Utah Administrative Code (Current through November 1, 2019) |
R432. Health, Family Health and Preparedness, Licensing |
R432-16. Hospice Inpatient Facility Construction |
R432-16-8. Service Requirements
-
(1) A nurse station shall be provided and have space for charting, storage, medication security, and administrative activities.
(2) Toilet room(s) with hand washing facilities for staff shall be provided and may be unisex.
(3) Hand washing facilities shall be located immediately adjacent to the nursing station and the drug distribution station.
(4) Provisions shall be made for 24-hour distribution of medications by providing a medicine preparation room or a self-contained medicine dispensing unit. If a medical cart is used it shall be under visual control of staff.
(5) A clean workroom or clean holding room shall be provided for resident care items.
(a) The clean work room shall contain a counter, hand washing facilities and storage facilities.
(b) The work counter and hand washing facilities may be omitted in rooms used only for storage and holding, as part of a larger system for distribution of clean and sterile supply materials.
(6) A soiled workroom shall be provided.
(a) The soiled workroom shall contain a clinical sink, a sink equipped for hand washing, a work counter, waste receptacles, and a linen receptacle.
(b) Hand washing sinks, clinical sinks, and work counters may be omitted in rooms used only for temporary holding of soiled, bagged material.
(c) In small hospice inpatient facilities, accommodations shall be available for cleaning and sanitizing patient service items.
(7) Clean linen shall be stored in a separate closet or room. If a closed cart is used for clean linen storage, it shall be stored in a room with a self closing door. Storage in an alcove in a corridor is prohibited. Clean linen may be stored in the clean work room or a clean holding room.
(8) Resident bathing facilities shall be provided in each hospice unit at a ratio of one bathing facility for each eight beds, or fraction thereof, not otherwise served by bathing facilities within individual resident rooms.
(a) Each resident bathtub or shower shall be in a separate room or enclosure large enough to ensure privacy and to allow staff to assist with bathing, drying, and dressing.
(b) A toilet and hand sink shall be provided at each common bathing area.
(9) An equipment storage room with a minimum area of five square feet for each licensed bed, but no less than 30 square feet, for portable equipment shall be provided.
(10) In small hospice inpatient facilities, accommodation shall be made for storage of portable equipment.