No. 40036 (Amendment): Rule R309-215. Monitoring and Water Quality: Treatment Plant Monitoring Requirements
(Amendment)
DAR File No.: 40036
Filed: 12/29/2015 01:58:42 PMRULE ANALYSIS
Purpose of the rule or reason for the change:
The purpose of this rule change is to adopt the revisions to the federal Total Coliform Rule as required by the federal regulations to maintain primary enforcement authority (primacy) for the rule.
Summary of the rule or change:
The Revised Total Coliform Rule (RTCR) requires changes to many of the Division's rules; therefore, the information and comments provided in this form will be applicable to the necessary changes to Rules R309-105, R309-110, R309-200, R309-210, R309-211, R309-215, R309-220, and R309-225 in aggregate. In this specific rule, R309-215, the changes made address updates to the monitoring required by system type and population. (DAR NOTE: The proposed amendment to Rule R309-105 is under DAR No. 40031, the proposed amendment to Rule R309-110 is under DAR No. 40032, the proposed amendment to Rule R309-200 is under DAR No. 40033, the proposed amendment to Rule R309-210 is under DAR No. 40034, the proposed new Rule R309-211 is under DAR No. 40035, the proposed amendment to Rule R309-215 is under DAR No. 40036, the proposed amendment to Rule R309-220 is under DAR No. 40037, and the proposed amendment to Rule R309-225 is under DAR No. 40038 in this issue, January 15, 2016, of the Bulletin.)
State statutory or constitutional authorization for this rule:
- Section 19-4-104
Anticipated cost or savings to:
the state budget:
Along with the final rule language, EPA presented the estimated increase in annual cost nationwide with the new requirements. They estimate nationwide there will be an increase of $30,000,000. With an implementation plan of monthly monitoring, it would be $30,000,000 nationwide. Utah is a 1% state. As such, the increase projected from the national estimate for Utah would be $300,000, respectively. The costs are estimated to be incurred 90% by public water systems and 10% by the state primacy programs; therefore, the estimated impact to the state budget based on EPA's cost analysis would be $30,000 per year. It is important to note this cost estimate also includes the cost of fixing sanitary defects (significant deficiencies) found in the system infra-structure which would be independently required to be fixed upon discovery during a sanitary survey.
local governments:
For local governments, the cost will not change. Base monitoring will stay the same, and for small communities, the follow-up monitoring requirements have been slightly reduced.
small businesses:
For small businesses that have their own public water system, there will be a cost impact. Base monitoring will switch from one sample per calendar quarter to one sample per month. For routine monitoring, the requirements will increase the samples from 4 per year to 12 per year. The increase in routine sample costs for just the laboratory analysis will be approximately $250 per year. This estimate does not include the transport of the sample to a certified lab. The transportation cost will vary greatly and will likely be mitigated by other required business near certified labs.
persons other than small businesses, businesses, or local governmental entities:
The rule will impact USFS campgrounds and kids camps. Base monitoring will switch from one sample per calendar quarter to one sample per month of operation. Most of these systems operate only part of the year (May through September). For routine monitoring, the requirements will increase the samples from two to three per year to one sample for each month of operation. The increase in routine sample costs for just the laboratory analysis will be approximately $100 to $150 per year. This estimate does not include the transport of the sample to a certified lab. The transportation cost will vary greatly and will likely be mitigated by other required business near certified labs.
Compliance costs for affected persons:
The rule impacts every public water system and every person in the state. It is unlikely the rule will independently impact the water rate structure of any community water system. The relatively small cost impact on transient and non-transient system (recreational type facilities and industrial type facilities) should not independently affect consumer costs.
Comments by the department head on the fiscal impact the rule may have on businesses:
The Executive Director agrees with the fiscal impacts detailed above.
Alan Matheson, Executive Director
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:
Environmental Quality
Drinking WaterRoom Third Floor
195 N 1950 W
SALT LAKE CITY, UT 84116-3085Direct questions regarding this rule to:
- Patti Fauver at the above address, by phone at 801-536-4196, by FAX at 801-536-4211, or by Internet E-mail at pfauver@utah.gov
- Jennifer Yee at the above address, by phone at 801-536-4216, by FAX at 801-536-4211, or by Internet E-mail at jyee@utah.gov
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:
02/16/2016
Interested persons may attend a public hearing regarding this rule:
- 01/20/2016 01:00 PM, MSOB, 195 N 1950 W, DEQ Board Room 1015, Salt Lake City, UT
This rule may become effective on:
02/23/2016
Authorized by:
Ken Bousfield, Director
RULE TEXT
R309. Environmental Quality, Drinking Water.
R309-215. Monitoring and Water Quality: Treatment Plant Monitoring Requirements.
R309-215-9. Turbidity Monitoring and Reporting.
Public water systems utilizing surface water and ground water under the direct influence of surface water shall monitor for turbidity in accordance with this section. Small surface water systems serving a population less than 10,000 shall monitor in accordance with subsections (1), (2), (3), (5) and (6). Large surface water systems serving 10,000 or more population shall monitor in accordance with subsections (1), (2), (3), (4) and (6).
(1) Routine Monitoring Requirements for Treatment Facilities utilizing surface water sources or ground water sources under the direct influence of surface water.
(a) All public water systems which use a treatment technique to treat water obtained in whole or in part from surface water sources or ground water sources under the direct influence of surface water shall monitor for turbidity at the treatment plant's clearwell outlet. This monitoring shall be independent of the individual filter monitoring required by R309-525-15(4)(b)(vi) and R309-525-15(4)(c)(vii). Where the plant facility does not have an internal clearwell, the turbidity shall be monitored at the inlet to a finished water reservoir external to the plant provided such reservoir receives only water from the treatment plant and, furthermore, is located before any point of consumer connection to the water system. If such external reservoir does not exist, turbidity shall then be monitored at a location immediately downstream of the treatment plant filters.
(b) All treatment plants, with the exception of those utilizing slow sand filtration and other conditions indicated in section (c) below, shall be equipped with continuous turbidity monitoring and recording equipment for which the direct responsible charge operator will validate the continuous measurements for accuracy in accordance with paragraph (d) below. These plants shall continuously record the finished water turbidity of the combined filter effluent as well as each individual filter. All systems shall be equipped to continuously monitor the turbidity at each filter unless the treatment plant is only equipped with two filters and the turbidity is measured at the combined filter effluent (CFE). If there is a failure in continuous monitoring equipment the system shall conduct grab sampling every 4 hours in lieu of continuous monitoring, but for no more than five working days following the failure of equipment. Systems serving less than 10,000 population shall have no more than 14 days to conduct grab samples in lieu of continuous monitoring in order to correct any failing equipment. All surface water systems shall monitor the turbidity results of individual filters at a frequency no greater than every 15 minutes.
(c) Turbidity measurements, as outlined below, shall be reported to the Division within ten days after the end of each month that the system serves water to the public. Systems are required to mark and interpret turbidity values from the recorded charts at the end of each four-hour interval of operation (or some shorter regular time interval) to determine compliance with the turbidity performance criterion. For systems using slow sand filtration the Director may reduce the sampling frequency to as little as once per day if the Director determines that less frequent monitoring is sufficient to indicate effective filtration performance. For systems serving 500 or fewer persons, the Director may reduce the turbidity sampling frequency to as little as once per day, regardless of the type of filtration treatment used, if the Director determines that less frequent monitoring is sufficient to indicate effective filtration performance.
The following shall be reported and the required percentage achieved for compliance:
(i) The total number of interpreted filtered water turbidity measurements taken during the month;
(ii) The number and percentage of interpreted filtered water turbidity measurements taken during the month which are less than or equal to the turbidity limits specified in R309-200-5(5)(a)(ii) (or increased limit approved by the Director). The percentage of measurements which are less than or equal to the turbidity limit shall be 95 percent or greater for compliance; and
(iii) The date and value of any turbidity measurements taken during the month which exceed 5 NTU. The system shall inform the Division as soon as practical, but no later than 24 hours after the exceedance is known, in accordance with R309-220-6(2)(c) if any turbidity measurements exceed 5 NTU.
(d) The analytical method which shall be followed in making the required determinations shall be Nephelometric Method - Nephelometric Turbidity Unit as set forth in the latest edition of Standard Methods for Examination of Water and Wastewater, 1985, American Public Health Association et al., (Method 214A, pp. 134-136 in the 16th edition). Continuous turbidity monitoring equipment shall be checked for accuracy and recalibrated using methods outlined in the above standard at a minimum frequency of monthly. The direct responsible charge operator will note on the turbidity report form when these recalibrations are conducted. For systems that practice lime softening, the representative combined filter effluent turbidity sample may be acidified prior to analysis with prior approval by the Director as to the protocol.
(2) Procedures if a Filtered Water Turbidity Limit is Exceeded
(a) Resampling -
If an analysis indicates that the turbidity limit has been exceeded, the sampling and measurement shall be confirmed by resampling as soon as practicable and preferably within one hour.
(b) If the result of resampling confirms that the turbidity limit has been exceeded, the system shall collect and have analyzed at least one bacteriologic sample near the first service connection from the source as specified in [
R309-210-5(1)(f)]R309-211-4(4). The system shall collect this bacteriologic sample within 24 hours of the turbidity exceedance. Sample results from this monitoring shall be included in determining bacteriologic compliance for that month.(c) Initial Notification of the Director -
If the repeat sample confirms that the turbidity limit has been exceeded, the supplier shall report this fact to the Director as soon as practical, but no later than 24 hours after the exceedance is known in accordance with the public notification requirements under R309-220-6(2)(c). This reporting is in addition to reporting the incident on any monthly reports.
(3) For the purpose of individual plant evaluation and establishment of pathogen removal credit for the purpose of lowering the required "CT" value assigned a plant, plant management may do additional turbidity monitoring at other points to satisfy criteria in R309-215-7(2).
(4) Additional reporting and recordkeeping requirements for large surface water systems (serving greater than 10,000 population) reporting and recordkeeping requirements.
In addition to the reporting and recordkeeping requirements sub-sections (1), (2) and (3) above, a large surface water system that provides conventional filtration treatment or direct filtration shall report monthly to the Division the information specified in paragraphs (a) and (b) of this section. In addition to the reporting and recordkeeping requirements above, a public water system subject to the requirements of this subpart that provides filtration approved under R309-530-8 or R309-530-9 shall report monthly to the Division the information specified in paragraphs (a) of this section. The reporting in paragraph (a) of this section is in lieu of the reporting specified above.
(a) Turbidity measurements, as required in R309-200-5(5)(a), shall be reported within 10 days after the end of each month the system serves water to the public. Information that shall be reported includes:
(i) The total number of filtered water turbidity measurements taken during the month.
(ii) The number and percentage of filtered water turbidity measurements taken during the month which are less than or equal to 0.3 NTU or those levels established under R309-200-5(5)(a)(ii).
(iii) The date and value of any turbidity measurements taken during the month which exceed 1 NTU for systems using conventional filtration treatment or direct filtration, or which exceed the maximum level set by the Director under R309-530-8 or R309-530-9.
(b) Systems shall maintain the results of individual filter monitoring taken under R309-215-9(1)(b) for at least three years. Systems shall record the results of individual filter monitoring every 15 minutes. Systems shall report that they have conducted individual filter turbidity monitoring within 10 days after the end of each month the system serves water to the public. Systems shall report individual filter turbidity measurement results within 10 days after the end of each month the system serves water to the public only if measurements demonstrate one or more of the conditions in paragraphs (b)(i) through (iv) of this section. Systems that use lime softening may apply to the Director for alternative exceedance levels for the levels specified in paragraphs (b)(i) through (iv) of this section if they can demonstrate that higher turbidity levels in individual filters are due to lime carryover only and not due to degraded filter performance.
(i) For any individual filter that has a measured turbidity level of greater than 1.0 NTU in two consecutive measurements taken 15 minutes apart, the system shall report the filter number, the turbidity measurement, and the date(s) on which the exceedance occurred. In addition, the system shall either produce a filter profile for the filter within 7 days of the exceedance (if the system is not able to identify an obvious reason for the abnormal filter performance) and report that the profile has been produced or report the obvious reason for the exceedance.
(ii) For any individual filter that has a measured turbidity level of greater than 0.5 NTU in two consecutive measurements taken 15 minutes apart at the end of the first four hours of continuous filter operation after the filter has been backwashed or otherwise taken offline, the system shall report the filter number, the turbidity, and the date(s) on which the exceedance occurred. In addition, the system shall either produce a filter profile for the filter within 7 days of the exceedance (if the system is not able to identify an obvious reason for the abnormal filter performance) and report that the profile has been produced or report the obvious reason for the exceedance.
(iii) For any individual filter that has a measured turbidity level of greater than 1.0 NTU in two consecutive measurements taken 15 minutes apart at any time in each of three consecutive months, the system shall report the filter number, the turbidity measurement, and the date(s) on which the exceedance occurred. In addition, the system shall conduct a self-assessment of the filter within 14 days of the exceedance and report that the self-assessment was conducted. The self assessment shall consist of at least the following components: assessment of filter performance; development of a filter profile; identification and prioritization of factors limiting filter performance; assessment of the applicability of corrections; and preparation of a filter self-assessment report.
(iv) For any individual filter that has a measured turbidity level of greater than 2.0 NTU in two consecutive measurements taken 15 minutes apart at any time in each of two consecutive months, the system shall report the filter number, the turbidity measurement, and the date(s) on which the exceedance occurred. In addition, the system shall arrange for and conduct a comprehensive performance evaluation by the Director or a third party approved by the Director no later than 30 days following the exceedance and have the evaluation completed and submitted to the Division no later than 90 days following the exceedance.
(5) Additional reporting and recordkeeping requirements for surface water systems serving less than 10,000 population.
In addition to the reporting and recordkeeping requirements sub-sections (1), (2) and (3) above, a surface water system that provides conventional filtration treatment or direct filtration shall report monthly to the Division the information specified in paragraphs (a) and (b) of this section. In addition to the reporting and recordkeeping requirements above, a public water system subject to the requirements of this subpart that provides filtration approved under R309-530-8 or R309-530-9 shall report monthly to the Division the information specified in paragraphs (a) of this section. The reporting in paragraph (a) of this section is in lieu of the reporting specified above.
(a) Turbidity measurements, as required in R309-200-5(5)(a), shall be reported within 10 days after the end of each month the system serves water to the public. Information that shall be reported includes:
(i) The total number of filtered water turbidity measurements taken during the month.
(ii) The number and percentage of filtered water turbidity measurements taken during the month which are less than or equal to 0.3 NTU or those levels established under R309-200-5(5)(a)(ii).
(iii) The date and value of any turbidity measurements taken during the month which exceed 1 NTU for systems using conventional filtration treatment or direct filtration, or which exceed the maximum level set by the Director under R309-530-8 or R309-530-9.
(b) Systems shall maintain the results of individual filter monitoring taken under R309-215-9(1)(b) for at least three years. Systems shall record the results of individual filter monitoring every 15 minutes. Systems shall report that they have conducted individual filter turbidity monitoring within 10 days after the end of each month the system serves water to the public. Systems shall report individual filter turbidity measurement results within 10 days after the end of each month the system serves water to the public only if measurements demonstrate one or more of the conditions in paragraphs (b)(i) through (iv) of this section. Systems that use lime softening may apply to the Director for alternative exceedance levels for the levels specified in paragraphs (b)(i) through (iv) of this section if they can demonstrate that higher turbidity levels in individual filters are due to lime carryover only and not due to degraded filter performance.
(i) For any individual filter (or CFE for systems with 2 filters that monitor CFE in lieu of individual filters) that has a measured turbidity level of greater than 1.0 NTU in two consecutive measurements taken 15 minutes apart, the system shall report the filter number(s), the corresponding date(s), the turbidity values which exceeded 1.0 NTU, and the cause (if known) for the exceedance(s), to the Director by the 10th of the following month.
(ii) If a system was required to report to the Director for three months in a row and turbidity exceeded 1.0 NTU in two consecutive recordings taken 15 minutes apart at the same filter (or CFE for systems with 2 filters that monitor CFE in lieu of individual filters), the system shall conduct a self-assessment of the filter within 14 days of the day the filter exceeded 1.0 NTU in two consecutive measurements for the third straight month unless a CPE as specified in paragraph (iii) of this section was required. Systems with 2 filters that monitor CFE in lieu of individual filters must conduct a self assessment on both filters. The self-assessment must consist of at least the following components: assessment of filter performance; development of a filter profile; identification and prioritization of factors limiting filter performance; assessment of the applicability of corrections; and preparation of a filter self-assessment report. If a self-assessment is required, the date that it was triggered and the date that it was completed.
(iii) If a system was required to report to the Director for two months in a row and turbidity exceeded 2.0 NTU in two consecutive measurements taken 15 minutes apart at the same filter (or CFE for systems with 2 filters that monitor CFE in lieu of individual filters), the system shall arrange to have a comprehensive performance evaluation (CPE) conducted by the Director or a third party approved by the Director no later than 60 days following the day the filter exceeded 2.0 NTU in two consecutive measurements for the second straight month. If a CPE is required, the system must report a CPE required and the date it was triggered. If a CPE has been completed by the Director or a third party approved by the Director within the 12 prior months or the system and Division are jointly participating in an ongoing Comprehensive Technical Assistance (CTA) project at the system, a new CPE is not required. If conducted, a CPE must be completed and submitted to the Division no later than 120 days following the day the filter exceeded 2.0 NTU in two consecutive measurements for the second straight month.
(6) Additional reporting requirements.
(a) If at any time the turbidity exceeds 1 NTU in representative samples of filtered water in a system using conventional filtration treatment or direct filtration, the system shall inform the Division as soon as possible, but no later than the end of the next business day.
(b) If at any time the turbidity in representative samples of filtered water exceeds the maximum level set by the Director under R309-530-8 or R309-530-9 for filtration technologies other than conventional filtration treatment, direct filtration, slow sand filtration, or diatomaceous earth filtration, the system shall inform the Division as soon as possible, but no later than the end of the next business day.
R309-215-10. Residual Disinfectant.
Treatment plant management shall continuously monitor disinfectant residuals and report the following to the Division within ten days after the end of each month that the system serves water to the public, except as otherwise noted:
(1) For each day, the lowest measurement of residual disinfectant concentration in mg/L in water entering the distribution system, except that if there is a failure in the continuous monitoring equipment, grab sampling every 4 hours may be conducted in lieu of continuous monitoring, but for no more than 5 working days following the failure of the equipment. Systems serving 3,300 or fewer persons may take grab samples in lieu of providing continuous monitoring on an ongoing basis at the frequencies listed in Table 215.2 below:
TABLE 215-2
RESIDUAL GRAB SAMPLE FREQUENCY
System size by population Samples/day
Less than 500 1
501 to 1,000 2
1,001 to 2,500 3
2,501 to 3,300 4
Note: The day's samples cannot be taken at the same time.
The sampling intervals are subject to Director's review and
approval.(2) The date and duration of each period when the residual disinfectant concentration in water entering the distribution system fell below 0.2 mg/L and when the Division was notified of the occurrence. The system shall notify the Division as soon as possible, but no later than by the end of the next business day. The system also shall notify the Division by the end of the next business day whether or not the residual was restored to at least 0.2 mg/L within four hours.
(3) The following information on the samples taken in the distribution system in conjunction with total coliform monitoring pursuant to [
R309-210-5]R309-211 and R309-210-8(3)(a)(i):(a) number of instances where the residual disinfectant concentration is measured;
(b) number of instances where the residual disinfectant concentration is not measured but heterotrophic bacteria plate count (HPC) is measured;
(c) number of instances where the residual disinfectant concentration is measured but not detected and no HPC is measured;
(d) number of instances where no residual disinfectant concentration is detected and where HPC is greater than 500/ml;
(e) number of instances where the residual disinfectant concentration is not measured and HPC is greater than 500/ml;
(f) for the current and previous month the system serves water to the public, the value of "V" in the formula, V = ((c+d+e)/(a+b)) x 100, where a = the value in sub-section (a) above, b = the value in sub-section (b) above, c = the value in sub-section (c) above, d = the value in sub-section (d) above, and e = the value in sub-section (e) above.
R309-215-16. Groundwater Rule.
(1) Applicability: This subpart applies to all public water systems that use ground water except that it does not apply to public water systems that combine all of their ground water with surface water or with ground water under the direct influence of surface water prior to treatment. For the purposes of this subpart, "ground water system" is defined as any public water system meeting this applicability, including consecutive systems receiving finished ground water.
(a) General requirements: Systems subject to this subpart must comply with the following requirements:
(i) Sanitary survey information requirements for all ground water systems as described in R309-100-7.
(ii) Microbial source water monitoring requirements for ground water systems that do not treat all of their ground water to at least 99.99 percent (4-log) treatment of viruses (using inactivation, removal, or an Director-approved combination of 4-log virus inactivation and removal) before or at the first customer as described in R309-215-16(2).
(iii) Treatment technique requirements, described in R309-215-16(3), that apply to ground water systems that have fecally contaminated source waters, as determined by source water monitoring conducted under R309-215-16(2), or that have significant deficiencies that are identified by the Director or that are identified by EPA under SDWA section 1445. A ground water system with fecally contaminated source water or with significant deficiencies subject to the treatment technique requirements of this subpart must implement one or more of the following corrective action options: correct all significant deficiencies; provide an alternate source of water; eliminate the source of contamination; or provide treatment that reliably achieves at least 4-log treatment of viruses (using inactivation, removal, or a Director-approved combination of 4-log virus inactivation and removal) before or at the first customer.
(b) Ground water systems that provide at least 4-log treatment of viruses (using inactivation, removal, or a Director-approved combination of 4-log virus inactivation and removal) before or at the first customer are required to conduct compliance monitoring to demonstrate treatment effectiveness, as described in R309-215-16(3)(b).
(c) If requested by the Director, ground water systems must provide the Director with any existing information that will enable the Director to perform a hydrogeologic sensitivity assessment. For the purposes of this subpart, "hydrogeologic sensitivity assessment" is a determination of whether ground water systems obtain water from hydrogeologically sensitive settings.
(d) Compliance date: Ground water systems must comply, unless otherwise noted, with the requirements of this subpart beginning December 1, 2009.
(2) Ground water source microbial monitoring and analytical methods.
(a) Triggered source water monitoring.
(i) General requirements. A ground water system must conduct triggered source water monitoring if the conditions identified in paragraphs (a)(i)(A) and (a)(i)(B) of this section exist.
(A) The system does not provide at least 4-log treatment of viruses (using inactivation, removal, or a Director-approved combination of 4-log virus inactivation and removal) before or at the first customer for each ground water source; and
(B) The system is notified that a sample collected under [
R309-210-5(1)]R309-211 is total coliform-positive and the sample is not invalidated under [R309-210-5(4)]R309-211-10.(ii) Sampling Requirements. A ground water system must collect, within 24 hours of notification of the total coliform-positive sample, at least one ground water source sample from each ground water source in use at the time the total coliform-positive sample was collected under [
R309-210-5(1)]R309-211, except as provided in paragraph (a)(ii)(B) of this section.(A) The Director may extend the 24-hour time limit on a case-by-case basis if the system cannot collect the ground water source water sample within 24 hours due to circumstances beyond its control. In the case of an extension, the Director must specify how much time the system has to collect the sample.
(B) If approved by the Director, systems with more than one ground water source may meet the requirements of this paragraph (a)(ii) by sampling a representative ground water source or sources. Systems must submit for Director approval a triggered source water monitoring plan that identifies one or more ground water sources that are representative of each monitoring site in the system's sample site plan under [
R309-210-5(1)(d)]R309-211- 4(1) and that the system intends to use for representative sampling under this paragraph.(C) A ground water system serving 1,000 or fewer people [
or fewer] may use a repeat sample collected from a ground water source to meet both the requirements of [R309-210-5(2)(a)]R309-211-7(1) and to satisfy the monitoring requirements of paragraph (a)(ii) of this section for that ground water source only if the Director approves the use of E. coli as a fecal indicator for source water monitoring under this paragraph (a) and approves the use of a single sample for meeting both the triggered source water monitoring requirements in this paragraph (a) and the repeat monitoring requirements in R309-211-7. If the repeat sample collected from the ground water source is E.coli positive, the system must comply with paragraph (a)(iii) of this section.(iii) Additional Requirements. If the Director does not require corrective action under R309-215-16(3)(a)(ii) for a fecal indicator-positive source water sample collected under paragraph (a)(ii) of this section that is not invalidated under paragraph ([
d]c) of this section, the system must collect five additional source water samples from the same source within 24 hours of being notified of the fecal indicator-positive sample.(iv) Consecutive and Wholesale Systems.
(A) In addition to the other requirements of this paragraph (a), a consecutive ground water system that has a total coliform-positive sample collected under [
R309-210-5(1)]R309-211 must notify the wholesale system(s) within 24 hours of being notified of the total coliform-positive sample.(B) In addition to the other requirements of this paragraph (a), a wholesale ground water system must comply with paragraphs (a)(iv)(B)(I) and (a)(iv)(B)(II) of this section.
(I) A wholesale ground water system that receives notice from a consecutive system it serves that a sample collected under [
R309-210-5(1)]R309-211-5 and 6 is total coliform-positive must, within 24 hours of being notified, collect a sample from its ground water source(s) under paragraph (a)(ii) of this section and analyze it for a fecal indicator under paragraph (c) of this section.(II) If the sample collected under paragraph (a)(iv)(B)(I) of this section is fecal indicator-positive, the wholesale ground water system must notify all consecutive systems served by that ground water source of the fecal indicator source water positive within 24 hours of being notified of the ground water source sample monitoring result and must meet the requirements of paragraph (a)(iii) of this section.
(v) Exceptions to the Triggered Source Water Monitoring Requirements. A ground water system is not required to comply with the source water monitoring requirements of paragraph (2)(a) of this section if either of the following conditions exists:
(A) The Director determines, and documents in writing, that the total coliform-positive sample collected under [
R309-210-5(1)]R309-211-5 and 6 is caused by a distribution system deficiency; or(B) The total coliform-positive sample collected under [
R309-210-5(1)]R309-211-5 and 6 is collected at a location that meets Director criteria for distribution system conditions that will cause total coliform-positive samples.(b) Assessment Source Water Monitoring. If directed by the Director, ground water systems must conduct assessment source water monitoring that meets Director-determined requirements for such monitoring. A ground water system conducting assessment source water monitoring may use a triggered source water sample collected under paragraph (a)(ii) of this section to meet the requirements of paragraph (b) of this section. Director-determined assessment source water monitoring requirements may include:
(i) collection of a total of 12 ground water source samples that represent each month the system provides ground water to the public,
(ii) collection of samples from each well unless the system obtains written Director approval to conduct monitoring at one or more wells within the ground water system that are representative of multiple wells used by that system and that draw water from the same hydrogeologic setting,
(iii) collection of a standard sample volume of at least 100 mL for fecal indicator analysis regardless of the fecal indicator or analytical method used,
(iv) analysis of all ground water source samples in accordance with R309-210-4(1) and R309-200-4(3) for the presence of E. coli, enterococci, or coliphage,
(v) collection of ground water source samples at a location prior to any treatment of the ground water source unless the Director approves a sampling location after treatment, and
(vi) collection of ground water source samples at the well itself unless the system's configuration does not allow for sampling at the well itself and the Director approves an alternate sampling location that is representative of the water quality of that well.
(c) Invalidation of a fecal indicator-positive ground water source sample.
(i) A ground water system may obtain Director invalidation of a fecal indicator-positive ground water source sample collected under paragraph (a) of this section only under the conditions specified in paragraphs (c)(i)(A) and (B) of this section.
(A) The system provides the Director with written notice from the laboratory that improper sample analysis occurred; or
(B) The Director determines and documents in writing that there is substantial evidence that a fecal indicator-positive ground water source sample is not related to source water quality.
(ii) If the Director invalidates a fecal indicator-positive ground water source sample, the ground water system must collect another source water sample under paragraph (a) of this section within 24 hours of being notified by the Director of its invalidation decision and have it analyzed for the same fecal indicator using the analytical methods in paragraph (c) of this section. The Director may extend the 24-hour time limit on a case-by-case basis if the system cannot collect the source water sample within 24 hours due to circumstances beyond its control. In the case of an extension, the Director must specify how much time the system has to collect the sample.
(d) Sampling location.
(i) Any ground water source sample required under paragraph (a) of this section must be collected at a location prior to any treatment of the ground water source unless the Director approves a sampling location after treatment.
(ii) If the system's configuration does not allow for sampling at the well itself, the system may collect a sample at a Director-approved location to meet the requirements of paragraph (a) of this section if the sample is representative of the water quality of that well.
(e) New Sources. If directed by the Director, a ground water system that places a new ground water source into service after November 30, 2009, must conduct assessment source water monitoring under paragraph (b) of this section. If directed by the Director, the system must begin monitoring before the ground water source is used to provide water to the public.
(f) Public Notification. A ground water system with a ground water source sample collected under paragraph (a) or (b) of this section that is fecal indicator-positive and that is not invalidated under paragraph (d) of this section, including consecutive systems served by the ground water source, must conduct public notification under R309-220-5.
(g) Monitoring Violations. Failure to meet the requirements of paragraphs (a)-(f) of this section is a monitoring violation and requires the ground water system to provide public notification under R309-220-7.
. . . . . . .
(5) Reporting and recordkeeping for ground water systems.
(a) Reporting. In addition to the requirements of R309-105-16, a ground water system regulated under this subpart must provide the following information to the Director:
(i) A ground water system conducting compliance monitoring under R309-215-16(3)(b) must notify the Director any time the system fails to meet any Director-specified requirements including, but not limited to, minimum residual disinfectant concentration, membrane operating criteria or membrane integrity, and alternative treatment operating criteria, if operation in accordance with the criteria or requirements is not restored within four hours. The ground water system must notify the Director as soon as possible, but in no case later than the end of the next business day.
(ii) After completing any corrective action under R309-215-16(3)(a), a ground water system must notify the Director within 30 days of completion of the corrective action.
(iii) If a ground water system subject to the requirements of R309-215-16(2)(a) does not conduct source water monitoring under R309-215-16(2)(a)(v)(B), the system must provide documentation to the Director within 30 days of the total coliform positive sample that it met the Director criteria.
(b) Recordkeeping. In addition to the requirements of R309-105-17, a ground water system regulated under this subpart must maintain the following information in its records:
(i) Documentation of corrective actions. Documentation shall be kept for a period of not less than ten years.
(ii) Documentation of notice to the public as required under R309-215-16(3)(a)(vii). Documentation shall be kept for a period of not less than three years.
(iii) Records of decisions under R309-215-16(2)(a)(v)(B) and records of invalidation of fecal indicator-positive ground water source samples under R309-215-16(2)(d). Documentation shall be kept for a period of not less than five years.
(iv) For consecutive systems, documentation of notification to the wholesale system(s) of total-coliform positive samples that are not invalidated under [
R309-210-5(4)]R309-211-10. Documentation shall be kept for a period of not less than five years.(v) For systems, including wholesale systems, that are required to perform compliance monitoring under R309-215-16(3)(b):
(A) Records of the Director-specified minimum disinfectant residual. Documentation shall be kept for a period of not less than ten years.
(B) Records of the lowest daily residual disinfectant concentration and records of the date and duration of any failure to maintain the Director-prescribed minimum residual disinfectant concentration for a period of more than four hours. Documentation shall be kept for a period of not less than five years.
(C) Records of Director-specified compliance requirements for membrane filtration and of parameters specified by the Director for Director-approved alternative treatment and records of the date and duration of any failure to meet the membrane operating, membrane integrity, or alternative treatment operating requirements for more than four hours. Documentation shall be kept for a period of not less than five years.
KEY: drinking water, surface water treatment plant monitoring, disinfection monitoring, compliance determinations
Date of Enactment or Last Substantive Amendment: [
September 21, 2010]2016Notice of Continuation: March 13, 2015
Authorizing, and Implemented or Interpreted Law: 19-4-104
Document Information
- Hearing Meeting:
- 01/20/2016 01:00 PM, MSOB, 195 N 1950 W, DEQ Board Room 1015, Salt Lake City, UT
- Effective Date:
- 2/23/2016
- Publication Date:
- 01/15/2016
- Type:
- Notices of Proposed Rules
- Filed Date:
- 12/29/2015
- Agencies:
- Environmental Quality, Drinking Water
- Rulemaking Authority:
Section 19-4-104
- Authorized By:
- Ken Bousfield, Director
- DAR File No.:
- 40036
- Summary:
- The Revised Total Coliform Rule (RTCR) requires changes to many of the Division's rules; therefore, the information and comments provided in this form will be applicable to the necessary changes to Rules R309-105, R309-110, R309-200, R309-210, R309-211, R309-215, R309-220, and R309-225 in aggregate. In this specific rule, R309-215, the changes made address updates to the monitoring required by system type and population. (DAR NOTE: The proposed amendment to Rule R309-105 is under DAR No. 40031, ...
- CodeNo:
- R309-215
- CodeName:
- {36645|R309-215|R309-215. Monitoring and Water Quality: Treatment Plant Monitoring Requirements}
- Link Address:
- Environmental QualityDrinking WaterRoom Third Floor 195 N 1950 WSALT LAKE CITY, UT 84116-3085
- Link Way:
Patti Fauver, by phone at 801-536-4196, by FAX at 801-536-4211, or by Internet E-mail at pfauver@utah.gov
Jennifer Yee, by phone at 801-536-4216, by FAX at 801-536-4211, or by Internet E-mail at jyee@utah.gov
- AdditionalInfo:
- More information about a Notice of Proposed Rule is available online. The Portable Document Format (PDF) version of the Bulletin is the official version. The PDF version of this issue is available at http://www.rules.utah.gov/publicat/bull-pdf/2016/b20160115.pdf. The HTML edition of the Bulletin is a convenience copy. Any discrepancy between the PDF version and HTML version is resolved in favor of the PDF version. Text to be deleted is struck through and surrounded by brackets ([example]). ...
- Related Chapter/Rule NO.: (1)
- R309-215. Monitoring and Water Quality: Treatment Plant Monitoring Requirements.