    Purpose of the rule or reason for the change:

    The purpose of this amendment is to clarify, simplify, and justify how sewers will be regulated within source protection zones and management areas for new wells and springs.

    Summary of the rule or change:

    In the amended rule, sewers within unprotected aquifers in zones one and two must be 50 feet from the well or spring collection area and and be constructed in accordance with Section R309-515-6. Sewers in zone one of protected aquifers must be at least 10 feet from the well and constructed in accordance with Section R309-515-6. Previously, the rule required that at least 5 feet of suitable soils be present below the sewer and above the water table or bedrock and be constructed in accordance with Section R309-515-6, or be at least 300 feet from the well or spring collection area and be constructed in accordance with Section R309-515-6. "Suitable soils" was not well defined, so emphasis has been changed to protected versus unprotected aquifers as defined in Rule R309-600.

    State statutory or constitutional authorization for this rule:

    Anticipated cost or savings to:

    the state budget:

    There should be no additional cost or savings from this rule change. The amount of time state staff spends reviewing and approving projects will not be affected.

    local governments:

    There should be no additional cost or savings from this rule change. The rule change for local governments, which often own water systems, will make it easier to understand what is required with regard to sewer systems, when developing new sources of drinking water.

    small businesses:

    There should be no additional cost or savings from this rule change. The rule change for small businesses, which are often the owners of water systems, will make it easier to understand what is required with regard to sewer systems, when developing new sources of drinking water.

    persons other than small businesses, businesses, or local governmental entities:

    There should be no additional cost or savings from this rule change. The rule change for persons, who might be the owners of a water system, will make it easier to understand what is required with regard to sewer systems, when developing new sources of drinking water.

    Compliance costs for affected persons:

    No additional costs--The rule change for persons, who might be the owners of a water system, will make it easier to understand what is required with regard to sewer systems, when developing new sources of drinking water.

    Comments by the department head on the fiscal impact the rule may have on businesses:

    The rule change clarifies, simplifies, and justifies how sewers will be handled within source protection zones and management areas, for water systems developing new sources of drinking water and there will be no additional costs involved in this rule change on affected water systems.

    Amanda Smith, Executive Director

    The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:

    Environmental Quality
    Drinking WaterRoom Third Floor
    195 N 1950 W
    SALT LAKE CITY, UT 84116-3085

    Direct questions regarding this rule to:

    Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:

    09/14/2012

    This rule may become effective on:

    09/21/2012

    Authorized by:

    Ken Bousfield, Director

    RULE TEXT

    R309. Environmental Quality, Drinking Water.

    R309-600. Source Protection: Drinking Water Source Protection For Ground-Water Sources.

    R309-600-13. New Ground-water Sources of Drinking Water.

    (1) Prior to constructing a new ground-water source of drinking water, each PWS shall develop a PER which demonstrates whether the source meets the requirements of this section and submit it to DDW. Additionally, engineering information in accordance with R309-515-6(5)(a) or R309-515-7(4) must be submitted to DDW. The Executive Secretary will not grant plan approval until both source protection and engineering requirements are met. Construction standards relating to protection zones and management areas (fencing, diversion channels, sewer line construction, and grouting, etc.) are found in R309-515. After the source is constructed a DWSP Plan must be developed, submitted, and implemented accordingly.

    (2) Preliminary Evaluation Report for New Sources of Drinking Water - PERs shall cover all four zones or the entire management area. PERs should be developed in accordance with the "Standard Report Format for New Wells and Springs." This document may be obtained from DDW. PWSs shall include the following four sections in each PER:

    (a) Delineation Report for Estimated DWSP Zones - The same requirements apply as in R309-600-9(6), except that the hydrogeologic data for the PER must be developed using the best available data which may be obtained from: surrounding wells, published information, or surface geologic mapping. PWSs must use the Preferred Delineation Procedure to delineate protection zones for new wells. The Delineation Report for Estimated DWSP Zones shall be stamped and signed by a professional geologist or professional engineer unless the Optional Two-Mile Radius Delineation Procedure is used for a new spring.

    (b) Inventory of Potential Contamination Sources and Identification and Assessment of Controls - The same requirements apply as in R309-600-10(1) and (2). Additionally, the PER must demonstrate that the source meets the following requirements:

    (i) Protection Areas Delineated using the Preferred Delineation Procedure in Protected Aquifers - A PWS shall not locate a new ground-water source of drinking water where an uncontrolled potential contamination source or a pollution source exists within zone one.

    (ii) Protection Areas Delineated using the Preferred Delineation Procedure in Unprotected Aquifers - A PWS shall not locate a new ground-water source of drinking water where an uncontrolled potential contamination source or an uncontrolled pollution source exists within zone one. Additionally, a new ground-water source of drinking water may not be located where a pollution source exists within zone two unless the pollution source implements design standards which prevent contaminated discharges to ground water.

    (iii) Management Areas Delineated using the Optional Two-Mile Radius Delineation Procedure - A PWS shall not locate a new spring where an uncontrolled potential contamination source or a pollution source exists within zone one. Additionally, a new spring may not be located where a pollution source exist within the management area unless: a hydrogeologic report in accordance with R309-600-9(6)(b)(ii) which verifies that it does not impact the spring; or the pollution source implements design standards which prevent contaminated discharges to ground water.

    (c) Land Ownership Map - A land ownership map which includes all land within zones one and two or the entire management area. Additionally, include a list which exclusively identifies the land owners in zones one and two or the management area, the parcel(s) of land which they own, and the zone in which they own land. A land ownership map and list are not required if ordinances are used to protect these areas.

    (d) Land Use Agreements, Letters of Intent, or Zoning Ordinances - Land use agreements which meet the requirements of the definition in R309-600-6(1)(p). Zoning ordinances which are already in effect or letters of intent may be substituted for land use agreements; however, they must accomplish the same level of protection that is required in a land use agreement. Letters of intent must be notarized, include the same language that is required in land use agreements, and contain the statement that "the owner agrees to record the land use agreement in the county recorder's office, if the source proves to be an acceptable drinking water source." The PWS shall not introduce a new source into its system until copies of all applicable recorded land use agreements are submitted to DDW.

    (3) Sewers Within DWSP Zones and Management Areas - Sewer lines may not be located within zones one and two or a management area unless the criteria identified below are met. If sewer lines are located or planned to be located within zones one and two or a management area, the PER must demonstrate that they comply with [this]these criteria. Sewer lines that comply with these criteria may be assessed as adequately controlled potential contamination sources.

    [(a) Zone One - If the conditions specified in R309-600-13(3)(a)(i and ii) below are met, all sewer lines within zone one shall be constructed in accordance with R309-515-6(4) and must be at least 10 feet from the wellhead.

    (i) There is at least 5 feet of suitable soil between the bottom of the sewer lines and the top of the maximum seasonal ground-water table or perched water table. (Suitable soils contain adequate sand/silt/clay to act as an effective effluent filter within its depth for the removal of pathogenic organisms and fill the voids between coarse particles such as gravel, cobbles, and angular rock fragments); and

    (ii) there is at least 5 feet of suitable soil between the bottom of the sewer line and the top of any bedrock formations or other unsuitable soils. Bedrock formations include formations that have such a low permeability that they prevent the downward passage of effluent. Bedrock formations that have open joints or solution channels, which permit such rapid flow that effluent is not renovated, are also considered unacceptable. Other unsuitable soils include those with coarse particles such as gravel, cobbles, or angular rock fragments with insufficient soil to fill the voids between the particles. Solid or fractured bedrock such as shale, sandstone, limestone, basalt, or granite are unacceptable.

    (b) Zones One and Two - If the conditions identified in R309-600-13(3)(a)(i and ii) above cannot be met, any sewer lines within zones one and two or a management area shall be constructed in accordance with R309-515-6(4) and must be at least 300 feet from the wellhead or margin of the collection area.](a) Unprotected Aquifers -

    (i) Zone one- all sewer lines and laterals shall be at least 50 feet from the wellhead or margin of the collection area, and be constructed in accordance to R309-515-6.

    (ii) Zone two- all sewer lines and laterals within zone two or a management area shall be constructed in accordance with R309-515-6.

    (b) Protected Aquifers - in zone one all sewer lines and laterals shall be constructed in accordance with R309-515-6, and shall be at least 10 feet from the wellhead or margin of the collection area.

    (4) Use waivers for the VOC and pesticide parameter groups may be issued if the inventory of potential contamination sources indicates that the chemicals within these parameter groups are not used, disposed, stored, transported, or manufactured within zones one, two, and three or the management area.

    (5) Replacement Wells - A PER is not required for proposed wells, if the PWS receives written notification from the Executive Secretary that the well is classified as a replacement well. The PWS must submit a letter requesting that the well be classified as a replacement well and include documentation to show that the conditions required in R309-600-6(1)(y) are met. If a proposed well is classified as a replacement well, the PWS is still required to submit and obtain written approval for all other information as required in:

    (a) DWSP Plan for New Sources of Drinking Water (refer to R309-600-13(6), and

    (b) the Outline of Well Approval Process (refer to R309-515-6(5)).

    (6) DWSP Plan for New Sources of Drinking Water - The PWS shall submit a DWSP Plan in accordance with R309-600-7(1) for any new ground-water source of drinking water within one year after the date of the Executive Secretary's concurrence letter for the PER. In developing this DWSP Plan, PWSs shall refine the information in the PER by applying any new, as-constructed characteristics of the source (i.e., pumping rate, aquifer test, etc.).

     

    KEY: drinking water, environmental health

    Date of Enactment or Last Substantive Amendment: [October 29, 2003]2012

    Notice of Continuation: March 17, 2010

    Authorizing, and Implemented or Interpreted Law: 19-4-104(1)(a)(iv)

     


Document Information

Effective Date:
9/21/2012
Publication Date:
08/15/2012
Filed Date:
07/30/2012
Agencies:
Environmental Quality,Drinking Water
Rulemaking Authority:

Subsection 19-4-104(1)(a)(ii)

Authorized By:
Ken Bousfield, Director
DAR File No.:
36561
Related Chapter/Rule NO.: (1)
R309-600-13. New Ground-water Sources of Drinking Water.