No. 32812 (Amendment): R309-215. Monitoring and Water Quality: Treatment Plant Monitoring Requirements
DAR File No.: 32812
Filed: 07/09/2009, 04:33
Received by: NLRULE ANALYSIS
Purpose of the rule or reason for the change:
This rule change is to address the changes required by the Groundwater Requirements (Section R309-215-16). There are a total of seven amendments that address these rules (Rules R309-100, R309-105, R309-110, R309-205, R309-215, R309-220, and R309-225). This rule adoption is necessary to maintain primacy. (DAR NOTE: The proposed amendment to Rule R309-100 is under DAR No. 32806, to Rule R309-105 is under DAR No. 32807, to Rule R309-110 is under DAR No. 32808, to Rule R309-205 is under DAR No. 32810, to Rule R309-215 is under DAR No. 32812, to Rule R309-220 is under DAR No. 32813, and to Rule R309-225 is under DAR No. 32814 all in this issue, August 1, 2009, of the Bulletin.)
Summary of the rule or change:
This change incorporates the requirements of the Groundwater Requirements (Section R309-215-16) that address general requirements, monitoring, reporting, and record keeping.
State statutory or constitutional authorization for this rule:
Section 19-4-104, and 40 CFR 141 subpart S
Anticipated cost or savings to:
the state budget:
Costs for the state budget, local governments, and other persons will be based on an aggregate for the changes in Rules R309-100, R309-105, R309-110, R309-205, R309-215, R309-220, and R309-225. The Environmental Protection Agency (EPA) estimates state costs to be $11,700,000 annually. Using the percentage of Utah systems versus the national total (approximately 1%), Utah's annual impact is approximately $117,000.
local governments:
For this rule change, aggregate costs will vary by type of water source, type of treatment, and physical facility deficiencies. EPA estimates the total national annual cost at $50,600,000. Using the percentage of Utah systems versus the national total, Utah's systems' impact is estimated to be $506,000 annually.
small businesses and persons other than businesses:
Other persons that own and operate a public water system may have the same cost impact as listed in "local government" above. Costs to consumers will vary depending upon the water system size. EPA estimates the costs to vary from $0.21 to $82.21 per household per year. The highest costs are associated with the small water systems that have to complete corrective actions. Persons that own and operate a public water system may have the same costs impact as listed under "local government" above.
Compliance costs for affected persons:
Aggregate compliance costs for the rule change will vary depending upon the water system size, type of source, type of treatment, and physical facility deficiencies. EPA estimates the costs to vary from $0.21 to $82.21 per household per year. The highest costs are associated with the small water systems that have to complete corrective actions. Persons that own and operate a public water system may have the same costs impact as listed under "local government" above.
Comments by the department head on the fiscal impact the rule may have on businesses:
The Department of Environmental Quality agrees with the comments in the cost and compliance summaries above. Amanda Smith, Acting Executive Director
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:
Environmental Quality
Drinking Water
150 N 1950 W
SALT LAKE CITY UT 84116-3085Direct questions regarding this rule to:
Rachael Cassady at the above address, by phone at 801-536-4467, by FAX at 801-536-4211, or by Internet E-mail at rcassady@utah.gov
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:
08/31/2009
This rule may become effective on:
09/07/2009
Authorized by:
Ken Bousfield, Director
RULE TEXT
R309. Environmental Quality, Drinking Water.
R309-215. Monitoring and Water Quality: Treatment Plant Monitoring Requirements.
R309-215-1. Purpose.
The purpose of this rule is to outline the monitoring and reporting requirements for public water systems which treat water prior to providing it for human consumption.
R309-215-2 Authority.
R309-215-3 Definitions.
R309-215-4 General.
R309-215-5 Monitoring Requirements for Groundwater Disinfection.
R309-215-6 Monitoring Requirements for Miscellaneous Treatment Plants.
R309-215-7 Surface Water Treatment Plant Evaluations.
R309-215-8 Surface Water Treatment Plant Monitoring and Reporting.
R309-215-9 Turbidity Monitoring and Reporting.
R309-215-10 Residual Disinfectant Monitoring.
R309-215-11 Waterborne Disease Outbreak.
R309-215-12 Monitoring Requirements for Disinfection Byproducts Precursors (DBPP).
R309-215-13 Treatment Techniques for control of Disinfection Byproducts Precursors (DBPP).
R309-215-14 Disinfection Profiling and Benchmarking.
R309-215-15 Enhanced Treatment for Cryptosporidium (Federal Subpart W).
R309-215-16 Groundwater Rule.
R309-215-2. Authority.
This rule is promulgated by the Drinking Water Board as authorized by Title 19, Environmental Quality Code, Chapter 4, Safe Drinking Water Act, Subsection 104 of the Utah Code and in accordance with [
63-46a]63G-3 of the same, known as the Administrative Rulemaking Act.R309-215-14. Disinfection Profiling and Benchmarking.
A disinfection profile is a graphical representation of your system's level of Giardia lamblia or virus inactivation measured during the course of a year. Community or non-transient non-community water systems which use surface water or ground water under the direct influence of surface must develop a disinfection profile unless the Executive Secretary determines that a system's profile is unnecessary. The Executive Secretary may approve the use of a more representative data set for disinfection profiling than the data set required under R309-215-14.
. . . . . . .
(2) Disinfection profiling.
(a) Any system that is required by paragraph (1) of this section shall develop a disinfection profile of its disinfection practice for a period of up to three years. A disinfection profile consists of the following 3 steps:
(i) The system must collect data for several parameters from the plant over the course of 12 months. If your system serves between 500 and 9,999 persons you must begin to collect data no later than July 1, 2003. If your system serves fewer than 500 persons you must begin to collect data no later than January 1, 2004. If your system serves 10,000 persons or greater than the requirements of R309-215-14(2) are only required if it meets the criteria in paragraph R309-215-14(1)(f).
(ii) The system must use this data to calculate weekly log inactivation as discussed in paragraph (d) of this section.
(iii) The system must use these weekly log inactivations to develop a disinfection profile.
(b) The system shall monitor daily for a period of 12 consecutive calendar months to determine the total logs of inactivation for each day of operation, based on the CT99.9 values in Tables 1.1-1.6, 2.1, and 3.1 of Section 141.74(b)(3) in the code of Federal Regulations (also available from the Division), as appropriate, through the entire treatment plant. This system shall begin this monitoring not later than April 1, 2000. As a minimum, the system with a single point of disinfectant application prior to entrance to the distribution system shall conduct the monitoring in paragraphs (2)(b)(i) through (iv) of this section. A system with more than one point of disinfectant application shall conduct the monitoring in paragraphs (2)(b)(i) through (iv) of this section for each disinfection segment. The system shall monitor the parameters necessary to determine the total inactivation ratio, using analytical methods in R309-200-4(3), as follows:
(i) The temperature of the disinfected water shall be measured once per day at each residual disinfectant concentration sampling point during peak hourly flow.
(ii) If the system uses chlorine, the pH of the disinfected water shall be measured once per day at each chlorine residual disinfectant concentration sampling point during peak hourly flow.
(iii) The disinfectant contact time(s) ("T") shall be determined for each day during peak hourly flow.
(iv) The residual disinfectant concentration(s) ("C") of the water before or at the first customer and prior to each additional point of disinfection shall be measured each day during peak hourly flow.
(v) For systems serving less than 10,000 persons, the above parameters shall be monitored once per week on the same calendar day, over 12 consecutive months for the purposes of disinfection profiling.
(c) In lieu of the monitoring conducted under the provisions of paragraph (2)(b) of this section to develop the disinfection profile, the system may elect to meet the requirements of paragraph (2)(c)(i) of this section. In addition to the monitoring conducted under the provisions of paragraph (2)(b) of this section to develop the disinfection profile, the system may elect to meet the requirements of paragraph (2)(c)(ii) of this section.
(i) A PWS that has three years of existing operational data may submit those data, a profile generated using those data, and a request that the Executive Secretary approve use of those data in lieu of monitoring under the provisions of paragraph (2)(b) of this section not later than March 31, 2000. The Executive Secretary shall determine whether these operational data are substantially equivalent to data collected under the provisions of paragraph (2)(b) of this section. These data shall also be representative of Giardia lamblia inactivation through the entire treatment plant and not just of certain treatment segments. Until the Executive Secretary approves this request, the system is required to conduct monitoring under the provisions of paragraph (2)(b) of this section.
(ii) In addition to the disinfection profile generated under paragraph (2)(b) of this section, a PWS that has existing operational data may use those data to develop a disinfection profile for additional years. Such systems may use these additional yearly disinfection profiles to develop a benchmark under the provisions of paragraph (3) of this section. The Executive Secretary shall determine whether these operational data are substantially equivalent to data collected under the provisions of paragraph (2)(b) of this section. These data shall also be representative of inactivation through the entire treatment plant and not just of certain treatment segments.
(d) The system shall calculate the total inactivation ratio as follows:
(i) If the system uses only one point of disinfectant application, the system may determine the total inactivation ratio for the disinfection segment based on either of the methods in paragraph (2)(d)(i)(A) or (2)(d)(i)(B) of this section.
(A) Determine one inactivation ratio (CTcalc/CT99.9) before or at the first customer during peak hourly flow.
(B) Determine successive CTcalc/CT99.9 values, representing sequential inactivation ratios, between the point of disinfectant application and a point before or at the first customer during peak hourly flow. Under this alternative, the system shall calculate the total inactivation ratio by determining (CTcalc/CT99.9) for each sequence and then adding the (CTcalc/CT99.9) values together to determine sum of (CTcalc/CT99.9).
(ii) If the system uses more than one point of disinfectant application before the first customer, the system shall determine the CT value of each disinfection segment immediately prior to the next point of disinfectant application, or for the final segment, before or at the first customer, during peak hourly flow. The (CTcalc/CT99.9) value of each segment and sum of (CTcalc/CT99.9) shall be calculated using the method in paragraph (b)(4)(i) of this section.
(iii) The system shall determine the total logs of inactivation by multiplying the value calculated in paragraph (2)(d)(i) or (ii) of this section by 3.0.
(e) A system that uses either chloramines and chlorine dioxide or ozone for primary disinfection shall also calculate the logs of inactivation for viruses using a method approved by the Executive Secretary.
(f) The system shall retain disinfection profile data in graphic form, as a spreadsheet, or in some other format acceptable to the Executive Secretary for review as part of sanitary surveys conducted by the Executive Secretary.
(3) Disinfection Benchmarking
(a) Any system required to develop a disinfection profile under the provisions of paragraphs (1) and (2) of this section and that decides to make a significant change to its disinfection practice shall consult with the Executive Secretary prior to making such change. Significant changes to disinfection practice are:
(i) Changes to the point of disinfection;
(ii) Changes to the disinfectant(s) used in the treatment plant;
(iii) Changes to the disinfection process; and
(iv) Any other modification identified by the Executive Secretary.
(b) Any system that is modifying its disinfection practice shall calculate its disinfection benchmark using the procedure specified in paragraphs (3)(b)(i) through (ii) of this section.
(i) For each year of profiling data collected and calculated under paragraph (2) of this section, the system shall determine the lowest average monthly Giardia lamblia inactivation in each year of profiling data. The system shall determine the average Giardia lamblia inactivation for each calendar month for each year of profiling data by dividing the sum of daily Giardia lamblia of inactivation by the number of values calculated for that month.
(ii) The disinfection benchmark is the lowest monthly average value (for systems with one year of profiling data) or average of lowest monthly average values (for systems with more than one year of profiling data) of the monthly logs of Giardia lamblia inactivation in each year of profiling data.
(c) A system that uses either chloramines, ozone or chlorine dioxide for primary disinfection must calculate the disinfection benchmark from the data the system collected for viruses to develop the disinfection profile in addition to the Giardia lamblia disinfection benchmark calculated under paragraph (b)(i) above. This viral benchmark must be calculated in the same manner used to calculate the Giardia lamblia disinfection benchmark in paragraph (b)(i).
(d) The system shall submit information in paragraphs (3)(d)(i) through (iv) of this section to the Executive Secretary as part of its consultation process.
(i) A description of the proposed change;
(ii) The disinfection profile for Giardia lamblia (and, if necessary, viruses) under paragraph (2) of this section and benchmark as required by paragraph (3)(b) of this section; and
(iii) An analysis of how the proposed change will affect the current levels of disinfection.
(iv) Any additional information requested by the Executive Secretary.
R309-215-16. Groundwater Rule.
(1) Applicability: This subpart applies to all public water systems that use ground water except that it does not apply to public water systems that combine all of their ground water with surface water or with ground water under the direct influence of surface water prior to treatment. For the purposes of this subpart, "ground water system" is defined as any public water system meeting this applicability Executive Secretaryment, including consecutive systems receiving finished ground water.
(a) General requirements: Systems subject to this subpart must comply with the following requirements:
(i) Sanitary survey information requirements for all ground water systems as described in R309-100-7.
(ii) Microbial source water monitoring requirements for ground water systems that do not treat all of their ground water to at least 99.99 percent (4-log) treatment of viruses (using inactivation, removal, or an Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer as described in R309-215-16(2).
(iii) Treatment technique requirements, described in R309-215-16(3), that apply to ground water systems that have fecally contaminated source waters, as determined by source water monitoring conducted under R309-215-16(2), or that have significant deficiencies that are identified by the Executive Secretary or that are identified by EPA under SDWA section 1445. A ground water system with fecally contaminated source water or with significant deficiencies subject to the treatment technique requirements of this subpart must implement one or more of the following corrective action options: correct all significant deficiencies; provide an alternate source of water; eliminate the source of contamination; or provide treatment that reliably achieves at least 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer.
(b) Ground water systems that provide at least 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer are required to conduct compliance monitoring to demonstrate treatment effectiveness, as described in R309-215-16(3)(b).
(c) If requested by the Executive Secretary, ground water systems must provide the Executive Secretary with any existing information that will enable the Executive Secretary to perform a hydrogeologic sensitivity assessment. For the purposes of this subpart, "hydrogeologic sensitivity assessment" is a determination of whether ground water systems obtain water from hydrogeologically sensitive settings.
(d) Compliance date: Ground water systems must comply, unless otherwise noted, with the requirements of this subpart beginning December 1, 2009.
(2) Ground water source microbial monitoring and analytical methods.
(a) Triggered source water monitoring.
(i) General requirements. A ground water system must conduct triggered source water monitoring if the conditions identified in paragraphs (a)(i)(A) and (a)(i)(B) of this section exist.
(A) The system does not provide at least 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer for each ground water source; and
(B) The system is notified that a sample collected under R309-210-5(1)is total coliform-positive and the sample is not invalidated under R309-210-5(4).
(ii) Sampling Requirements. A ground water system must collect, within 24 hours of notification of the total coliform-positive sample, at least one ground water source sample from each ground water source in use at the time the total coliform-positive sample was collected under R309-210-5(1), except as provided in paragraph (a)(ii)(B) of this section.
(A) The Executive Secretary may extend the 24-hour time limit on a case-by-case basis if the system cannot collect the ground water source water sample within 24 hours due to circumstances beyond its control. In the case of an extension, the Executive Secretary must specify how much time the system has to collect the sample.
(B) If approved by the Executive Secretary, systems with more than one ground water source may meet the requirements of this paragraph (a)(ii) by sampling a representative ground water source or sources. Systems must submit for Executive Secretary approval a triggered source water monitoring plan that identifies one or more ground water sources that are representative of each monitoring site in the system's sample site plan under R309-210-5(1)(d) and that the system intends to use for representative sampling under this paragraph.
(C) A ground water system serving 1,000 people or fewer may use a repeat sample collected from a ground water source to meet both the requirements of R309-210-5(2)(a) and to satisfy the monitoring requirements of paragraph (a)(ii) of this section for that ground water source only if the Executive Secretary approves the use of E. colias a fecal indicator for source water monitoring under this paragraph (a). If the repeat sample collected from the ground water source is E.coli positive, the system must comply with paragraph (a)(iii) of this section.
(iii) Additional Requirements. If the Executive Secretary does not require corrective action under R309-215-16(3)(a)(ii) for a fecal indicator-positive source water sample collected under paragraph (a)(ii) of this section that is not invalidated under paragraph (d) of this section, the system must collect five additional source water samples from the same source within 24 hours of being notified of the fecal indicator-positive sample.
(iv) Consecutive and Wholesale Systems.
(A) In addition to the other requirements of this paragraph (a), a consecutive ground water system that has a total coliform-positive sample collected under R309-210-5(1) must notify the wholesale system(s) within 24 hours of being notified of the total coliform-positive sample.
(B) In addition to the other requirements of this paragraph (a), a wholesale ground water system must comply with paragraphs (a)(iv)(B)(I) and (a)(iv)(B)(II) of this section.
(I) A wholesale ground water system that receives notice from a consecutive system it serves that a sample collected under R309-210-5(1) is total coliform-positive must, within 24 hours of being notified, collect a sample from its ground water source(s) under paragraph (a)(ii) of this section and analyze it for a fecal indicator under paragraph (c) of this section.
(II) If the sample collected under paragraph (a)(iv)(B)(I) of this section is fecal indicator-positive, the wholesale ground water system must notify all consecutive systems served by that ground water source of the fecal indicator source water positive within 24 hours of being notified of the ground water source sample monitoring result and must meet the requirements of paragraph (a)(iii) of this section.
(v) Exceptions to the Triggered Source Water Monitoring Requirements. A ground water system is not required to comply with the source water monitoring requirements of paragraph (a) of this section if either of the following conditions exists:
(A) The Executive Secretary determines, and documents in writing, that the total coliform-positive sample collected under R309-210-5(1)is caused by a distribution system deficiency; or
(B) The total coliform-positive sample collected under R309-210-5(1) is collected at a location that meets Executive Secretary criteria for distribution system conditions that will cause total coliform-positive samples.
(b) Assessment Source Water Monitoring. If directed by the Executive Secretary, ground water systems must conduct assessment source water monitoring that meets Executive Secretary-determined requirements for such monitoring. A ground water system conducting assessment source water monitoring may use a triggered source water sample collected under paragraph (a)(ii) of this section to meet the requirements of paragraph (b) of this section. Executive Secretary-determined assessment source water monitoring requirements may include:
(i) collection of a total of 12 ground water source samples that represent each month the system provides ground water to the public,
(ii) collection of samples from each well unless the system obtains written Executive Secretary approval to conduct monitoring at one or more wells within the ground water system that are representative of multiple wells used by that system and that draw water from the same hydrogeologic setting,
(iii) collection of a standard sample volume of at least 100 mL for fecal indicator analysis regardless of the fecal indicator or analytical method used,
(iv) analysis of all ground water source samples using one of the analytical methods listed in the in paragraph (c)(ii) of this section for the presence of E. coli, enterococci, or coliphage,
(v) collection of ground water source samples at a location prior to any treatment of the ground water source unless the Executive Secretary approves a sampling location after treatment, and
(vi) collection of ground water source samples at the well itself unless the system's configuration does not allow for sampling at the well itself and the Executive Secretary approves an alternate sampling location that is representative of the water quality of that well.
(c) Invalidation of a fecal indicator-positive ground water source sample.
(i) A ground water system may obtain Executive Secretary invalidation of a fecal indicator-positive ground water source sample collected under paragraph (a) of this section only under the conditions specified in paragraphs (c)(i)(A) and (B) of this section.
(A) The system provides the Executive Secretary with written notice from the laboratory that improper sample analysis occurred; or
(B) The Executive Secretary determines and documents in writing that there is substantial evidence that a fecal indicator-positive ground water source sample is not related to source water quality.
(ii) If the Executive Secretary invalidates a fecal indicator-positive ground water source sample, the ground water system must collect another source water sample under paragraph (a) of this section within 24 hours of being notified by the Executive Secretary of its invalidation decision and have it analyzed for the same fecal indicator using the analytical methods in paragraph (c) of this section. The Executive Secretary may extend the 24-hour time limit on a case-by-case basis if the system cannot collect the source water sample within 24 hours due to circumstances beyond its control. In the case of an extension, the Executive Secretary must specify how much time the system has to collect the sample.
(d) Sampling location.
(i) Any ground water source sample required under paragraph (a) of this section must be collected at a location prior to any treatment of the ground water source unless the Executive Secretary approves a sampling location after treatment.
(ii) If the system's configuration does not allow for sampling at the well itself, the system may collect a sample at a Executive Secretary-approved location to meet the requirements of paragraph (a) of this section if the sample is representative of the water quality of that well.
(e) New Sources. If directed by the Executive Secretary, a ground water system that places a new ground water source into service after November 30, 2009, must conduct assessment source water monitoring under paragraph (b) of this section. If directed by the Executive Secretary, the system must begin monitoring before the ground water source is used to provide water to the public.
(f) Public Notification. A ground water system with a ground water source sample collected under paragraph (a) or (b) of this section that is fecal indicator-positive and that is not invalidated under paragraph (d) of this section, including consecutive systems served by the ground water source, must conduct public notification under R309-220-5.
(g) Monitoring Violations. Failure to meet the requirements of paragraphs (a)-(f) of this section is a monitoring violation and requires the ground water system to provide public notification under R309-220-7.
(3) Treatment technique requirements for ground water systems.
(a) Ground water systems with significant deficiencies or source water fecal contamination.
(i) The treatment technique requirements of this section must be met by ground water systems when a significant deficiency is identified or when a ground water source sample collected under R309-215-16(2)(a)(iii) is fecal indicator-positive.
(ii) If directed by the Executive Secretary, a ground water system with a ground water source sample collected under R309-215-16(2)(a)(ii), R309-215-16(2)(a)(iv), or R309-215-16(2)(b) that is fecal indicator-positive must comply with the treatment technique requirements of this section.
(iii) When a significant deficiency is identified at a public water system that uses both ground water and surface water or ground water under the direct influence of surface water, the system must comply with provisions of this paragraph except in cases where the Executive Secretary determines that the significant deficiency is in a portion of the distribution system that is served solely by surface water or ground water under the direct influence of surface water.
(iv) Unless the Executive Secretary directs the ground water system to implement a specific corrective action, the ground water system must consult with the Executive Secretary regarding the appropriate corrective action within 30 days of receiving written notice from the Executive Secretary of a significant deficiency, written notice from a laboratory that a ground water source sample collected under R309-215-16(2)(a)(iii) was found to be fecal indicator-positive, or direction from the Executive Secretary that a fecal indicator-positive collected under R309-215-16(2)(a)(ii), R309-215-16(2)(a)(iv), or R309-215-16(2)(b) requires corrective action. For the purposes of this subpart, significant deficiencies include, but are not limited to, defects in design, operation, or maintenance, or a failure or malfunction of the sources, treatment, storage, or distribution system that the Executive Secretary determines to be causing, or have potential for causing, the introduction of contamination into the water delivered to consumers.
(v) Within 120 days (or earlier if directed by the Executive Secretary) of receiving written notification from the Executive Secretary of a significant deficiency, written notice from a laboratory that a ground water source sample collected under R309-215-16(2)(a)(iii) was found to be fecal indicator-positive, or direction from the Executive Secretary that a fecal indicator-positive sample collected under R309-215-16(2)(a)(ii), R309-215-16(2)(a)(iv), or R309-215-16(2)(b) requires corrective action, the ground water system must either:
(A) have completed corrective action in accordance with applicable Executive Secretary plan review processes or other Executive Secretary guidance or direction, if any, including Executive Secretary-specified interim measures; or
(B) be in compliance with a Executive Secretary-approved corrective action plan and schedule subject to the conditions specified in paragraphs (a)(v)(B)(I) and (a)(v)(B)(II) of this section.
(I) Any subsequent modifications to a Executive Secretary-approved corrective action plan and schedule must also be approved by the Executive Secretary.
(II) If the Executive Secretary specifies interim measures for protection of the public health pending Executive Secretary approval of the corrective action plan and schedule or pending completion of the corrective action plan, the system must comply with these interim measures as well as with any schedule specified by the Executive Secretary.
(vi) Corrective Action Alternatives. Ground water systems that meet the conditions of paragraph (a)(i) or (a)(ii) of this section must implement one or more of the following corrective action alternatives:
(A) correct all significant deficiencies;
(B) provide an alternate source of water;
(C) eliminate the source of contamination; or
(D) provide treatment that reliably achieves at least 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer for the ground water source.
(vii) Special notice to the public of significant deficiencies or source water fecal contamination.
(A) In addition to the applicable public notification requirements of R309-220-5, a community ground water system that receives notice from the Executive Secretary of a significant deficiency or notification of a fecal indicator-positive ground water source sample that is not invalidated by the Executive Secretary under R309-215-16(2)(d) must inform the public served by the water system under R309-225-5(8)of the fecal indicator-positive source sample or of any significant deficiency that has not been corrected. The system must continue to inform the public annually until the significant deficiency is corrected or the fecal contamination in the ground water source is determined by the Executive Secretary to be corrected under paragraph (a)(v) of this section.
(B) In addition to the applicable public notification requirements of R309-220-5, a non-community ground water system that receives notice from the Executive Secretary of a significant deficiency must inform the public served by the water system in a manner approved by the Executive Secretary of any significant deficiency that has not been corrected within 12 months of being notified by the Executive Secretary, or earlier if directed by the Executive Secretary. The system must continue to inform the public annually until the significant deficiency is corrected. The information must include:
(I) The nature of the significant deficiency and the date the significant deficiency was identified by the Executive Secretary;
(II) The Executive Secretary-approved plan and schedule for correction of the significant deficiency, including interim measures, progress to date, and any interim measures completed; and
(III) For systems with a large proportion of non-English speaking consumers, as determined by the Executive Secretary, information in the appropriate language(s) regarding the importance of the notice or a telephone number or address where consumers may contact the system to obtain a translated copy of the notice or assistance in the appropriate language.
(C) If directed by the Executive Secretary, a non-community water system with significant deficiencies that have been corrected must inform its customers of the significant deficiencies, how the deficiencies were corrected, and the dates of correction under paragraph (a)(vii)(B) of this section.
(b) Compliance monitoring.
(i) Existing ground water sources. A ground water system that is not required to meet the source water monitoring requirements of this subpart for any ground water source because it provides at least 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer for any ground water source before December 1, 2009, must notify the Executive Secretary in writing that it provides at least 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer for the specified ground water source and begin compliance monitoring in accordance with paragraph (b)(iii) of this section by December 1, 2009. Notification to the Executive Secretary must include engineering, operational, or other information that the Executive Secretary requests to evaluate the submission. If the system subsequently discontinues 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer for a ground water source, the system must conduct ground water source monitoring as required under R309-215-16(2).
(ii) New ground water sources. A ground water system that places a ground water in service after November 30, 2009, that is not required to meet the source water monitoring requirements of this subpart because the system provides at least 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer for the ground water source must comply with the requirements of paragraphs (b)(ii)(A), (b)(ii)(B) and (b)(ii)(C) of this section.
(A) The system must notify the Executive Secretary in writing that it provides at least 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer for the ground water source. Notification to the Executive Secretary must include engineering, operational, or other information that the Executive Secretary requests to evaluate the submission.
(B) The system must conduct compliance monitoring as required under R309-215-16(3)(b)(iii) of this subpart within 30 days of placing the source in service.
(C) The system must conduct ground water source monitoring under R309-215-16(2) if the system subsequently discontinues 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer for the ground water source.
(iii) Monitoring requirements. A ground water system subject to the requirements of paragraph (b)(i) or (b)(ii) of this section must monitor the effectiveness and reliability of treatment for that ground water source before or at the first customer as follows:
(A) Chemical disinfection.
(I) Ground water systems serving greater than 3,300 people. A ground water system that serves greater than 3,300 people must continuously monitor the residual disinfectant concentration using analytical methods specified in R444-14-4 at a location approved by the Executive Secretary and must record the lowest residual disinfectant concentration each day that water from the ground water source is served to the public. The ground water system must maintain the Executive Secretary-determined residual disinfectant concentration every day the ground water system serves water from the ground water source to the public. If there is a failure in the continuous monitoring equipment, the ground water system must conduct grab sampling every four hours until the continuous monitoring equipment is returned to service. The system must resume continuous residual disinfectant monitoring within 14 days.
(II) Ground water systems serving 3,300 or fewer people. A ground water system that serves 3,300 or fewer people must monitor the residual disinfectant concentration using analytical methods specified in R444-14-4 at a location approved by the Executive Secretary and record the residual disinfection concentration each day that water from the ground water source is served to the public. The ground water system must maintain the Executive Secretary-determined residual disinfectant concentration every day the ground water system serves water from the ground water source to the public. The ground water system must take a daily grab sample during the hour of peak flow or at another time specified by the Executive Secretary. If any daily grab sample measurement falls below the Executive Secretary-determined residual disinfectant concentration, the ground water system must take follow-up samples every four hours until the residual disinfectant concentration is restored to the Executive Secretary-determined level. Alternatively, a ground water system that serves 3,300 or fewer people may monitor continuously and meet the requirements of paragraph (b)(iii)(A)(I) of this section.
(B) Membrane filtration. A ground water system that uses membrane filtration to meet the requirements of this subpart must monitor the membrane filtration process in accordance with all Executive Secretary-specified monitoring requirements and must operate the membrane filtration in accordance with all Executive Secretary-specified compliance requirements. A ground water system that uses membrane filtration is in compliance with the requirement to achieve at least 4-log removal of viruses when:
(I) The membrane has an absolute molecular weight cut-off (MWCO), or an alternate parameter that describes the exclusion characteristics of the membrane, that can reliably achieve at least 4-log removal of viruses;
(II) The membrane process is operated in accordance with Executive Secretary-specified compliance requirements; and
(III) The integrity of the membrane is intact.
(C) Alternative treatment. A ground water system that uses a Executive Secretary-approved alternative treatment to meet the requirements of this subpart by providing at least 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer must:
(I) Monitor the alternative treatment in accordance with all Executive Secretary-specified monitoring requirements; and
(II) Operate the alternative treatment in accordance with all compliance requirements that the Executive Secretary determines to be necessary to achieve at least 4-log treatment of viruses.
(c) Discontinuing treatment. A ground water system may discontinue 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer for a ground water source if the Executive Secretary determines and documents in writing that 4-log treatment of viruses is no longer necessary for that ground water source. A system that discontinues 4-log treatment of viruses is subject to the source water monitoring and analytical methods requirements of R309-215-16(2) of this subpart.
(d) Failure to meet the monitoring requirements of paragraph (b) of this section is a monitoring violation and requires the ground water system to provide public notification under R309-220-7.
(4) Treatment technique violations for ground water systems.
(a) A ground water system with a significant deficiency is in violation of the treatment technique requirement if, within 120 days (or earlier if directed by the Executive Secretary) of receiving written notice from the Executive Secretary of the significant deficiency, the system:
(i) Does not complete corrective action in accordance with any applicable Executive Secretary plan review processes or other Executive Secretary guidance and direction, including Executive Secretary specified interim actions and measures, or
(ii) Is not in compliance with a Executive Secretary-approved corrective action plan and schedule.
(b) Unless the Executive Secretary invalidates a fecal indicator-positive ground water source sample under R309-215-16(2)(d), a ground water system is in violation of the treatment technique requirement if, within 120 days (or earlier if directed by the Executive Secretary) of meeting the conditions of R309-215-16(3)(a)(i) or R309-215-16(3)(a)(ii), the system:
(i) Does not complete corrective action in accordance with any applicable Executive Secretary plan review processes or other Executive Secretary guidance and direction, including Executive Secretary-specified interim measures, or
(ii) Is not in compliance with a Executive Secretary-approved corrective action plan and schedule.
(c) A ground water system subject to the requirements of R309-215-16(3)(b)(iii) that fails to maintain at least 4-log treatment of viruses (using inactivation, removal, or a Executive Secretary-approved combination of 4-log virus inactivation and removal) before or at the first customer for a ground water source is in violation of the treatment technique requirement if the failure is not corrected within four hours of determining the system is not maintaining at least 4-log treatment of viruses before or at the first customer.
(d) Ground water system must give public notification under R309-220-6 for the treatment technique violations specified in paragraphs (a), (b) and (c) of this section.
(5) Reporting and recordkeeping for ground water systems.
(a) Reporting. In addition to the requirements of R309-105-16, a ground water system regulated under this subpart must provide the following information to the Executive Secretary:
(i) A ground water system conducting compliance monitoring under R309-215-16(3)(b) must notify the Executive Secretary any time the system fails to meet any Executive Secretary-specified requirements including, but not limited to, minimum residual disinfectant concentration, membrane operating criteria or membrane integrity, and alternative treatment operating criteria, if operation in accordance with the criteria or requirements is not restored within four hours. The ground water system must notify the Executive Secretary as soon as possible, but in no case later than the end of the next business day.
(ii) After completing any corrective action under R309-215-16(3)(a), a ground water system must notify the Executive Secretary within 30 days of completion of the corrective action.
(iii) If a ground water system subject to the requirements of R309-215-16(2)(a) does not conduct source water monitoring under R309-215-16(2)(a)(v)(B), the system must provide documentation to the Executive Secretary within 30 days of the total coliform positive sample that it met the Executive Secretary criteria.
(b) Recordkeeping. In addition to the requirements of R309-105-17, a ground water system regulated under this subpart must maintain the following information in its records:
(i) Documentation of corrective actions. Documentation shall be kept for a period of not less than ten years.
(ii) Documentation of notice to the public as required under R309-215-16(3)(a)(vii). Documentation shall be kept for a period of not less than three years.
(iii) Records of decisions under R309-215-16(2)(a)(v)(B) and records of invalidation of fecal indicator-positive ground water source samples under R309-215-16(2)(d). Documentation shall be kept for a period of not less than five years.
(iv) For consecutive systems, documentation of notification to the wholesale system(s) of total-coliform positive samples that are not invalidated under R309-210-5(4). Documentation shall be kept for a period of not less than five years.
(v) For systems, including wholesale systems, that are required to perform compliance monitoring under R309-215-16(3)(b):
(A) Records of the Executive Secretary-specified minimum disinfectant residual. Documentation shall be kept for a period of not less than ten years.
(B) Records of the lowest daily residual disinfectant concentration and records of the date and duration of any failure to maintain the Executive Secretary-prescribed minimum residual disinfectant concentration for a period of more than four hours. Documentation shall be kept for a period of not less than five years.
(C) Records of Executive Secretary-specified compliance requirements for membrane filtration and of parameters specified by the Executive Secretary for Executive Secretary-approved alternative treatment and records of the date and duration of any failure to meet the membrane operating, membrane integrity, or alternative treatment operating requirements for more than four hours. Documentation shall be kept for a period of not less than five years.
KEY: drinking water, surface water treatment plant monitoring, disinfection monitoring, compliance determinations
Date of Enactment or Last Substantive Amendment: [
May 14, 2007]2009Notice of Continuation: May 16, 2005
Authorizing, and Implemented or Interpreted Law: 19-4-104; [
63-46b-4]63G-4-202
Document Information
- Effective Date:
- 9/7/2009
- Publication Date:
- 08/01/2009
- Filed Date:
- 07/09/2009
- Agencies:
- Environmental Quality,Drinking Water
- Rulemaking Authority:
Section 19-4-104, and 40 CFR 141 subpart S
- Authorized By:
- Ken Bousfield, Director
- DAR File No.:
- 32812
- Related Chapter/Rule NO.: (1)
- R309-215. Monitoring and Water Quality: Treatment Plant Monitoring Requirements.