DAR File No.: 27101
Filed: 06/24/2004, 04:06
Received by: NLRULE ANALYSIS
Purpose of the rule or reason for the change:
After a public hearing and comments received, the Division and the Uniform Building Code Commission determined that the proposed amendment to the International Residential Code (IRC) regarding landing requirements in Subsection R156-56-711(13) was defective in that it failed to adequately consider all the factors that should be considered in adopting an amendment in this area. The effect being that there will be no amendment to the IRC requirements in this area.
Summary of the rule or change:
In Sections R156-56-704 and R156-56-707, made several minor typographical or technical error corrections throughout these sections. In Section R156-56-711, deleted Subsection R156-56-711(13) (previously proposed) regarding landings at doors and renumbered the remaining subsections. (DAR NOTE: This change in proposed rule has been filed to make additional changes to a proposed amendment that was published in the May 1, 2004, issue of the Utah State Bulletin, on page 5. Underlining in the rule below indicates text that has been added since the publication of the proposed rule mentioned above; strike-out indicates text that has been deleted. You must view the change in proposed rule and the proposed amendment together to understand all of the changes that will be enforceable should the agency make this rule effective.)
State statutory or constitutional authorization for this rule:
Section 58-56-1; and Subsections 58-1-106(1)(a), 58-1-202(1)(a), 58-56-4(2); and 58-56-6(2)(a)
Anticipated cost or savings to:
the state budget:
The Division does not anticipate any additional costs or savings beyond those identified in the original rule filing.
local governments:
The Division does not anticipate any additional costs or savings beyond those identified in the original rule filing.
other persons:
Since the landing requirement amendment is now being deleted, there may be no anticipated minor savings in the costs of landings at certain residences as was identified in the original rule filing.
Compliance costs for affected persons:
Since the landing requirement amendment is now being deleted, there may be no anticipated minor savings in the costs of landings at certain residences as was identified in the original rule filing.
Comments by the department head on the fiscal impact the rule may have on businesses:
Based upon comments received at the rule hearing, a previously proposed rule change to modify the IRC as to stairway landings is withdrawn with this filing. There are also minor technical amendments such as correction of references and typographical errors. These amendments do not appear to create any fiscal impact to businesses. Klarice A. Bachman, Executive Director
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:
Commerce
Occupational and Professional Licensing
HEBER M WELLS BLDG
160 E 300 S
SALT LAKE CITY UT 84111-2316Direct questions regarding this rule to:
Dan S. Jones at the above address, by phone at 801-530-6720, by FAX at 801-530-6511, or by Internet E-mail at dsjones@utah.gov
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:
08/16/2004
This rule may become effective on:
08/17/2004
Authorized by:
J. Craig Jackson, Director
RULE TEXT
R156. Commerce, Occupational and Professional Licensing.
R156-56. Utah Uniform Building Standard Act Rules.
R156-56-704. Statewide Amendments to the IBC.
The following are adopted as amendments to the IBC to be applicable statewide:
(1) All references to the International Electrical Code are deleted and replaced with the National Electrical Code adopted under Subsection R156-56-701(1)(b).
. . . . . . .
(14) Section 310.1 is deleted and replaced with the following:
310.1 Residential Group "R". Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classed as an Institutional Group I. Residential occupancies shall include the following:
R-1: Residential occupancies where the occupants are primarily transient in nature (less than 30 days) including: Boarding Houses (transient), Hotels (transient), and Motels (transient).
Exception: Boarding houses accommodating 10 persons or less shall be classified as a Residential Group R-3 or shall comply with the International Residential Code in accordance with Section 101.2.
R-2: Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including: Apartment Houses, Boarding houses (not transient), Convents, Dormitories, Fraternities and Sororities, Monasteries, Vacation timeshare properties, Hotels (non transient), and Motels (non transient).
Exception: Boarding houses accommodating 10 persons or less shall be classified as a Residential Group R-3 or shall comply with the International Residential Code in accordance with Section 101.2.
R-3: Residential occupancies where the occupants are primarily permanent in nature and not classified as R-1, R-2, R-4 or I and where buildings do not contain more than two dwelling units, as applicable in Section 101.2, or adult and child care facilities that provide accommodations for five or fewer persons of any age for less than 24 hours. Adult and child care facilities that are within a single family home are permitted to comply with the International Residential Code in accordance with Section 101.2. Areas used for day care purposes may be located in a residential dwelling unit under all of the following conditions:
1. Compliance with the Utah Administrative Code, R710-8, Day Care Rules, as enacted under the authority of the Utah Fire Prevention Board.
2. Use is approved by the State Department of Health, as enacted under the authority of the Utah Child Care Licensing Act, UCA, Sections 26-39-101 through 26-39-110, and in any of the following categories:
a. Utah Administrative Code, R430-50, Residential Certificate Child Care Standards.
b. Utah Administrative Code, R430-90, Licensed Family Child Care.
3. Compliance with all zoning regulations of the local regulator.
R-4: Residential occupancies shall include buildings arranged for occupancy as Residential Care/Assisted Living Facilities including more than five but not more than 16 occupants, excluding staff.
Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3 except as otherwise provided for in this code or shall comply with the International Residential Code in accordance with Section 101.2.
. . . . . . .
(24) Section 1009.11 [
Exemption]Exception #4 is deleted and replaced with the following:4. In occupancies in Group R-3, as applicable in Section 101.2 and in occupancies in Group U, which are accessory to an occupancy in Group R-3, as applicable in Section 101.2, handrails shall be provided on at least one side of stairways consisting of four or more risers.
(25) Section 1009.11.3 is amended to include the following exception at the end of the section:
Exception. Non-circular handrails serving an individual unit in a Group R-1, Group R-2 or Group R-3 occupancy shall be permitted to have a maximum cross sectional dimension of 3.25 inches (83 mm) measured 2 inches (51 mm) down from the top of the crown. Such handrail is required to have an indention on both sides between 0.625 inch (16 mm) and 1.5 inches (38 mm) down from the top or crown of the cross section. The indentation shall be a minimum of 0.25 inch (6 mm) deep on each side and shall be at least 0.5 (13 mm) high. Edges within the handgrip shall have a minimum radius of 0.0625 inch (2 mm). The handrail surface shall be smooth with no cusps so as to avoid catching clothing or skin.
(26) In Section 1012.2 Exception 3 is added as follows:
3. For occupancies in Group R-3 and within individual dwelling units in occupancies in Group R-2, as applicable in Section 101.2, guards shall form a protective barrier not less than 36 inches (914 mm) in height.
(27) New sections 1109.7.1 and 1109.7.2 are added as follows:
1109.7.1 All platform (wheelchair) lifts shall be capable of independent operation without a key.
1109.7.2 Standby power shall be provided for platform lifts permitted to serve as part of the accessible means of egress.
(28) Section 1208.4 subparagraph 1 is deleted and replaced with the following:
1. The unit shall have a living room of not less than 165 square feet (15.3 [
m]m2) of floor area. An additional 100 square feet (9.3 [m]m2) of floor area shall be provided for each occupant of such unit in excess of two.(29) Section 1405.3 is deleted and replaced with the following:
1405.3 Flashing. Flashing shall be installed in such a manner so as to prevent moisture from entering the wall or to redirect it to the exterior. Flashings shall be installed at the perimeters of exterior door and window assemblies, penetrations and terminations of exterior wall assemblies, exterior wall intersections with roofs, chimneys, porches, decks, balconies and similar projections and at built-in gutters and similar locations where moisture could enter the wall. Flashing with projected flanges shall be installed on both sides and the ends of copings, under sills and continuously above projected trim. A flashing shall be installed at the intersection of the foundation to stucco, masonry, siding or brick veneer. The flashing shall be on an approved corrosion-resistant flashing with a 1/2" drip leg extending past exterior side of the foundation.
. . . . . . .
(41) Section 1608.3.2 is deleted and replaced with the following:
[
1086]1608.3.2 Thermal Factor. The value for the thermal factor, Ct, used in calculation of pf shall be determined from Table 1608.3.2.Exception: Except for unheated structures, the value of Ct need not exceed 1.0 when ground snow load, Pg, is calculated using Section 1608.1.1 as amended.
. . . . . . .
(59) The following referenced standard is added under NFPA in chapter 35:
TABLE
Referenced in code
Number Title Section number
720-99 Recommended Practice for the 907.2.10.1, 907.2.10.5
Installation of Household Carbon
Monoxide (CO) Warning Equipment(60) In Chapter 35, Referenced Standards, the following NFPA referenced standards are deleted and replaced with the current versions as follows:
TABLE
DELETED REPLACED BY
13 - 99 13 - 02 Installation of Sprinkler Systems
13D - 99 13D - 02 Installation of Sprinkler Systems in
One- and Two-family Dwellings and
Manufactured Homes
13R - 99 13R - 02 Installation of Sprinkler Systems in
Residential Occupancies Up to and
Including Four Stories in Height
72 - 99 72 - 02 National Fire Alarm Code
101 - 00 101 - 03 Life Safety CodeR156-56-707. Statewide Amendments to the IPC.
The following are adopted as amendments to the IPC to be applicable statewide:
. . . . . . .
(20) A new section 406.4 is added as follows:
406.4 Automatic clothes washer metal safe pans. Metal safe pans, when installed under automatic clothes washers, shall only be allowed to receive the unintended discharge from a leaking appliance, valve, supply hose, or overflowing waste water from the clothes washer standpipe. Clothes washer metal safe pans shall not be used as indirect waste receptors to receive the discharge of waste water from any other equipment, appliance, appurtenance, drain pipe, etc. Each safe pan shall be provided with an approved trap seal primer, conforming to ASSE 1018 or 1044 or a deep seal trap. The sides of the safe pan shall be no less than 1 1/2" high and shall be soldered at the joints to provide a water tight seal.
406.4.1 Safe pan outlet. The safe pan outlet shall be no less than 1 1/2" in diameter and shall be located in a visible and accessible location to facilitate cleaning and maintenance. The outlet shall be flush with the surface of the pan so as not to allow water retention within the pan.
(21) Section 412.1 is deleted and replaced with the following:
412.1 Approval. Floor drains shall be made of ABS, PVC, cast-iron, stainless steel, brass, or other approved materials that are listed for the use.
(22) Section 412.5 is added as follows:
412.5 Public toilet rooms. All public toilet rooms shall be equipped with at least one floor drain.
(23) Section 417.5.2 is deleted and replaced with the following:
417.5.2 Shower lining. Floors under shower compartments, except where prefabricated receptors have been provided, shall be lined and made water tight utilizing material complying with Sections 417.5.2.1 through 417.5.2.4. Such liners shall turn up on all sides at least three inches (76.2 mm) above the finished threshold level. Liners shall be recessed and fastened to an approved backing so as not to occupy the space required for wall covering, and shall not be nailed or perforated at any point less than two inches (50.8 mm) above finished threshold. Liners shall be pitched one-fourth unit vertical in 12 units horizontal (2-percent slope) and shall be sloped towards the fixture drains and be securely fastened to the waste outlet at the seepage entrance, making a watertight joint between the liner and the outlet.
. . . . . . .
(66) Section 1108 is deleted in its entirety.
(67) Chapter 13, Referenced Standards, is amended as follows:
NSF - Standard Reference Number 61-99 - The following referenced in code section number is added: 608.11
The following reference standard is added:
TABLE
USC- Foundation for Cross-Connection [Control]Table 608.1
FCCCHR Control and Hydraulic Research
9th University of Southern California
Edition Kaprielian Hall 300
Manual Los Angeles CA 90089-2531
of Cross
Connection
Control(68) Appendix C of the IPC, Gray Water Recycling Systems as amended herein shall not be adopted by any local jurisdiction until such jurisdiction has requested Appendix C as amended to be adopted as a local amendment and such local amendment has been approved as a local amendment under these rules.
. . . . . . .
R156-56-711. Statewide Amendments to the IRC.
The following are adopted as amendments to the IRC to be applicable statewide:
(1) All amendments to the IBC under Section R156-56-704, local amendments under Section R156-56-705, the NEC under Section R156-56-706, the IPC under Section R156-56-707, the IMC under Section R156-56-708, the IFGC under Section R156-56-709 and the IECC under Section R156-56-710 which may be applied to detached one and two family dwellings and multiple single family dwellings shall be applicable to the corresponding provisions of the IRC. All references to the International Electrical Code are deleted and replaced with the National Electrical Code adopted under Section R156-56-701(1)(b). Should there be any conflicts between the NEC and the IRC, the NEC shall prevail.
. . . . . . .
(12) Section R304.3 is deleted and replaced with the following:
R304.3 Minimum dimensions. Habitable rooms shall not be less than 7 feet (2134 mm) in any horizontal dimension.
Exception: Kitchens shall have a clear passageway of not less than 3 feet (914 mm) between counter fronts and appliances or counter fronts and walls.
(13) [
In Section R311.4.3 the exceptions are deleted and replaced with the following:Exception to the first paragraph:Exception: Where a stairway with a rise of less than 30 inches (762 mm) is located on the exterior side of a door, other than the required exit door, a landing is not required for the exterior side of the door.Exception to the second paragraph:Exception: The landing at an exterior doorway shall not be more than 8 inches (203 mm) below the top of the threshold, provided the door, other than an exterior storm or screen door, does not swing over the landing.(14)]Section R311.5.3 is deleted and replaced with the following:R311.5.3 Treads and risers. The maximum riser height shall be 8 inches (203 mm) and the minimum tread depth shall be 9 inches (229 mm). The riser height shall be measured vertically between leading edges of the adjacent treads. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. The walking surface of treads and landings of a stairway shall be sloped no steeper than one unit vertical in 48 units horizontal (2-percent slope). The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm).
R311.5.3.3 Profile. The radius of curvature at the leading edge of the tread shall be no greater than 9/16 inch (14.3 mm). A nosing not less than 3/4 inch (19.1 mm) but not more than 1 1/4 inches (32 mm) shall be provided on stairways with solid risers. The greatest nosing projection shall not exceed shall not exceed the smallest nosing projection by more than 3/8 inches (9.5 mm) between two stories, including the nosing at the level of floors and landings. Beveling of nosing shall not exceed 1/2 inch (12.7 mm). Risers shall be vertical or sloped from the underside of the leading edge of the tread above at an angle not more than 30 degrees from the vertical. Open risers are permitted, provided that the opening between treads does not permit the passage of a 4-inch diameter (102 mm) sphere.
Exceptions.
1. A nosing is not required where the tread depth is a minimum of 10 inches (254 mm).
2. The opening between adjacent treads is not limited on stairs with a total rise of 30 inches (762 mm) or less.
([
15]14) Section R311.5.6 is deleted and replaced with the following:R311.5.6 Handrails. Handrails shall be provided on at least one side of stairways consisting of four or more risers. Handrails shall have a minimum height of 34 inches (864 mm) and a maximum height of 38 inches (965 mm) measured vertically from the nosing of the treads. All required handrails shall be continuous the full length of the stairs from a point directly above the top riser to a point directly above the lowest riser of the stairway. The ends of the handrail shall be returned into a wall or shall terminate in newel post or safety terminals. A minimum clear space of 1 1/2 inches (38 mm) shall be provided between the wall and the handrail.
Exceptions:
1. Handrails shall be permitted to be interrupted by a newel post at a turn.
2. The use of a volute, turnout or starting easing shall be allowed over the lowest tread.
([
16]15) Section R311.5.6.3 is deleted and replaced with the following:R311.5.6.3 Handrail grip size. The handgrip portion of handrails shall have a circular cross section of 1 1/4 inches (32mm) minimum to 2 5/8 inches (67mm) maximum. Edges shall have a minimum radius of 1/8 inch (3.2mm).
Exception: Non-circular handrails shall be permitted to have a maximum cross sectional dimension of 3.25 inches (83mm) measured 2 inches (51 mm) down from the top of the crown. Such handrail is required to have an indentation on both sides between 0.625 inch (16mm) and 1.5 inches (38mm) down from the top or crown of the cross section. The indentation shall be a minimum of 0.25 inch (6mm) deep on each side and shall be at least 0.5 inch (13 mm)high. Edges within the handgrip shall have a minimum radius of 0.0625 inch (2 mm). The handrail surface shall be smooth with no cusps so as to avoid catching clothing or skin.
([
17]16) Section R313 is deleted and replaced with the following:R313.1 Single- and multiple-station smoke alarms. Single- and multiple-station smoke alarms shall be installed in the following locations:
1. In each sleeping room.
2. Outside of each separate sleeping area in the immediate vicinity of the bedrooms.
3. On each additional story of the dwelling, including basements and cellars but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.
All smoke alarms shall be listed and installed in accordance with the provisions of this code and the household fire warning equipment provision of NFPA 72.
R313.2 Carbon monoxide alarms. Carbon monoxide alarms shall be installed on each habitable level of a dwelling unit equipped with fuel burning appliances. All carbon monoxide detectors shall be listed and comply with U.L. 2034 and shall be installed in accordance with provisions of this code and NFPA 720.
R313.3 Interconnection of alarms. When multiple alarms are required to be installed within an individual dwelling unit, the alarm devices shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed. Approved combination smoke- and carbon-monoxide detectors shall be permitted.
R313.4 Power source. In new construction, the required alarms shall receive their primary power from the building wiring when such wiring is served from a commercial source, and when primary power is interrupted, shall receive power from a battery. Wiring shall be permanent and without a disconnecting switch other than those required for overcurrent protection. Alarms shall be permitted to be battery operated when installed in buildings without commercial power or in buildings that undergo alterations, repairs, or additions regulated by Section R313.5
R313.5 Alterations, repairs and additions. When interior alterations, repairs or additions requiring a permit occur, or when one or more sleeping rooms are added or created in existing dwellings, the individual dwelling unit shall be provided with alarms located as required for new dwellings; the alarms shall be interconnected and hard wired.
Exceptions:
1. Alarms in existing areas shall not be required to be interconnected and hard wired where the alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space, or basement available which could provide access for hard wiring and interconnection without the removal of interior finishes.
2. Repairs to the exterior surfaces of dwellings are exempt from the requirements of this section.
([
18]17) In Section 317.3.2 Exception 1.1 is deleted and replaced with the following:1.1 By a horizontal distance of not less than the width of a stud space regardless of stud spacing, or
([
19]18) In Section R403.1.4.1 exception 1 is deleted and replaced with the following:1. Freestanding accessory structures, not intended for human occupancy, with an area of 1,000 square feet (93m2) or less, of wood framed construction, with an eave height of 10 feet (3080 mm) or less shall not be required to be protected.
([
20]19) In Section R403.1.6 the exception is deleted and replaced with the following exceptions:Exceptions:
1. Foundation anchor straps, spaced as required to provide equivalent anchorage to 1/2 inch diameter (12.7 mm) anchor bolts.
2. When anchor bolt spacing does not exceed 32 inches (816 mm) apart, anchor bolts may be placed with a minimum of two bolts per plate section located not less than 4 inches (102 mm) from each end of each plate section at interior bearing walls, interior braced wall lines and at all exterior walls.
([
21]20) In Section R403.1.6.1 the following exception is added at the end of Item 2 and Item 3:Exception: When anchor bolt spacing does not exceed 32 inches (816 mm) apart, anchor bolts may be placed with a minimum of two bolts per plate section located not less than 4 inches (102 mm) from each end of each plate section at interior bearing walls, interior braced wall lines and at all exterior walls.
([
22]21) Section R703.6 is deleted and replaced with the following:R703.6 Exterior plaster.
R703.6.1 Lath. All lath and lath attachments shall be of corrosion-resistant materials. Expanded metal or woven wire lath shall be attached with 1 1/2 inch-long (38 mm), 11 gage nails having 7/16 inch (11.1 mm) head, or 7/8-inch-long (22.2 mm), 16 gage staples, spaced at no more than 6 inches (152 mm), or as otherwise approved.
R703.6.2 Weather-resistant barriers. Weather-resistant barriers shall be installed as required in Section R703.2 and, where applied over wood-based sheathing, shall include a weather-resistive vapor permeable barrier with a performance at least equivalent to two layers of Grade D paper.
R703.6.3 Plaster. Plastering with portland cement plaster shall be not less than three coats when applied over metal lath or wire lath and shall be not less than two coats when applied over masonry, concrete or gypsum backing. If the plaster surface is completely covered by veneer or other facing material or is completed concealed, plaster application need be only two coats, provided the total thickness is as set forth in Table R702.1(1). On wood-frame construction with an on-grade floor slab system, exterior plaster shall be applied in such a manner as to cover, but not extend below, lath, paper and screed.
The proportion of aggregate to cementitious materials shall be as set forth in Table R702.1(3).
([
23]22) In Section R703.8, number 8 is added as follows:8. At the intersection of foundation to stucco, masonry, siding, or brick veneer with an approved corrosive-resistance flashing with a 1/2" drip leg extending past exterior side of the foundation.
([
24]23) A new Section G2401.2 is added as follows:G2401.2 Meter Protection. Gas meters shall be protected from physical damage, including falling ice and snow.
([
25]24) Section P2602.3 is added as follows:P2602.3 Individual water supply. Where a potable public water supply is not available, individual sources of potable water supply shall be utilized provided that the source has been developed in accordance with Sections 73-3-1 and 73-3-25, Utah Code Ann. (1953), as amended, as administered by the Department of Natural Resources, Division of Water Rights. In addition, the quality of the water shall be approved by the local health department having jurisdiction.
([
26]25) Section P2602.4 is added as follows:P2602.4 Sewer required. Every building in which plumbing fixtures are installed and all premises having drainage piping shall be connected to a public sewer where the sewer is within 300 feet of the property line in accordance with Section 10-8-38, Utah Code Ann, (1953), as amended; or an approved private sewage disposal system in accordance with Rule R317-501 through R317-513 and Rule R317-5, Utah Administrative Code, as administered by the Department of Environmental Quality, Division of Water Quality.
([
27]26) Section P2603.2.1 is deleted and replaced with the following:P2603.2.1 Protection against physical damage. In concealed locations where piping, other than cast-iron or galvanized steel, is installed through holes or notches in studs, joists, rafters, or similar members less than 1 1/2 inch (38 mm) from the nearest edge of the member, the pipe shall be protected by shield plates. Protective shield plates shall be a minimum of 1/16 inch-thick (1.6 mm) steel, shall cover the area of the pipe where the member is notched or bored, and shall be at least the thickness of the framing member penetrated.
([
28]27) Section P2801.2.1 is added as follows:P2801.2.1 Water heater seismic bracing. In Seismic Design Categories C, D1 and D2, water heaters shall be anchored or strapped in the upper third of the appliance to resist a horizontal force equal to one third the operating weight of the water heater, acting in any horizontal direction, or in accordance with the appliance manufacturers recommendations.
([
29]28) Section P2902.1.1 is added as follows:P2902.1.1 Backflow assembly testing. The premise owner or his designee shall have backflow prevention assemblies operation tested at the time of installation, repair and relocation and at least on an annual basis thereafter, or more frequently as required by the authority having jurisdiction. Testing shall be performed by a Certified Backflow Preventer Assembly Tester. The assemblies that are subject to this paragraph are the Spill Resistant Vacuum Breaker, the Pressure Vacuum Breaker Assembly, the Double Check Backflow Prevention Assembly, the Double Check Detector Assembly Backflow Preventer, the Reduced Pressure Principle Backflow Preventer, and Reduced Pressure Detector Assembly.
([
30]29) Section P3003.2.1 is added as follows:Section P3003.2.1 Improper Connections. No drain, waste, or vent piping shall be drilled and tapped for the purpose of making connections.
([
31]30) In Section P3103.6, the following sentence is added at the end of the paragraph:Vents extending through the wall shall terminate not less than 12 inches from the wall with an elbow pointing downward.
([
32]31) In Section P3104.4, the following sentence is added at the end of the paragraph:Horizontal dry vents below the flood level rim shall be permitted for floor drain and floor sink installations when installed below grade in accordance with Chapter 30, and Sections P3104.2 and P3104.3. A wall cleanout shall be provided in the vertical vent.
([
33]32) Chapter 43, Referenced Standards, is amended as follows:The following reference standard is added:
TABLE
USC- Foundation for Cross-Connection Section P2902
FCCCHR Control and Hydraulic Research
9th University of Southern California
Edition Kaprielian Hall 300
Manual Los Angeles CA 90089-2531
of Cross
Connection
Control([
34]33) In Chapter 43, the following standard is added under NFPA as follows:TABLE
720-98 Recommended Practice for the Installation R313.2
of Household Carbon Monoxide (CO) Warning
EquipmentKEY: contractors, building codes, building inspection, licensing
2004
Notice of Continuation May 16, 2002
Document Information
- Effective Date:
- 8/17/2004
- Publication Date:
- 07/15/2004
- Filed Date:
- 06/24/2004
- Agencies:
- Commerce,Occupational and Professional Licensing
- Rulemaking Authority:
Section 58-56-1; and Subsections 58-1-106(1)(a), 58-1-202(1)(a), 58-56-4(2); and 58-56-6(2)(a)
- Authorized By:
- J. Craig Jackson, Director
- DAR File No.:
- 27101
- Related Chapter/Rule NO.: (1)
- R156-56. Utah Uniform Building Standard Act Rules.