R432-8-4. General Construction, Ancillary Support Facilities  


Latest version.
  • R432-4-23 applies with the following modifications:

    (1) Corridors. Corridors in patient use areas shall be a minimum six feet wide.

    (2) Door leaf width for patient room doors and doors to patient treatment rooms shall be a minimum three feet.

    (3) Ceiling finishes. Ceiling construction in patient and seclusion rooms shall be monolithic.

    (4) Bed pan flushing devices are optional.

    (5) Windows, in rooms intended for 24-hour occupancy, shall be operable.

    (6) Emergency Electrical Service.

    (a) An on-site emergency generator shall be provided.

    (b) The following services shall be connected to the emergency generator:

    (i) life safety branch, as defined in section 517-32 of the National Electric Code NFPA 70;

    (ii) critical branch, as defined in 517-33 of the National Electric Code NFPA 70;

    (iii) equipment system, as defined in 517-34 of the National Electric Code NFPA 70;

    (iv) telephone;

    (v) nurse call;

    (vi) heating equipment necessary to provide adequate heated space to house all patients under emergency conditions;

    (vii) one duplex convenience outlet in each patient bedroom;

    (viii) one duplex convenience outlet at each nurse station;

    (ix) duplex convenience outlets in the emergency heated area at a ratio of one for each ten patients.

    (6) Nurse Call System.

    (a) A nurse call system is optional.

    (b) If a nurse call system is installed, provisions shall be made for the easy removal or covering of call buttons.