R156-56-711. Statewide Amendments to the IRC.  


Latest version.
  • The following are adopted as amendments to the IRC to be applicable statewide:

    (1) All amendments to the IBC under Section R156-56-704, local amendments under Section R156-56-705, the NEC under Section R156-56-706, the IPC under Section R156-56-707, the IMC under Section R156-56-708, the IFGC under Section R156-56-709 and the IECC under Section R156-56-710 which may be applied to detached one and two family dwellings and multiple single family dwellings shall be applicable to the corresponding provisions of the IRC. All references to the ICC Electrical Code are deleted and replaced with the National Electrical Code adopted under Section R156-56-701(1)(b).

    (2) Section 106.3.2 is deleted and replaced with the following:

    106.3.2 Previous approval. If a lawful permit has been issued and the construction of which has been pursued in good faith within 180 days after the effective date of the code and has not been abandoned, then the construction may be completed under the code in effect at the time of the issuance of the permit.

    (3) In Section 109, a new section is added as follows:

    R109.1.5 Weather-resistive barrier and flashing inspections. An inspection shall be made of the weather-resistive barrier as required by Section R703.1 and flashings as required by Section R703.8 to prevent water from entering the weather-resistant exterior wall envelope.

    The remaining sections are renumbered as follows:

    R109.1.6 Other inspections

    R109.1.6.1 Fire-resistance-rated construction inspection

    R109.1.6.2 Reinforced masonry, insulating concrete form (ICF) and conventionally formed concrete wall inspection

    R109.1.7 Final inspection.

    (4) Section R114.1 is deleted and replaced with the following:

    R114.1 Notice to owner. Upon notice from the building official that work on any building or structured is being prosecuted contrary to the provisions of this code or other pertinent laws or ordinances or in an unsafe and dangerous manner, such work shall be immediately stopped. The stop work order shall be in writing and shall be given to the owner of the property involved, or to the owner's agent or to the person doing the work; and shall state the conditions under which work will be permitted to resume.

    (5) In Section R202, the definition of "Backsiphonage" is deleted and replaced with the following:

    BACKSIPHONAGE: The backflow of potentially contaminated, polluted or used water into the potable water system as a result of the pressure in the potable water system falling below atmospheric pressure of the plumbing fixtures, pools, tanks or vats connected to the potable water distribution piping.

    (6) In Section R202 the following definition is added:

    CERTIFIED BACKFLOW PREVENTER ASSEMBLY TESTER: A person who has shown competence to test Backflow prevention assemblies to the satisfaction of the authority having jurisdiction under Subsection 19-4-104(4), Utah Code Ann. (1953), as amended.

    (7) In Section R202 the definition of "Cross Connection" is deleted and replaced with the following:

    CROSS CONNECTION. Any physical connection or potential connection or arrangement between two otherwise separate piping systems, one of which contains potable water and the other either water of unknown or questionable safety or steam, gas or chemical, whereby there exists the possibility for flow from one system to the other, with the direction of flow depending on the pressure differential between the two systems(see "Backflow, Water Distribution").

    (8) In Section R202 the following definition is added:

    HEAT exchanger (Potable Water). A device to transfer heat between two physically separated fluids (liquid or steam), one of which is potable water.

    (9) In Section R202 the definition of "Potable Water" is deleted and replaced with the following:

    POTABLE WATER. Water free from impurities present in amounts sufficient to cause disease or harmful physiological effects and conforming to the Titles 19-4 and 19-5, Utah Code Ann. (1953), as amended and the regulations of the public health authority having jurisdiction.

    (10) In Section R202, the following definition is added:

    S-Trap. A trap having it's weir installed above the inlet of the vent connection.

    (11) In Section R202 the definition of "Water Heater" is deleted and replaced with the following:

    WATER HEATER. A closed vessel in which water is heated by the combustion of fuels or electricity and is withdrawn for use externally to the system at pressures not exceeding 160 psig (1100 kPa (gage)), including the apparatus by which heat is generated, and all controls and devices necessary to prevent water temperatures from exceeding 210 degrees Fahrenheit (99 degrees Celsius).

    (12) Figure R301.2(5) is deleted and replaced with Table R301.2(5a) and Table R301.2(5b) as follows:


    TABLE NO. R301.2(5a)

    STATE OF UTAH - REGIONAL SNOW LOAD FACTORS


         COUNTY Po S Ao


         Beaver 43 63 6.2

         Box Elder 43 63 5.2

         Cache 50 63 4.5

         Carbon 43 63 5.2

         Daggett 43 63 6.5

         Davis 43 63 4.5

         Duchesne 43 63 6.5

         Emery 43 63 6.0

         Garfield 43 63 6.0

         Grand 36 63 6.5

         Iron 43 63 5.8

         Juab 43 63 5.2

         Kane 36 63 5.7

         Millard 43 63 5.3

         Morgan 57 63 4.5

         Piute 43 63 6.2

         Rich 57 63 4.1

         Salt Lake 43 63 4.5

         San Juan 43 63 6.5

         Sanpete 43 63 5.2

         Sevier 43 63 6.0

         Summit 86 63 5.0

         Tooele 43 63 4.5

         Uintah 43 63 7.0

         Utah 43 63 4.5

         Wasatch 86 63 5.0

         Washington 29 63 6.0

         Wayne 36 63 6.5

         Weber 43 63 4.5



    TABLE NO. R301.2(5b)

    RECOMMENDED SNOW LOADS FOR SELECTED UTAH CITIES AND TOWNS(2)


                                      Roof Snow Ground Snow

                                      Load (PSF) Load (PSF)


         Beaver County

            Beaver 5920 ft. 43 62

         Box Elder County

            Brigham City 4300 ft. 30 43

            Tremonton 4290 ft. 30 43

         Cache County

            Logan 4530 ft. 35 50

            Smithfield 4595 ft. 35 50

         Carbon County

            Price 5550 ft. 30 43

         Daggett County

            Manila 5377 ft. 30 43

         Davis County

            Bountiful 4300 ft. 30 43

            Farmington 4270 ft. 30 43

            Layton 4400 ft. 30 43

            Fruit Heights 4500 ft. 40 57

         Duchesne County

            Duchesne 5510 ft. 30 43

            Roosevelt 5104 ft. 30 43

         Emery County

            Castledale 5660 ft. 30 43

            Green River 4070 ft. 25 36

         Garfield County

            Panguitch 6600 ft. 30 43

         Grand County

            Moab 3965 ft. 25 36

         Iron County

            Cedar City 5831 ft. 30 43

         Juab County

            Nephi 5130 ft. 30 43

         Kane County

            Kanab 5000 ft. 25 36

         Millard County

            Millard 5000 ft. 30 43

            Delta 4623 ft. 30 43

         Morgan County

            Morgan 5064 ft. 40 57

         Piute County

            Piute 5996 ft. 30 43

         Rich County

            Woodruff 6315 ft. 40 57

         Salt Lake County

            Murray 4325 ft. 30 43

            Salt Lake City 4300 ft. 30 43

            Sandy 4500 ft. 30 43

            West Jordan 4375 ft. 30 43

            West Valley 4250 ft. 30 43

         San Juan County

            Blanding 6200 ft. 30 43

            Monticello 6820 ft. 35 50

         Sanpete County

            Fairview 6750 ft. 35 50

            Mt. Pleasant 5900 ft. 30 43

            Manti 5740 ft. 30 43

            Ephraim 5540 ft. 30 43

            Gunnison 5145 ft. 30 43

         Sevier County

            Salina 5130 ft. 30 43

            Richfield 5270 ft. 30 43

         Summit County

            Coalville 5600 ft. 60 86

            Kamas 6500 ft. 70 100

            Park City 6800 ft. 100 142

            Park City 8400 ft. 162 231

            Summit Park 7200 ft. 90 128

         Tooele County

            Tooele 5100 ft. 30 43

         Uintah County

            Vernal 5280 ft. 30 43

         Utah County

            American Fork 4500 ft. 30 43

            Orem 4650 ft. 30 43

            Pleasant Grove 5000 ft. 30 43

            Provo 5000 ft. 30 43

           Spanish Fork 4720 ft. 30 43

         Wasatch County

           Heber 5630 ft. 60 86

         Washington County

           Central 5209 ft. 25 36

           Dameron 4550 ft. 25 36

           Leeds 3460 ft. 20 29

           Rockville 3700 ft. 25 36

           Santa Clara 2850 ft. 15 (1) 21

           St. George 2750 ft. 15 (1) 21

         Wayne County

           Loa 7080 ft. 30 43

           Hanksville 4308 ft. 25 36

         Weber County

           North Ogden 4500 ft. 40 57

           Ogden 4350 ft. 30 43


    NOTES

        (1) The IRC requires a minimum live load - See R301.6.

        (2) This table is informational only in that actual site

    elevations may vary. Table is only valid if site elevation

    is within 100 feet of the listed elevation.


    (13) Section R301.6 is deleted and replaced with the following:

    R301.6 Utah Snow Loads. The ground snow load, Pg, to be used in the determination of design snow loads for buildings and other structures shall be determined by using the following formula: Pg = (Po2 + S2(A-Ao)2)0.5 for A greater than Ao, and Pg = Po for A less than or equal to Ao.

    WHERE

    Pg = Ground snow load at a given elevation (psf)

    Po = Base ground snow load (psf) from Table No. R301.2(5a)

    S = Change in ground snow load with elevation (psf/100 ft.) From Table No. R301.2(5a)

    A = Elevation above sea level at the site (ft./1000)

    Ao = Base ground snow elevation from Table R301.2(5a) (ft./1000)

    The building official may round the roof snow load to the nearest 5 psf. The ground snow load, Pg, may be adjusted by the building official when a licensed engineer or architect submits data substantiating the adjustments. A record of such action together with the substantiating data shall be provided to the division for a permanent record.

    The building official may also directly adopt roof snow loads in accordance with Table R301.2(5b), provided the site is no more than 100 ft. higher than the listed elevation.

    Where the minimum roof live load in accordance with Table R301.6 is greater than the design roof snow load, such roof live load shall be used for design, however, it shall not be reduced to a load lower than the design roof snow load. Drifting need not be considered for roof snow loads less than 20 psf.

    (14) Section R304.3 is deleted and replaced with the following:

    R304.3 Minimum dimensions. Habitable rooms shall not be less than 7 feet (2134 mm) in any horizontal dimension.

    Exception: Kitchens shall have a clear passageway of not less than 3 feet (914 mm) between counter fronts and appliances or counter fronts and walls.

    (15) Section R311.5.3 is deleted and replaced with the following:

    R311.5.3 Stair treads and risers.

    R311.5.3.1 Riser height. The maximum riser height shall be 8 inches (203 mm). The riser shall be measured vertically between leading edges of the adjacent treads. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm).

    R311.5.3.2 Tread depth. The minimum tread depth shall be 9 inches (228 mm). The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). Winder treads shall have a minimum tread depth of 10 inches (254 mm) measured as above at a point 12 inches (305 mm) from the side where the treads are narrower. Winder treads shall have a minimum tread depth of 6 inches (152 mm) at any point. Within any flight of stairs, the greatest winder tread depth at the 12 inch (305 mm) walk line shall not exceed the smallest by more than 3/8 inch (9.5 mm).

    R311.5.3.3 Profile. The radius of curvature at the leading edge of the tread shall be no greater than 9/16 inch (14.3 mm). A nosing not less than 3/4 inch (19 mm) but not more than 1 1/4 inches (32 mm) shall be provided on stairways with solid risers. The greatest nosing projection shall not exceed the smallest nosing projection by more than 3/8 inches (9.5 mm) between two stories, including the nosing at the level of floors and landings. Beveling of nosing shall not exceed 1/2 inch (12.7 mm). Risers shall be vertical or sloped from the underside of the leading edge of the tread above at an angle not more than 30 degrees (0.51 rad) from the vertical. Open risers are permitted, provided that the opening between treads does not permit the passage of a 4-inch diameter (102 mm) sphere.

    Exceptions.

    1. A nosing is not required where the tread depth is a minimum of 10 inches (254 mm).

    2. The opening between adjacent treads is not limited on stairs with a total rise of 30 inches (762 mm) or less.

    (16) Section R313 is deleted and replaced with the following:

    Section R313 SMOKE AND CARBON MONOXIDE ALARMS

    R313.1 Single- and multiple-station smoke alarms. Single- and multiple-station smoke alarms shall be installed in the following locations:

    1. In each sleeping room.

    2. Outside of each separate sleeping area in the immediate vicinity of the bedrooms.

    3. On each additional story of the dwelling, including basements and cellars but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.

    All smoke alarms shall be listed and installed in accordance with the provisions of this code and the household fire warning equipment provision of NFPA 72.

    R313.2 Carbon monoxide alarms. In new residential structures regulated by this code that are equipped with fuel burning appliances, carbon monoxide alarms shall be installed on each habitable level. All carbon monoxide detectors shall be listed and comply with U.L. 2034 and shall be installed in accordance with provisions of this code and NFPA 720.

    R313.3 Interconnection of alarms. When multiple alarms are required to be installed within an individual dwelling unit, the alarm devices shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed. Approved combination smoke- and carbon-monoxide detectors shall be permitted.

    R313.4 Power source. In new construction, the required alarms shall receive their primary power from the building wiring when such wiring is served from a commercial source, and when primary power is interrupted, shall receive power from a battery. Wiring shall be permanent and without a disconnecting switch other than those required for overcurrent protection. Alarms shall be permitted to be battery operated when installed in buildings without commercial power or in buildings that undergo alterations, repairs, or additions regulated by Section R313.5

    R313.5 Alterations, repairs and additions. When interior alterations, repairs or additions requiring a permit occur, or when one or more sleeping rooms are added or created in existing dwellings, the individual dwelling unit shall be provided with alarms located as required for new dwellings; the alarms shall be interconnected and hard wired.

    Exceptions:

    1. Alarms in existing areas shall not be required to be interconnected and hard wired where the alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space, or basement available which could provide access for hard wiring and interconnection without the removal of interior finishes.

    2. Repairs to the exterior surfaces of dwellings are exempt from the requirements of this section.

    (17) In Section R403.1.6 exception 4 is added as follows: 4. When anchor bolt spacing does not exceed 32 inches (813 mm) apart, anchor bolts may be placed with a minimum of two bolts per plate section located not less than 4 inches (102 mm) from each end of each plate section at interior bearing walls, interior braced wall lines and at all exterior walls.

    (18) In Section R403.1.6.1 the following exception is added at the end of Item 2 and Item 3:

    Exception: When anchor bolt spacing does not exceed 32 inches (816 mm) apart, anchor bolts may be placed with a minimum of two bolts per plate section located not less than 4 inches (102 mm) from each end of each plate section at interior bearing walls, interior braced wall lines and at all exterior walls.

    (19) New Sections R404.0, R404.0.1 and R404.0.2 are added before Section 404.1 as follows:

    R404.0 This section may be used as an alternative to complying with Sections R404.1 through R404.1.5.1.

    R404.0.1 Concrete and masonry foundation walls. Concrete and masonry foundation walls may be designed in accordance with IBC Chapters 19 or 21 respectively. Foundation walls that are laterally supported at the top and bottom within the parameters of IBC Tables 1805.5(1) through 1805.5(5) are permitted to be designed and constructed in accordance with IBC Sections 1805.5.1 through 1805.5.5. Concrete foundation walls may also be constructed in accordance with Section R404.0.2.

    R404.0.2 Empirical foundation design. Buildings constructed with repetitive wood frame construction or repetitive cold-formed steel structural member construction may be permitted to have concrete foundations constructed in accordance with IBC Table 1805.5(6). IBC Table 1805.5(6) entitled "Empirical Foundations Walls", dated January 1, 2007, published by the Department of Commerce, Division of Occupational and Professional Licensing, is hereby adopted and incorporated by reference. Table 1805.5(6) identifies foundation requirements for empirical walls.

    (20) Section R703.6 is deleted and replaced with the following:

    R703.6 Exterior plaster.

    R703.6.1 Lath. All lath and lath attachments shall be of corrosion-resistant materials. Expanded metal or woven wire lath shall be attached with 1 1/2 inch-long (38 mm), 11 gage nails having 7/16 inch (11.1 mm) head, or 7/8-inch-long (22.2 mm), 16 gage staples, spaced at no more than 6 inches (152 mm), or as otherwise approved.

    R703.6.2 Weather-resistant barriers. Weather-resistant barriers shall be installed as required in Section R703.2 and, where applied over wood-based sheathing, shall include a weather-resistive vapor permeable barrier with a performance at least equivalent to two layers of Grade D paper.

    R703.6.3 Plaster. Plastering with portland cement plaster shall be not less than three coats when applied over metal lath or wire lath and shall be not less than two coats when applied over masonry, concrete or gypsum backing. If the plaster surface is completely covered by veneer or other facing material or is completely concealed, plaster application need be only two coats, provided the total thickness is as set forth in Table R702.1(1). On wood-frame construction with an on-grade floor slab system, exterior plaster shall be applied in such a manner as to cover, but not extend below, lath, paper and screed.

    The proportion of aggregate to cementitious materials shall be as set forth in Table R702.1(3).

    R703.6.3.1 Weep screeds. A minimum 0.019-inch (0.5 mm) (No. 26 galvanized sheet gage), corrosion-resistant weep screed or plastic weep screed, with a minimum vertical attachment flange of 3 1/2 inches (89 mm) shall be provided at or below the foundation plate line on exterior stud walls in accordance with ASTM C 926. The weep screed shall be placed a minimum of 4 inches (102 mm) above the earth or 2 inches (51 mm) above paved areas and shall be of a type that will allow trapped water to drain to the exterior of the building. The weather-resistant barrier shall lap the attachment flange. The exterior lath shall cover and terminate on the attachment flange of the weep screed.

    (21) In Section R703.8, number 8 is added as follows:

    8. At the intersection of foundation to stucco, masonry, siding, or brick veneer with an approved corrosive-resistance flashing with a 1/2" drip leg extending past exterior side of the foundation.

    (22) A new Section G2401.2 is added as follows:

    G2401.2 Meter Protection. Fuel gas services shall be in an approved location and/or provided with structures designed to protect the fuel gas meter and surrounding piping from physical damage, including falling, moving, or migrating ice and snow. If an added structure is used, it must provide access for service and comply with the IBC or the IRC.

    (23) In Section G2413.1(402.1) General Considerations, the following sentence is added at the end of the section:

    In residential occupancies, natural gas service lines shall be no less than 1 inch (25 mm) in diameter.

    (24) Section P2602.3 is added as follows:

    P2602.3 Individual water supply. Where a potable public water supply is not available, individual sources of potable water supply shall be utilized provided that the source has been developed in accordance with Sections 73-3-1 and 73-3-25, Utah Code Ann. (1953), as amended, as administered by the Department of Natural Resources, Division of Water Rights. In addition, the quality of the water shall be approved by the local health department having jurisdiction.

    (25) Section P2602.4 is added as follows:

    P2602.4 Sewer required. Every building in which plumbing fixtures are installed and all premises having drainage piping shall be connected to a public sewer where the sewer is within 300 feet of the property line in accordance with Section 10-8-38, Utah Code Ann, (1953), as amended; or an approved private sewage disposal system in accordance with Rule R317, Chapter 4, Utah Administrative Code, as administered by the Department of Environmental Quality, Division of Water Quality.

    (26) Section P2603.2.1 is deleted and replaced with the following:

    P2603.2.1 Protection against physical damage. In concealed locations where piping, other than cast-iron or galvanized steel, is installed through holes or notches in studs, joists, rafters, or similar members less than 1 1/2 inch (38 mm) from the nearest edge of the member, the pipe shall be protected by shield plates. Protective shield plates shall be a minimum of 1/16 inch-thick (1.6 mm) steel, shall cover the area of the pipe where the member is notched or bored, and shall be at least the thickness of the framing member penetrated.

    (27) In Section P2801.7 the word townhouses is deleted.

    (28) Section P2902.1.1 is added as follows:

    P2902.1.1 Backflow assembly testing. The premise owner or his designee shall have backflow prevention assemblies operation tested at the time of installation, repair and relocation and at least on an annual basis thereafter, or more frequently as required by the authority having jurisdiction. Testing shall be performed by a Certified Backflow Preventer Assembly Tester. The assemblies that are subject to this paragraph are the Spill Resistant Vacuum Breaker, the Pressure Vacuum Breaker Assembly, the Double Check Backflow Prevention Assembly, the Double Check Detector Assembly Backflow Preventer, the Reduced Pressure Principle Backflow Preventer, and Reduced Pressure Detector Assembly.

    (29) Table P2902.3 is deleted and replaced with the following:


    TABLE P2902.3

    General Methods of Protection


    Assembly Degree Application Installation Criteria

    (applicable of

    standard) Hazard

    Air Gap High or Backsiphonage See Table P2902.3.1

    (ASME A112.1.2) Low


    Reduced High or Backpressure or a. The bottom of each

    Pressure Low Backsiphonage RP assembly shall

    Principle Backflow 1/2" - 16" be a minimum of 12

    Preventer (AWWA inches above the

    C511, USC-FCCCHR, ground or floor.

    ASSE 1013 b. RP assemblies shall

    CSA CNA/CSA-B64.4) NOT be installed in

    and Reduced Pressure a pit.

    Detector Assembly c. The relief valve on

    (ASSE 1047, USC- each RP assembly

    FCCCHR) shall not be

                                                 directly connected

                                                 to any waste

                                                 disposal line,

                                                 including sanitary

                                                 sewer, storm drains,

                                                 or vents.

                                              d. The assembly shall

                                                 be installed in a

                                                 horizontal position

                                                 only unless listed

                                                 or approved for

                                                 vertical

                                                 installation.


    Double Check Low Backpressure or a. If installed in a

    Backflow Backsiphonage pit, the DC assembly

    Prevention 1/2" - 16" shall be installed

    Assembly with a minimum of

    (AWWA C510, 12 inches of

    USC-FCCCHR, clearance between

    ASSE 1015) all sides of the

    Double Check vault including

    Detector Assembly the floor and roof

    Backflow Preventer or ceiling with

    (ASSE 1048, adequate room for

    USC-FCCCHR) testing and

                                                 maintenance.

                                              b. Shall be installed

                                                 in a horizontal

                                                 position unless

                                                 listed or approved

                                                 for vertical

                                                 installation.


    Pressure High or Backsiphonage a. Shall not be

    Vacuum Low 1/2" - 2" installed in an

    Breaker area that could be

    Assembly subjected to

    (ASSE 1020, backpressure or

    USC-FCCCHR) back drainage

                                                 conditions.

                                              b. Shall be installed

                                                 a minimum of 12

                                                 inches above all

                                                 downstream piping

                                                 and the highest

                                                 point of use.

                                              c. Shall not be

                                                 installed below

                                                 ground or in a

                                                 vault or pit.

                                              d. Shall be installed

                                                 in a vertical

                                                 position only.


    Spill High or Backsiphonage a. Shall not be

    Resistant Low 1/4" - 2" installed in an

    Vacuum area that could

    Breaker be subjected to

    (ASSE 1056, backpressure or

    USC-FCCCHR) back drainage

                                                 conditions.

                                              b. Shall be installed

                                                 a minimum of 12

                                                 inches above all

                                                 downstream piping

                                                 and the highest

                                                 point of use.

                                              c. Shall not be

                                                 installed below

                                                 ground or in a

                                                 vault or pit.

                                              d. Shall be installed

                                                 in a vertical

                                                 position only.


    Atmospheric High or Backsiphonage a. Shall not be

    Vacuum Low installed in an

    Breaker area that could be

    (ASSE 1001 subjected to

    USC-FCCCHR, backpressure or back

    CSA CAN/CSA-B64.1.1 drainage conditions.

                                              b. Shall not be

                                                 installed where it

                                                 may be subjected to

                                                 continuous pressure

                                                 for more than 12

                                                 consecutive hours

                                                 at any time.

                                              c. Shall be installed

                                                 a minimum of six

                                                 inches above all

                                                 downstream piping

                                                 and the highest

                                                 point of use.

                                              d. Shall be installed

                                                 on the discharge

                                                 (downstream) side

                                                 of any valves.

                                              e. The AVB shall be

                                                 installed in a

                                                 vertical position

                                                 only.


    General The assembly owner,

    Installation when necessary,

    Criteria shall provide

                                                 devices or

                                                 structures to

                                                 facilitate testing,

                                                 repair, and/or

                                                 maintenance and to

                                                 insure the safety

                                                 of the backflow

                                                 technician.

                                                 Assemblies shall

                                                 not be installed

                                                 more than five feet

                                                 off the floor unless

                                                 a permanent platform

                                                 is installed.


                                                 The body of the

                                                 assembly shall not

                                                 be closer than 12

                                                 inches to any wall,

                                                 ceiling or

                                                 incumbrance, and

                                                 shall be accessible

                                                 for testing, repair

                                                 and/or maintenance.

                                                 In cold climates,

                                                 assemblies shall be

                                                 protected from

                                                 freezing by a means

                                                 acceptable to the

                                                 code official.


                                                 Assemblies shall

                                                 be maintained as

                                                 an intact assembly.


    (30) Table 2902.3a is added as follows:

    TABLE 2902.3a

    Specialty Backflow Devices for low hazard use only


         Device Degree of Application Applicable

                         Hazard Standard


    Antisiphon-type Low Backsiphonage ASSE 1002

    Water Closet Flush CSA CAN/

    Tank Ball Cock CSA-B125


    Dual check valve Low Backsiphonage ASSE 1024

    Backflow Preventer or Backpressure

                                       1/4" - 1"


    Backflow Preventer Low Backsiphonage ASSE 1012

    with Intermediate Residential or Backpressure CSA CAN/

    Atmospheric Vent Boiler 1/4" - 3/4" CSA-B64.3


    Dual check valve Low Backsiphonage ASSE 1022

    type Backflow or Backpressure

    Preventer for 1/4" - 3/8"

    Carbonated Beverage

    Dispensers/Post

    Mix Type


    Hose-connection Low Backsiphonage ASSE 1011

    Vacuum Breaker 1/2", 3/4", 1" CSA CAN/

                                                       CSA-B64.2


    Vacuum Breaker Low Backsiphonage ASSE 1019

    Wall Hydrants, 3/4", 1" CSA CAN/

    Frost-resistant, CSA-B64.2.2

    Automatic Draining

    Type


    Laboratory Faucet Low Backsiphonage ASSE 1035

    Backflow Preventer CSA CAN/

                                                       CSA-B64.7


    Hose Connection Low Backsiphonage ASSE 1052

    Backflow Preventer 1/2" - 1"

    Installation Guidelines: The above specialty devices shall

    be installed in accordance with their listing and the

    manufacturer's instructions and the specific provisions of

    this chapter.


    (31) Section P3003.2.1 is added as follows:

    Section P3003.2.1 Improper Connections. No drain, waste, or vent piping shall be drilled and tapped for the purpose of making connections.

    (32) In Section P3103.6, the following sentence is added at the end of the paragraph:

    Vents extending through the wall shall terminate not less than 12 inches from the wall with an elbow pointing downward.

    (33) In Section P3104.4, the following sentence is added at the end of the paragraph:

    Horizontal dry vents below the flood level rim shall be permitted for floor drain and floor sink installations when installed below grade in accordance with Chapter 30, and Sections P3104.2 and P3104.3. A wall cleanout shall be provided in the vertical vent.

    (34) Chapter 43, Referenced Standards, is amended as follows:

    The following reference standard is added:


    TABLE


    USC- Foundation for Cross-Connection Table P2902.3

    FCCCHR Control and Hydraulic Research

    9th University of Southern California

    Edition Kaprielian Hall 300

    Manual Los Angeles CA 90089-2531

    of Cross

    Connection

    Control


    (35) In Chapter 43, the following standard is added under NFPA as follows:


    TABLE


    720-05 Recommended Practice for the Installation R313.2

             of Household Carbon Monoxide (CO) Warning

             Equipment