 of the 2006 International Wildland-Urban Interface Code (IWUIC), as promulgated by the International Code Council, shall be used to determine Fire Hazard Severity. The provisions listed in Chapter 5 of the 2006 International Wildland-Urban Interface Code, as modified herein, shall be used to determine the requirements for Ignition Resistant Construction.

    (i) In Section 504 of the IWUIC Class I IGNITION-RESISTANT CONSTRUCTION a new Section 504.1.1 is added as follows:

    504.1.1 General. Subsections 504.5, 504.6, and 504.7 shall only be required on the exposure side of the structure, as determined by the Fire Marshal, where defensible space is less than 50 feet as defined in Section 603 of the 2006 International Wildland-Urban Interface Code.

    (ii) In Section 505 of the IWUIC Class 2 IGNITION-RESISTANT CONSTRUCTION Subsections 505.5 and 505.7 are deleted.