R313-28-200. Information on Radiation Shielding Required for Plan Reviews  


Latest version.
  • In order to evaluate a need for radiation shielding associated with a plan review, the following information shall be submitted to a Qualified Expert so that an adequate review may be performed.

    (1) The plans showing, as a minimum, the following:

    (a) the normal location of the radiation producing equipment's radiation port, the port's travel and traverse limits, general directions of the radiation beam, locations of windows, the location of the operator's booth, and the location of the x-ray control panel;

    (b) structural composition and thickness of walls, doors, partitions, floor, and ceiling of the rooms concerned;

    (c) the dimensions, including height, floor to floor, of the rooms concerned;

    (d) the type of occupancy of adjacent areas inclusive of space above and below the rooms concerned. If there is an exterior wall, show distance to the closest existing occupied areas;

    (e) the make and model of the x-ray equipment, the maximum energy output, and the energy waveform; and

    (f) the type of examination or treatment which will be performed with the equipment.

    (2) Information on the anticipated workload of the x-ray systems in mA-minutes per week.

    (3) A report showing all basic assumptions used in the development of the shielding specifications.