(Amendment)
DAR File No.: 33566
Filed: 04/22/2010 09:17:16 AMRULE ANALYSIS
Purpose of the rule or reason for the change:
The purpose of this filing is to update the rule as necessitated by H.B. 45, H.B. 73 and H.B. 183 which were passed during the 2010 Legislative Session. The proposed amendments clarify duties of the advisory peer committees, update and clarify building code training fund requirements, and make technical cleanup changes. (DAR NOTE: H.B. 45 (2010) is found at Chapter 232, Laws of Utah 2010, and will be effective 07/01/2010. H.B. 73 (2010) is found at Chapter 53, Laws of Utah 2010, and was effective 05/11/2010. H.B. 183 (2010) is found at chapter 310, Laws of Utah 2010, and will be effective 07/01/2010.)
Summary of the rule or change:
The term "rules" has been replaced with "rule" throughout the rule. Also, the words "Division" and "Commission" have been capitalized throughout the rule where appropriate. In Section R156-56-102, amendments delete definitions of "Uniform Building Standards" and "Unprofessional conduct" as they are no longer used in the rule. In Section R156-56-202, amendments clarify the duties of the advisory peer committees. In Section R156-56-303, statute and rule citations are updated. In Section R156-56-420, amendments update current procedures for submitting funding requests to the Uniform Building Code Commission Education Advisory Committee and to clarify the criteria which the Committee shall consider in approving funding grants. In Section R156-56-604, amendments are made due to H.B. 73 which changed the statute citation concerning contractor continuing education requirements. In Sections R156-56-701 and R156-56-703, and the new Sections R156-56-702, R156-56-801, R156-56-802, R156-56-803, R156-56-804, R156-56-805, R156-56-806, R156-56-807, R156-56-808, R156-56-901, R156-56-902, R156-56-903, R156-56-904, R156-56-905, R156-56-906, and R156-56-907, changes to these sections are made as the result of H.B. 45 which now adopts building codes by legislative action rather than by the Division by administrative rule. This filing deletes all adopted codes from the rule. It leaves approved codes which are still approved by the Uniform Building Code Commission and the Division. It also leaves the provisions dealing with the review process for proposed amendments to adopted or approved codes. In Section R156-56-801 (previously Section R156-56-820), the amendments approve codes that were reviewed and approved by the Uniform Building Code Commission and were recommended to the Legislature to be included in H.B. 45. Pursuant to H.B. 183 approved codes are still approved by the Uniform Building Code Commission rather than adopted by the Legislature. Section R156-56-920 is renumbered as Section R156-56-802. It should be noted that even though numerous code books which have been incorporated by reference in this rule are being deleted in this rule filing, updated editions of the code books are now contained in statute as a result of H.B. 45. Therefore, various agencies/persons will still be responsible to purchase/have knowledge concerning those code books.
State statutory or constitutional authorization for this rule:
- Section 58-56-1
- Subsection 58-1-106(1)(a)
- Subsection 58-56-6(2)(a)
- Subsection 58-1-202(1)(a)
- Section 58-56-19
- Subsection 58-56-4(2)
This rule or change incorporates by reference the following material:
- Removes: Table 1805.5(6) entitled "Empirical Foundation Walls", 01/01/2007
- Updates: International Existing Building Code (IEBC), including its appendix chapters, 2009
- Removes: International Building Code (IBC), including Appendix J, 2006
- Removes: International Mechanical Code, 2006
- Removes: Utah Wildland Urban Interface Code (UWUI), 2006
- Removes: International Energy Conservation Code (IECC), 2006
- Removes: National Electrical Code (NEC), 2008
- Removes: International Fuel Gas Code (IFGC), 2006
- Removes: International Plumbing Code (IPC), 2006
- Removes: International Residential Code (IRC), 2006
- Removes: Appendix E of the International Residential Code, 2006
- Removes: Pre-standard and Commentary for the Seismis Rehabilitation of Buildings (FEMA 356), November 2000
- Removes: NFPA 225 Model Manufactured Home Installation Standard, 2005
- Removes: Federal Manufactured Housing Construction and Safety Standards (HUD Code), 04/01/1990
- Adds: ASCE/SEI 41-06, the Seismic Rehabiliation of Existing Buildings, 2007
Anticipated cost or savings to:
the state budget:
The amendments that are being proposed implement legislation from the recent 2010 Legislative Session and will not result in any additional impact on any party beyond what was identified in the legislative fiscal notes associated with the bills identified above.
local governments:
The amendments that are being proposed implement legislation from the recent 2010 Legislative Session and will not result in any additional impact on any party beyond what was identified in the legislative fiscal notes associated with the bills identified above.
small businesses:
The amendments that are being proposed implement legislation from the recent 2010 Legislative Session and will not result in any additional impact on any party beyond what was identified in the legislative fiscal notes associated with the bills identified above.
persons other than small businesses, businesses, or local governmental entities:
The amendments that are being proposed implement legislation from the recent 2010 Legislative Session and will not result in any additional impact on any party beyond what was identified in the legislative fiscal notes associated with the bills identified above.
Compliance costs for affected persons:
The amendments that are being proposed implement legislation from the recent 2010 Legislative Session and will not result in any additional impact on any party beyond what was identified in the legislative fiscal notes associated with the bills identified above.
Comments by the department head on the fiscal impact the rule may have on businesses:
As indicated in the rule summary, this filing conforms the existing rule to recent statutory amendments. No fiscal impact to businesses is anticipated.
Francine A. Giani, Executive Director
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:
Commerce
Occupational and Professional Licensing
160 E 300 S
SALT LAKE CITY, UT 84111-2316Direct questions regarding this rule to:
- Dan Jones at the above address, by phone at 801-530-6720, by FAX at 801-530-6511, or by Internet E-mail at dansjones@utah.gov
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:
06/14/2010
Interested persons may attend a public hearing regarding this rule:
- 06/09/2010 09:00 AM, State Office Building, 450 N State Street, Room 4112, Salt Lake City, UT
This rule may become effective on:
06/21/2010
Authorized by:
Mark Steinagel, Director
RULE TEXT
R156. Commerce, Occupational and Professional Licensing.
R156-56. Utah Uniform Building Standard Act Rule[
s].R156-56-101. Title.
[
These rules are]This rule is known as the "Utah Uniform Building Standard Act Rule[s]".R156-56-102. Definitions.
In addition to the definitions in Title 58, Chapters 1, 55 and 56, as used in Title 58, Chapter 56 or [
these rules]this rule:(1) "Building permit" means, for the purpose of determining the building permit surcharge under Subsection 58-56-9(4), a warrant, license or authorization to build or construct a building or structure or any part thereof.
(2) "Building permit fee" means, for the purpose of determining the building permit surcharge under Subsection 58-56-9(4), fees assessed by an agency of the state or political subdivision of the state for the issuance of permits for construction, alteration, remodeling, and repair and installation including building, electrical, mechanical and plumbing components.
(3) "Employed by a local regulator, state regulator or compliance agency" means, with respect to Subsection 58-56-9(1), the hiring of services of a qualified inspector whether by an employer/employee relationship, an independent contractor relationship, a fee-for-service relationship or any other lawful arrangement under which the regulating agency purchases the services of a qualified inspector.
(4) "Inspector" means a person employed by a local regulator, state regulator or compliance agency for the purpose of inspecting building, electrical, plumbing or mechanical construction, alteration, remodeling, repair or installation in accordance with the codes adopted under [
these rules]this rule and taking appropriate action based upon the findings made during inspection.(5) "Permit number", as used in Sections R156-56-401 and R156-56-402, means the standardized building permit number described below in R156-56-401.
(6) "Refuses to establish a method of appeal" means with respect to Subsection 58-56-8(3), that a compliance agency does not in fact adopt a formal written method of appealing uniform building standard matters in accordance with generally recognized standards of due process; or, that the compliance agency does not convene an appeals board and render a decision in the matter within ninety days from the date on which the appeal is properly filed with the compliance agency.[
(7) "Uniform Building Standards" means the codes identified in Section R156-56-701 and as amended under these rules.(8) "Unprofessional conduct" as defined in Title 58, Chapter 1 is further defined, in accordance with Subsection 58-1-203(5), in Section R156-56-502.]R156-56-103. Authority.
[
These rules are]This rule is adopted by the [d]Division under the authority of Subsection 58-1-106(1)(a) to enable the [d]Division to administer Title 58, Chapter 56.R156-56-105. Board of Appeals.
If the [
c]Commission is required to act as an appeals board in accordance with the provisions of Subsection 58-56-8(3), the following shall regulate the convening and conduct of the special appeals board:(1) If a compliance agency refuses to establish a method of appeal regarding a uniform building standard issue, the appealing party may petition the [
c]Commission to act as the board of appeals.(2) The person making the appeal shall file the request to convene the [
c]Commission as an appeals board in accordance with the requirements for a request for agency action, as set forth in Subsection 63G-4-201(3)(a) and Section R151-46b-7. A request by other means shall not be considered. Any request received by the [c]Commission or [d]Division by any other means shall be returned to the appellant with appropriate instructions.(3) A copy of the final written decision of the compliance agency interpreting or applying a code which is the subject of the dispute shall be submitted as an attachment to the request. If the person making the appeal requests, but does not timely receive a final written decision, the person shall submit an affidavit to this effect in lieu of the final written decision.
(4) The request shall be filed with the [
d]Division no later than 30 days following the issuance of the disputed written decision by the compliance agency.(5) The compliance agency shall file a written response to the request not later than 20 days after the filing of the request. The request and response shall be provided to the [
c]Commission in advance of any hearing in order to properly frame the disputed issues.(6) Except with regard to the time period specified in Subsection (7), the time periods specified in this section may, upon a showing of good cause, be modified by the presiding officer conducting the proceeding.
(7) The [
c]Commission shall convene as an appeals board within 45 days after a request is properly filed.(8) Upon the convening of the [
c]Commission as an appeals board, the board members shall review the issue to be considered to determine if a member of the board has a conflict of interest which would preclude the member from fairly hearing and deciding the issue. If it is determined that a conflict does exist, the member shall be excused from participating in the proceedings.(9) The hearing shall be a formal hearing held in accordance with the Utah Administrative Procedures Act, Title 63G, Chapter 4.
(10) Decisions relating to the application and interpretation of the code made by a compliance agency board of appeals shall be binding for the specific individual case and shall not require [
c]Commission approval.R156-56-106. Fees.
In accordance with Subsection 58-56-9(4), on April 30, July 31, October 31 and January 31 of each year, each agency of the state and each political subdivision of the state which assesses a building permit fee shall file with the [
d]Division a report of building fees and surcharge for the immediately preceding calendar quarter; and, shall remit 80% of the amount of the surcharge to have been assessed to the [d]Division.R156-56-202. Advisory Peer Committees Created - Membership - Duties.
(1) There is created in accordance with Subsection 58-1-203(1)(f) and 58-56-5(10)(e), the following committees as advisory peer committees to the Uniform Building Codes Commission:
(a) the Education Advisory Committee consisting of nine members, which shall include a design professional, a general contractor, an electrical contractor, a mechanical or plumbing contractor, an educator, and four inspectors (one from each of the specialties of plumbing, electrical, mechanical and general building);
(b) the Plumbing and Health Advisory Committee consisting of nine members;
(c) the Structural Advisory Committee consisting of seven members;
(d) the Architectural Advisory Committee consisting of seven members;
(e) the Fire Protection Advisory Committee consisting of five members;
(i) This committee shall join together with the Fire Advisory and Code Analysis Committee of the Utah Fire Prevention Board to form the Unified Code Analysis Council.
(ii) The Unified Code Analysis Council shall meet as directed by the Utah Fire Prevention Board or as directed by the Uniform Building Code Commission or as needed to review fire prevention and building code issues that require definitive and specific analysis.
(iii) The Unified Code Analysis Council shall select one of its members to act in the position of chair and another to act as vice chair. The chair and vice chair shall serve for one year terms on a calendar year basis. Elections for chair and vice chair shall occur at the meeting conducted in the last quarter of the calendar year.
(iv) The chair or vice chair shall report to the Utah Fire Prevention Board or Uniform Building Code Commission recommendations of the council with regard to the review of fire and building codes;
(f) the Mechanical Advisory Committee consisting of seven members; and
(g) the Electrical Advisory Committee consisting of seven members.
(2) The committees shall be appointed and serve in accordance with Section R156-1-205. The membership of each committee shall be made up of individuals who have direct knowledge or involvement in the area of code involved in the title of that committee.
(3) The duties and responsibilities of the committees shall include:
(a) review of codes proposed for adoption or approval as assigned by the Division in collaboration with the Commission;
(b) review of requests for amendments to the adopted codes or approved codes as assigned to each committee by the [
d]Division with the collaboration of the [c]Commission;([
b]c) submission of recommendations concerning the [requests for amendment]reviews made under Subsection (a) and (b); and([
c]d) the Education Advisory Committee shall review and make recommendations regarding funding requests which are submitted, and review and make recommendations regarding budget, revenue and expenses of the education fund established pursuant to Subsection 58-56-9(4).R156-56-302. Licensure of Inspectors.
In accordance with Subsection 58-56-9(1), the licensee classifications, scope of work, qualifications for licensure, and application for license are established as follows:
(1) License Classifications. Each inspector required to be licensed under Subsection 58-56-9(1) shall qualify for licensure and be licensed by the [
d]Division in one of the following classifications:(a) Combination Inspector; or
(b) Limited Inspector.
(2) Scope of Work. The scope of work permitted under each inspector classification is as follows:
(a) Combination Inspector.
(i) Inspect the components of any building, structure or work for which a standard is provided in the specific edition of the codes adopted under [
these rules]this rule or amendments to these codes as included in [these rules]this rule.(ii) Determine whether the construction, alteration, remodeling, repair or installation of all components of any building, structure or work is in compliance with the adopted codes.
(iii) After determination of compliance or noncompliance with the adopted codes take appropriate action as is provided in the aforesaid codes.
(b) Limited Inspector.
(i) A Limited Inspector may only conduct activities under Subsections (ii), (iii) or (iv) for which the Limited Inspector has maintained current certificates under the adopted codes as provided under Subsections R156-56-302(3)(b) and R156-56-302(2)(c)(ii).
(ii) Subject to the limitations of Subsection (i), inspect the components of any building, structure or work for which a standard is provided in the specific edition of the codes adopted under [
these rules]this rule or amendments to these codes as included in [these rules]this rule.(iii) Subject to the limitations under Subsection (i), determine whether the construction, alteration, remodeling, repair or installation of components of any building, structure or work is in compliance with the adopted codes.
(iv) Subject to the limitations under Subsection (i), after determination of compliance or noncompliance with the adopted codes, take appropriate action as is provided in the adopted codes.
(3) Qualifications for Licensure. The qualifications for licensure for each inspector classification are as follows:
(a) Combination Inspector.
Has passed the examination for and maintained as current the following national certifications for codes adopted under [
these rules]this rule:(i) the "Combination Inspector Certification" issued by the International Code Council; or
(ii) all of the following certifications:
(A) the "Building Inspector Certification" issued by the International Code Council or both the "Commercial Building Inspector Certification" and the "Residential Building Inspector Certification" issued by the International Code Council;
(B) the "Electrical Inspector Certification" issued by the International Code Council or the "General Electrical Certification" issued by the International Association of Electrical Inspectors, or both the "Commercial Electrical Inspector Certification" and the "Residential Electrical Inspector Certification" issued by the International Code Council;
(C) the "Plumbing Inspector Certification" issued by the International Code Council, or both the "Commercial Plumbing Inspector Certification" and the "Residential Plumbing Inspector Certification" issued by the International Code Council; and
(D) the "Mechanical Inspector Certification" issued by the International Code Council or both the "Commercial Mechanical Inspector Certification" and the "Residential Mechanical Inspector Certification" issued by the International Code Council.
(b) Limited Inspector.
Has passed the examination for and maintained as current one or more of the following national certifications for codes adopted under [
these rules]this rule:(i) the "Building Inspector Certification" issued by the International Code Council;
(ii) the "Electrical Inspector Certification" issued by the International Code Council or the "General Electrical Certification" issued by the International Association of Electrical Inspectors;
(iii) the "Plumbing Inspector Certification" issued by the International Code Council;
(iv) the "Mechanical Inspector Certification" issued by the International Code Council;
(v) the "Residential Combination Inspector Certification" issued by the International Code Council;
(vi) the "Commercial Combination Certification" issued by the International Code Council;
(vii) the "Commercial Building Inspector Certification" issued by the International Code Council;
(viii) the "Commercial Electrical Inspector Certification" issued by the International Code Council;
(ix) the "Commercial Plumbing Inspector Certification" issued by the International Code Council;
(x) the "Commercial Mechanical Inspector Certification issued by the International Code Council;
(xi) the "Residential Building Inspector Certification" issued by the International Code Council;
(xii) the "Residential Electrical Inspector Certification" issued by the International Code Council;
(xiii) the "Residential Plumbing Inspector Certification" issued by the International Code Council;
(xiv) the "Residential Mechanical Inspector Certification" issued by the International Code Council;
(xv) any other special or otherwise limited inspector certifications used by the International Code Council which certifications cover a part of the codes adopted under [
these rules]this rule including but not limited to each of the following: Reinforced Concrete Special Inspector, Prestressed Concrete Special Inspector, Structural Masonry Special Inspector, Structural Steel and Bolting Special Inspection, Structural Welding Special Inspection, Spray Applied Fire Proofing Special Inspector, Residential Energy Inspector, Commercial Energy Inspector;(xvi) the Certified Welding Inspector Certification issued by the American Welding Society;
(xvii) any other certification issued by an agency specified in Chapter 17 of the IBC or an agency specified in the referenced standards; or
(xviii) any combination certification which is based upon a combination of one or more of the above listed certifications.
(c) If no qualification is listed in the IBC for a special inspector, the special inspector may submit his qualifications to the licensing board for approval.
(4) Application for License.
(a) An applicant for licensure shall:
(i) submit an application in a form prescribed by the [
d]Division; and(ii) pay a fee determined by the department pursuant to Section 63J-1-504.
(5) Code transition provisions.
(a) If an inspector or applicant obtains a new, renewal or recertification or replacement national certificate after a new code or code edition is adopted, the inspector or applicant is required to obtain that certification under the currently adopted code or code edition.
(b) After a new code or new code edition is adopted under [
these rules]this rule, the inspector is required to re-certify their national certification to the new code or code edition at the next available renewal cycle of the national certification.(c) If a licensed inspector fails to obtain the national certification as required in Subsection (a) or (b), their authority to inspect for the area covered by the national certification automatically expires at the expiration date of the national certification that was not obtained as required.
(d) If an inspector recertifies a national certificate on a newer edition of the codes adopted before that newer edition is adopted under [
these rules]this rule, such recertification shall be considered as a current national certification as required by [these rules]this rule.(e) If an inspector complies with these transition provisions, the inspector shall be considered to have a current national certification as required by [
these rules]this rule.R156-56-303. Renewal Cycle - Procedures.
(1) In accordance with Subsection 58-1-308(1) (a), the renewal date for the two-year cycle applicable to licenses under Title 58, Chapter 56 is established by rule in Section R156-1-308 a.
(2) Renewal procedures shall be in accordance with Section R156-1-308 c.
R156-56-420. Administration of Building Code Training Fund.
In accordance with Subsection 58-56-9(3)(a), the Division shall use monies received under Subsection 58-56-9(4) to provide education regarding codes and code amendments to building inspectors and individuals engaged in construction-related trades or professions. The following procedures, standards and policies are established to apply to the administration of the fund:
(1) The Division shall not approve or deny expenditure requests from the Building Code Training Fund ("the fund") until the Uniform Building Code Commission (UBCC) Education Advisory Committee ("the Committee"), created in accordance with Subsections 58-1-203(1)(f), 58-56-5(10)(d) and (e), and R156-56-202(1)(a) has considered and made its recommendations on the requests.
(2) Appropriate funding expenditure categories include:
(a) grants in the form of reimbursement funding to the following organizations which administer code related educational events, seminars or classes:
(i) schools, colleges, universities, departments of universities or other institutions of learning;
(ii) professional associations or organizations; and
(iii) governmental agencies.
(b) costs or expenses incurred as a result of educational events, seminars or classes directly administered by the Division;
(c) expenses incurred for the salary, benefits or other compensation and related expenses resulting from the employment of a Board Secretary;
(d) office equipment and associated administrative expenses required for the performance of the duties of the Board Secretary, including but not limited to computer equipment, telecommunication equipment and costs and general office supplies; and
(e) other related expenses as determined by the Division.
(3) The following procedure shall be used for submission, review and payment of funding grants:
(a) [
A funding grant applicant shall submit a "Tentative Training Plans and Funding Request Estimate" preferably prior to the beginning of the fiscal year for budget consideration.(b)] A funding grant applicant shall submit a completed "Application for Building Code Training Funds Grant" [preferably]a minimum of 15 days prior to the meeting at which the request is to be considered and prior to the training event on forms provided for that purpose by the Division. Applications received less than 15 days prior to a meeting may be denied.[(c) A funding grant applicant shall include in its application a summary and analysis of training costs based upon the estimated costs of the proposed training.]([
d]b) Payment of approved funding grants will be made as reimbursement after the approved event, class, or seminar has been held and the required receipts, invoices and supporting documentation , including proof of payment if requested by the Division or Committee, have been submitted to the Division.(4) The Committee shall consider the following in determining whether to recommend approval of a proposed funding request to the Division:
(a) the fund balance available and whether the proposed request meets the overall training objectives of the fund, including but not limited to:
(i) the need for training on the subject matter;
(ii) the need for training in the geographical area where the training is offered; and
(iii) the need for training on new codes being considered for adoption;
(b) the prior record of the program sponsor in providing codes training including:
(i) whether the subject matter taught was appropriate;
(ii) whether the instructor was appropriately qualified and prepared; and
(iii) whether the program sponsor followed appropriate and adequate procedures and requirements in providing the training and submitting requests for funding;
([
a]c) costs of the facility including:(i) the location of a facility or venue to the type of event, seminar or class;
(ii) the suitability of said facility or venue with regard to the anticipated attendance at or in connection with additional non-funded portions of an event or conference;
(iii) the duration of the proposed educational event, seminar or class; and
(iv) whether the proposed cost of the facility is reasonable compared to the cost of alternative available facilities;
([
b]d) the estimated cost for instructor fees including:(i) the experience or expertise of the instructor in the proposed training area;
(ii) the quality of training based upon events, seminars or classes that have been previously taught by the instructor;
(iii) the drawing power of the instructor, meaning the ability to increase the attendance at the proposed educational event, seminar or class;
(iv) travel expenses; and
(v) whether the proposed cost for the instructor or instructors is reasonable compared to the costs of similar educational events, seminars or classes;
([
c]e) the estimated cost of advertising materials, brochures, registration and agenda materials including:(i) printing costs which may include creative or design expenses; and
(ii) whether delivery or mailing costs, including postage and handling, are reasonable compared to the cost of alternate available means of delivery;
([
d]f) other reasonable and comparable cost alternatives for each proposed expense item; and([
e]g) any other information the Committee reasonably believes may assist in evaluating a proposed expenditure.(5) Joint Functions.
(a) "Joint function" means a proposed event, class, seminar or program that provides code or code related education and education or activities in other areas.
(b) Only the prorated portions of a joint function which are code and code related education are eligible for a funding grant.
(c) In considering a proposed funding request that involves a joint function, the Committee shall consider whether:
(i) the expenses subject to funding are reasonably prorated for the costs directly related to the code and code amendment education; and
(ii) the education being proposed will be reasonable and successful in the training objective in the context of the entire program or event.
(6) Advertising materials, brochures and agenda or training materials for a funded educational event, seminar or class shall include a statement which acknowledges that partial funding of the training program has been provided by the Utah Division of Occupational and Professional Licensing from the 1% surcharge funds on all building permits.
R156-56-501. Administrative Penalties - Unlawful Conduct.
In accordance with Subsections 58-56-9.1 and 58-56-9.5, unless otherwise ordered by the presiding officer, the following fine schedule shall apply:
(1) Engaging in the sale of factory built housing without being registered.
First offense: $500
Second offense: $1,000
(2) Selling factory built housing within the state as a dealer without collecting and remitting to the [
d]Division the fee required by Section 58-56-17.First offense: $500
Second offense: $1,000
(3) Acting as a building inspector or representing oneself to be acting as a building inspector, unless licensed or exempted from licensure under Title 58, Chapter 56 or using the title building inspector or any other description, words, letters, or abbreviation indicating that the person is a building inspector if the person has not been licensed under Title 58, Chapter 56.
First offense: $500
Second offense: $1,000
(4) Acting as a building inspector beyond the scope of the license held.
First offense: $500
Second offense: $1,000
(5) Hiring or employing in any manner an unlicensed person as a building inspector, unless exempted from licensure.
First offense: $800
Second offense: $1,600
(6) Citations shall not be issued for third offenses, except in extraordinary circumstances approved by the investigative supervisor. If a citation is issued for a third offense, the fine is double the second offense amount, with a maximum amount not to exceed the maximum fine allowed under Section 58-56-9.5.
(7) If multiple offenses are cited on the same citation, the fine shall be determined by evaluating the most serious offense.
(8) An investigative supervisor may authorize a deviation from the fine schedule based upon the aggravating or mitigating circumstances.
(9) In all cases the presiding officer shall have the discretion, after a review of the aggravating or mitigating circumstances, to increase or decrease the fine amount based on the evidence reviewed.
R156-56-601. Modular Unit Construction and Set-up.
Modular construction and set-up shall be as set forth in accordance with the following:
(1) Construction shall be in accordance with the building standards accepted by the state pursuant to Section 58-56-4.
(2) The inspection of the construction, modification of or set-up of a modular unit shall be the responsibility of the local regulator; however, nothing in [
these rules]this rule shall preclude the local regulator from entering into an agreement with another qualified person for the inspection of the unit(s) in the manufacturing facility.R156-56-604. Factory Built Housing Continuing Education Requirements.
[
(1)] Pursuant to Subsection 58-56-15(1)(f)(ii), continuing education required for manufactured housing installation contractors is [defined and clarified as follows:(a)] the continuing education required by Subsection [58-55-501(21), which is effective July 1, 2005]58-55-303(2)(b).R156-56-701. [
Specific Editions of Uniform Building Standards]Adopted and Approved Codes.(1) Adopted Codes. The Division shall publish the codes adopted by the Legislature pursuant to Section 58-56-4 on its website as a separate document and adopted codes shall be no longer be incorporated into this rule.[
In accordance with Subsection 58-56-3(1)(b)(ii), and subject to the limitations contained in Subsection (6), (7), and (8), the following codes are hereby incorporated by reference, which codes together with any amendments specified under these rules, are adopted as the construction standards to be applied to building construction, alteration, remodeling and repair and in the regulation of building construction, alteration, remodeling and repair in the state:(a) the 2006 edition of the International Building Code (IBC), including Appendix J promulgated by the International Code Council shall become effective on January 1, 2007;(b) the 2008 edition of the National Electrical Code (NEC) promulgated by the National Fire Protection Association, to become effective January 1, 2009;(c) the 2006 edition of the International Plumbing Code (IPC) promulgated by the International Code Council shall become effective on January 1, 2007;(d) the 2006 edition of the International Mechanical Code (IMC) promulgated by the International Code Council shall become effective on January 1, 2007;(e) the 2006 edition of the International Residential Code (IRC) promulgated by the International Code Council shall become effective on January 1, 2007;(f) the 2006 edition of the International Energy Conservation Code (IECC) promulgated by the International Code Council shall become effective on January 1, 2007;(g) the 2006 edition of the International Fuel Gas Code (IFGC) promulgated by the International Code Council shall become effective on January 1, 2007;(h) subject to the provisions of Subsection (4), the Federal Manufactured Housing Construction and Safety Standards Act (HUD Code) as promulgated by the Department of Housing and Urban Development and published in the Federal Register as set forth in 24 CFR parts 3280 and 3282 as revised April 1, 1990;(i) subject to the provisions of Subsection (4), Appendix E of the 2006 edition of the International Residential Code promulgated by the International Code Council shall become effective on January 1, 2007;(j) subject to the provisions of Subsection (4), the 2005 edition of the NFPA 225 Model Manufactured Home Installation Standard promulgated by the National Fire Protection Association shall become effective January 1, 2007; and(k) the 2006 edition of the Utah Wildland Urban Interface Code (UWUI) promulgated by the International Code Council together with alternatives or amendments approved by the Utah Division of Forestry shall be effective July 1, 2008 as an approved code that may be adopted by the local compliance agency by local ordinance or other similar action as a local amendment to the codes listed in this Subsection.](2) Approved Codes. In accordance with Subsection 58-56-4(6), and subject to the limitations contained in Subsection 58-56-4(7), the following codes or standards are hereby incorporated by reference and approved for use and adoption by a compliance agency as the construction standards which may be applied to existing buildings in the regulation of building alteration, remodeling, repair, removal, seismic evaluation and rehabilitation in the state:
(a) the 1997 edition of the Uniform Code for the Abatement of Dangerous Buildings (UCADB) promulgated by the International Code Council;
(b) the [
2006]2009 edition of the International Existing Building Code (IEBC), including its appendix chapters, promulgated by the International Code Council;(c) ASCE 31-03, Seismic Evaluation of Existing Buildings, promulgated by the American Society of Civil Engineers;
(d) [
Pre-standard and Commentary for]ASCE/SEI 41-06, the Seismic Rehabilitation of Existing Buildings ,[(FEMA 356) published by the Federal Emergency Management Agency (November 2000)]promulgated by the American Society of Civil Engineers, 2007 edition.[(3) Amendments adopted by rule to prior editions of the Uniform Building Standards shall remain in effect until specifically amended or repealed.(4) In accordance with Subsection 58-56-3(1)(b)(ii), the following are hereby adopted as the installation standard for manufactured housing for new installations or for existing manufactured or mobile homes which are subject to relocation, building alteration, remodeling or rehabilitation in the state:(a) The manufacturer's installation instruction for the model being installed shall be the primary standard.(b) If the manufacturer's installation instruction for the model being installed is not available or is incomplete, the following standards shall be applicable:(i) Appendix E of the 2006 edition of the International Residential Code as promulgated by the International Code Council for installations defined in Section AE101 of Appendix E; or(ii) If an installation is beyond the scope of the 2006 edition of the International Residential Code as defined in Section AE101 of Appendix E, then the 2005 edition of the NFPA 225 Model Manufactured Home Installation Standard promulgated by the National Fire Protection Association shall apply.(c) The manufacturer, dealer or homeowner shall be permitted to design for unusual installation of a manufactured home not provided for in the manufacturer's standard installation instruction Appendix E of the 2006 edition of the International Residential Code, or the 2005 edition of the NFPA 225, provided the design is approved in writing by a professional engineer or architect licensed in Utah.(d) For mobile homes built prior to June 15, 1976, the home shall also comply with the additional installation and safety requirements specified in Section R156-56-808.(5) Pursuant to the Federal Manufactured Home Construction and Safety Standards Section 604(d), a manufactured home may be installed in the state of Utah which does not meet the local snow load requirements as specified in Subsection R156-56-801; however all such homes which fail to meet the standards of Subsection R156-56-801 shall have a protective structure built over the home which meets the International Building Code and the snow load requirements under Subsection R156-56-801.(6) To the extent that the building codes adopted under Subsection (1) establish local administrative functions or establish a method of appeal which pursuant to Section 58-56-8 are designated to be established by the compliance agency, such provisions are not included in the codes adopted hereunder but authority over such provisions are reserved to the compliance agency to establish such provisions.(7) To the extent that the building codes adopted under Subsection (1) establish provisions, standards or references to other codes which by state statutes are designated to be established or administered by other state agencies or local city, town or county jurisdictions, such provisions are not included in the codes adopted herein but authority over such provisions are reserved to the agency or local government having authority over such provisions. Provisions excluded under this Subsection include but are not limited to:(a) the International Property Maintenance Code;(b) the International Private Sewage Disposal Code, authority over which would be reserved to the Department of Health and the Department of Environmental Quality;(c) the International Fire Code which pursuant to Section 53-7-106 authority is reserved to the Utah Fire Prevention Board;(d) day care provisions which are in conflict with the Child Care Licensing Act, authority over which is designated to the Utah Department of Health; and(e) wildland urban interface provisions which go beyond the authority of Subsection 58-56-4(2), authority over which is designated to the Utah Division of Forestry or to the local compliance agencies.(8) To the extent that the codes adopted under Subsection (1) establish provisions that exceed the authority granted to the Division, under the Utah Uniform Building Standards Act, to adopt codes or amendments to such codes by rulemaking procedures, such provisions, to the extent such authority is exceeded, are not included in the codes adopted.]R156-56-[
703]702. Requests for Code Amendments.In accordance with Subsection 58-56-7(1), the procedure and manner under which requests for amendments to codes shall be filed with the [
d]Division and recommended or declined for adoption are as follows:(1) All requests for amendments to any of the [
uniform building standards]adopted codes or approved codes shall be submitted to the [d]Division on forms specifically prepared by the [d]Division for that purpose.(2) The processing of requests for code amendments shall be in accordance with [
d]Division policies and procedures.[
R156-56-801. Statewide Amendments to the IBC.The following are adopted as amendments to the IBC to be applicable statewide:(1) All references to the ICC Electrical Code are deleted and replaced with the National Electrical Code adopted under Subsection R156-56-701(1)(b).(2) Section 101.4.1 is deleted and replaced with the following:101.4.1 Electrical. The provisions of the National Electrical Code (NEC) shall apply to the installation of electrical systems, including alterations, repairs, replacement, equipment, appliances, fixtures, fittings and appurtenances thereto.(3) Section 106.3.2 is deleted and replaced with the following:106.3.2 Previous approval. If a lawful permit has been issued and the construction of which has been pursued in good faith within 180 days after the effective date of the code and has not been abandoned, then the construction may be completed under the code in effect at the time of the issuance of the permit.(4) In Section 109, a new section is added as follows:109.3.5 Weather-resistive barrier and flashing. An inspection shall be made of the weather-resistive barrier as required by Section 1403.2 and flashing as required by Section 1405.3 to prevent water from entering the weather-resistant exterior wall envelope.The remaining sections will be renumbered as follows:109.3.6 Lath or gypsum board inspection109.3.7 Fire-resistant penetrations109.3.8 Energy efficiency inspections109.3.9 Other inspections109.3.10 Special inspections109.3.11 Final inspection.(5) Section 114.1 is deleted and replaced with the following:114.1 Authority. Whenever the building official finds any work regulated by this code being performed in a manner either contrary to the provisions of this code or other pertinent laws or ordinances or dangerous or unsafe, the building official is authorized to stop work.(6) In Section 202, the definition for Assisted Living Facility is deleted and replaced with the following:ASSISTED LIVING FACILITY. See Section 308.1.1.(7) Section 305.2 is deleted and replaced with the following:305.2 Day care. The building or structure, or portion thereof, for educational, supervision, child day care centers, or personal care services of more than four children shall be classified as a Group E occupancy. See Section 421 for special requirements for Group E child day care centers.Exception: Areas used for child day care purposes with a Residential Certificate, Family License or Family Group License may be located in a Group R-2 or R-3 occupancy as provided in Section 310.1 or shall comply with the International Residential Code in accordance with Section 101.2.Child day care centers providing care for more than 100 children 2 1/2 years or less of age shall be classified as Group I-4.(8) In Section 308 the following definitions are added:308.1.1 Definitions. The following words and terms shall, for the purposes of this section and as used elsewhere in this code, have the meanings shown herein.TYPE I ASSISTED LIVING FACILITY. A residential facility licensed by the Utah Department of Health that provides a protected living arrangement for ambulatory, non-restrained persons who are capable of achieving mobility sufficient to exit the facility without the assistance of another person.TYPE II ASSISTED LIVING FACILITY. A residential facility licensed by the Utah Department of Health that provides an array of coordinated supportive personal and health care services to residents who meet the definition of semi-independent.SEMI-INDEPENDENT. A person who is:A. Physically disabled but able to direct his or her own care; orB. Cognitively impaired or physically disabled but able to evacuate from the facility with the physical assistance of one person.RESIDENTIAL TREATMENT/SUPPORT ASSISTED LIVING FACILITY. A residential treatment/support assisted living facility which creates a group living environment for four or more residents licensed by the Utah Department of Human Services, and provides a protected living arrangement for ambulatory, non-restrained persons who are capable of achieving mobility sufficient to exit the facility without the physical assistance of another person.(9) Section 308.2 is deleted and replaced with the following:308.2 Group I-1. This occupancy shall include buildings, structures, or parts thereof housing more than 16 persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services. The occupants are capable of responding to an emergency situation without physical assistance from staff. This group shall include, but not be limited to, the following: residential board and care facilities, type I assisted living facilities, residential treatment/support assisted living facility, half-way houses, group homes, congregate care facilities, social rehabilitation facilities, alcohol and drug centers and convalescent facilities. A facility such as the above with five or fewer persons shall be classified as a Group R-3 or shall comply with the International Residential Code in accordance with Section 101.2. A facility such as above, housing at least six and not more than 16 persons, shall be classified as a Group R-4.(10) Section 308.3 is deleted and replaced with the following:308.3 Group I-2. This occupancy shall include buildings and structures used for medical, surgical, psychiatric, nursing or custodial care on a 24-hour basis of more than three persons who are not capable of self-preservation. This group shall include, but not be limited to the following: hospitals, nursing homes (both intermediate care facilities and skilled nursing facilities), mental hospitals, detoxification facilities, ambulatory surgical centers with two or more operating rooms where care is less than 24 hours, outpatient medical care facilities for ambulatory patients (accommodating more than five such patients in each tenant space) which may render the patient incapable of unassisted self-preservation, and type II assisted living facilities. Type II assisted living facilities with five or fewer persons shall be classified as a Group R-4. Type II assisted living facilities as defined in 308.1.1 with at least six and not more than sixteen residents shall be classified as a Group I-1 facility.(11) Section 308.3.1 is deleted and replaced with the following:308.3.1 Child care facility. A child care facility that provides care on a 24 hour basis to more than four children 2 1/2 years of age or less shall be classified as Group I-2.(12) Section 308.5 is deleted and replaced with the following:308.5 Group I-4, day care facilities. This group shall include buildings and structures occupied by persons of any age who receive custodial care less than 24 hours by individuals other than parents or guardians, relatives by blood, marriage, or adoption, and in a place other than the home of the person cared for. A facility such as the above with four or fewer persons shall be classified as an R-3 or shall comply with the International Residential Code in accordance with Section 101.2. Places of worship during religious functions and Group E child day care centers are not included.(13) Section 308.5.2 is deleted and replaced with the following:308.5.2 Child care facility. A facility that provides supervision and personal care on less than a 24 hour basis for more than 100 children 2 1/2 years of age or less shall be classified as Group I-4.(14) Section 310.1 is deleted and replaced with the following:310.1 Residential Group "R". Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classed as an Institutional Group I. Residential occupancies shall include the following:R-1: Residential occupancies where the occupants are primarily transient in nature (less than 30 days) including: Boarding Houses (transient) and congregate living facilities, Hotels (transient), and Motels (transient).Exception: Boarding houses and congregate living facilities accommodating 10 persons or less shall be classified as a Residential Group R-3 or shall comply with the International Residential Code in accordance with Section 101.2.R-2: Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including: Apartment Houses, Boarding houses (not transient) and congregate living facilities, Convents, Dormitories, Fraternities and Sororities, Monasteries, Vacation timeshare properties, Hotels (non transient), and Motels (non transient).Exception: Boarding houses and congregate living facilities accommodating 10 persons or less shall be classified as a Residential Group R-3 or shall comply with the International Residential Code in accordance with Section 101.2.R-3: Residential occupancies where the occupants are primarily permanent in nature and not classified as R-1, R-2, R-4 or I and where buildings do not contain more than two dwelling units, as applicable in Section 101.2, or adult and child care facilities that provide accommodations for five or fewer persons of any age for less than 24 hours. Adult and child care facilities that are within a single family home are permitted to comply with the International Residential Code in accordance with Section 101.2. Areas used for day care purposes may be located in a residential dwelling unit under all of the following conditions:1. Compliance with the Utah Administrative Code, R710-8, Day Care Rules, as enacted under the authority of the Utah Fire Prevention Board.2. Use is approved by the State Department of Health, as enacted under the authority of the Utah Child Care Licensing Act, UCA, Sections 26-39-101 through 26-39-110, and in any of the following categories:a. Utah Administrative Code, R430-50, Residential Certificate Child Care Standards.b. Utah Administrative Code, R430-90, Licensed Family Child Care.3. Compliance with all zoning regulations of the local regulator.R-4: Residential occupancies shall include buildings arranged for occupancy as Residential Care/Assisted Living Facilities or Residential Treatment/Support Assisted Living Facilities including more than five but not more than 16 occupants, excluding staff.Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3 except as otherwise provided for in this code or shall comply with the International Residential Code in accordance with Section 101.2.(15) In Section 310.2 the definition for Residential Care/Assisted Living Facilities is deleted and replaced with the following:See Section 308.1.1.(16) A new section 421 is added as follows:Section 421 Group E Child Day Care Centers. Group E child day care centers shall comply with Section 421.421.1 Location at grade. Group E child day care centers shall be located at the level of exit discharge.Exception: Child day care spaces for children over the age of 24 months may be located on the second floor of buildings equipped with automatic fire protection throughout and an automatic fire alarm system.421.2 Egress. All Group E child day care spaces with an occupant load of more than 10 shall have a second means of egress. If the second means of egress is not an exit door leading directly to the exterior, the room shall have an emergency escape and rescue window complying with Section 1026.(17) In Section 504.2 a new section is added as follows:504.2.1 Notwithstanding the exceptions to Section 504.2, Group I-2 Assisted Living Facilities shall be allowed to be two stories of Type V-A construction when all of the following apply:1. All secured units are located at the level of exit discharge in compliance with Section 1008.1.8.3 as amended;2. The total combined area of both stories shall not exceed the total allowable area for a one-story building; and3. All other provisions that apply in Section 407 have been provided.(18) In Section (F)902, the definition for record drawings is deleted and replaced with the following:(F)RECORD DRAWINGS. Drawings ("as builts") that document all aspects of a fire protection system as installed.(19) In Section (F)903.2.3 condition 2 is deleted and replaced with the following:2. Where a Group F-1 fire area is located more than three stories above the lowest level of fire department vehicle access; or(20) In Section (F)903.2.6 condition 2 is deleted and replaced with the following:2. Where a Group M fire area is located more than three stories above the lowest level of fire department vehicle access; or(21) Section (F)903.2.7 is deleted and replaced with the following:(F)903.2.7 Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area.Exceptions:1. Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) constructed in accordance with the International Residential Code For One- and Two-Family Dwellings.2. Group R-4 fire areas not more than 4,500 gross square feet and not containing more than 16 residents, provided the building is equipped throughout with an approved fire alarm system that is interconnected and receives it primary power from the building wiring and a commercial power system.(22) In Section F903.2.8 condition 2 is deleted and replaced with the following:2. Where a Group S-1 fire area is located more than three stories above the lowest level of fire department vehicle access; or(23) Section (F)903.2.9 is deleted and replaced with the following:(F)903.2.9 Group S-2. An automatic sprinkler system shall be provided throughout buildings classified as parking garages in accordance with Section 406.2 or where located beneath other groups.Exception 1: Parking garages of less than 5,000 square feet (464 m 2)accessory to Group R-3 occupancies.Exception 2: Open parking garages not located beneath other groups if one of the following conditions is met:a. Access is provided for fire fighting operations to within 150 feet (45,720 mm) of all portions of the parking garage as measured from the approved fire department vehicle access; orb. Class I standpipes are installed throughout the parking garage.(24) In Section (F)903.2.9.1 the last clause "where the fire area exceeds 5,000 square feet (464 m 2)" is deleted.(25) Section (F)904.11 and Subsections (F)904.11.3, (F)904.11.3.1, (F)904.11.4 and (F)904.11.4.1 are deleted and replaced with the following:(F)904.11 Commercial cooking systems. The automatic fire-extinguishing system for commercial cooking systems shall be of a type recognized for protection of commercial cooking equipment and exhaust systems of the type and arrangement protected. Pre-engineered automatic extinguishing systems shall be tested in accordance with UL 300 and listed and labeled for the intended application. The system shall be installed in accordance with this code, its listing and the manufacturer's installation instructions. Automatic fire-extinguishing systems shall be installed in accordance with the referenced standard for wet-chemical extinguishing systems, NFPA 17A.Exception: Factory-built commercial cooking recirculating systems that are tested in accordance with UL 710B and listed, labeled and installed in accordance with Section 304.1 of the International Mechanical Code.(Subsections (F)904.11.1 and (F)904.11.2 remain unchanged.(26) Section (F)907.2.10 is deleted and replaced with the following:(F)907.2.10 Single- and multiple-station alarms. Listed single- and multiple-station smoke alarms complying with U.L. 217 shall be installed in accordance with the provision of this code and the household fire-warning equipment provision of NFPA 72. Listed single- and multiple-station carbon monoxide detectors shall comply with U.L. 2034 and shall be installed in accordance with the provisions of this code and NFPA 720.(F)907.2.10.1 Smoke alarms. Single- or multiple-station smoke alarms shall be installed in the locations described in Sections (F)907.2.10.1.1 through (F)907.2.10.1.3.(F)907.2.10.1.1 Group R-1. Single- or multiple-station smoke alarms shall be installed in all of the following locations in Group R-1:1. In sleeping areas.2. In every room in the path of the means of egress from the sleeping area to the door leading from the sleeping unit.3. In each story within the sleeping unit, including basements. For sleeping units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.(F)907.2.10.1.2 Groups R-2, R-3, R-4 and I-1. Single- or multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4 and I-1, regardless of occupant load at all of the following locations:1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms.2. In each room used for sleeping purposes.3. In each story within a dwelling unit, including basements and cellars but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.(F)907.2.10.1.3 Group I-1. Single- or multiple-station smoke alarms shall be installed and maintained in sleeping areas in occupancies in Group I-1.Exception: Single- or multiple-station smoke alarms shall not be required where the building is equipped throughout with an automatic fire detection system in accordance with Section (F)907.2.6.(F)907.2.10.2 Carbon monoxide alarms. Carbon monoxide alarms shall be installed on each habitable level of a dwelling unit or sleeping unit in Groups R-2, R-3, R-4 and I-1 equipped with fuel burning appliances.(F)907.2.10.3. Power source. In new construction, required alarms shall receive their primary power from the building wiring where such wiring is served from a commercial source and shall be equipped with a battery backup. Alarms shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than as required for overcurrent protection.Exception: Alarms are not required to be equipped with battery backup in Group R-1 where they are connected to an emergency electrical system.(F)907.2.10.4 Interconnection. Where more than one alarm is required to be installed with an individual dwelling unit in Group R-2, R-3, or R-4, or within an individual sleeping unit in Group R-1, the alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed. Approved combination smoke and carbon-monoxide detectors shall be permitted.(F)907.2.10.5 Acceptance testing. When the installation of the alarm devices is complete, each detector and interconnecting wiring for multiple-station alarm devices shall be tested in accordance with the household fire warning equipment provisions of NFPA 72 and NFPA 720, as applicable.(27) In Section 1007.3 a new exception 6 is added as follows:6. Areas of refuge are not required at exit stairways in buildings or facilities equipped throughout with an automatic fire sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.(28) In Section 1007.4 the word "exception" is changed to "exception 1" and an exception 2 is added as follows:2. Elevators are not required to be accessed from an area of refuge or horizontal exit in buildings or facilities equipped throughout with an automatic fire sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.(29) In Section 1008.1.8.3, a new subparagraph (5) is added as follows:(5) Doors in Group I-1 and I-2 occupancies, where the clinical needs of the patients require specialized security measures for their safety, approved access controlled egress may be installed when all the following are met:5.1 The controlled egress doors shall unlock upon activation of the automatic fire sprinkler system or automatic fire detection system.5.2 The facility staff can unlock the controlled egress doors by either sensor or keypad.5.3 The controlled egress doors shall unlock upon loss of power.(30) In Section 1009.3, Exception #4 is deleted and replaced with the following:4. In Group R-3 occupancies, within dwelling units in Group R-2 occupancies, and in Group U occupancies that are accessory to a Group R-3 occupancy, or accessory to individual dwelling units in Group R-2 occupancies, the maximum riser height shall be 8 inches (203 mm) and the minimum tread depth shall be 9 inches (229 mm). The minimum winder tread depth at the walk line shall be 10 inches (254 mm), and the minimum winder tread depth shall be 6 inches (152 mm). A nosing not less than 0.75 inch (19.1 mm) but not more than 1.25 inches (32 mm) shall be provided on stairways with solid risers where the tread depth is less than 10 inches (254 mm).(31) In Section 1009.10 Exception 6 is added as follows:6. In occupancies in Group R-3, as applicable in Section 101.2 and in occupancies in Group U, which are accessory to an occupancy in Group R-3, as applicable in Section 101.2, handrails shall be provided on at least one side of stairways consisting of four or more risers.(32) Section 1012.3 is amended to include the following exception at the end of the section:Exception. Non-circular handrails serving an individual unit in a Group R-1, Group R-2 or Group R-3 occupancy with a perimeter greater than 6 1/4 inches (160 mm) shall provide a graspable finger recess area on both sides of the profile. The finger recess shall begin within a distance of 3/4 inch (19 mm) measured vertically from the tallest portion of the profile and achieve a depth of at least 5/16 inch (8 mm) within 7/8 inch (22 mm) below the widest portion of the profile. This required depth shall continue for at least 3/8 inch (10 mm) to a level that is not less than 1 3/4 inches (45 mm) below the tallest portion of the profile. The minimum width of the handrail above the recess shall be 1 1/4 inches (32 mm) to a maximum of 2 3/4 inches (70 mm). Edges shall have a minimum radius of 0.01 inch (0.25 mm).(33) In Section 1013.2 Exception 3 is added as follows:3. For occupancies in Group R-3 and within individual dwelling units in occupancies in Group R-2, as applicable in Section 101.2, guards shall form a protective barrier not less than 36 inches (914 mm) in height.(34) In Section 1015.2.2 the following sentence is added at the end:Additional exits or exit access doorways shall be arranged a reasonable distance apart so that if one becomes blocked, the others will be available.(35) A new Section 1109.7.1 is added as follows:1109.7.1 Platform (wheelchair) lifts. All platform (wheelchair) lifts shall be capable of independent operation without a key.(36) In Section 1208.4 subparagraph 1 is deleted and replaced with the following:1. The unit shall have a living room of not less than 165 square feet (15.3 m 2) of floor area. An additional 100 square feet (9.3 m 2) of floor area shall be provided for each occupant of such unit in excess of two.(37) Section 1405.3 is deleted and replaced with the following:1405.3 Flashing. Flashing shall be installed in such a manner so as to prevent moisture from entering the wall or to redirect it to the exterior. Flashings shall be installed at the perimeters of exterior door and window assemblies, penetrations and terminations of exterior wall assemblies, exterior wall intersections with roofs, chimneys, porches, decks, balconies and similar projections and at built-in gutters and similar locations where moisture could enter the wall. Flashing with projected flanges shall be installed on both sides and the ends of copings, under sills and continuously above projected trim. A flashing shall be installed at the intersection of the foundation to stucco, masonry, siding or brick veneer. The flashing shall be on an approved corrosion-resistant flashing with a 1/2" drip leg extending past exterior side of the foundation.(38) In Section 1605.2.1, the formula shown as "f 2 = 0.2 for other roof configurations" is deleted and replaced with the following:f 2 = 0.20 + .025(A-5) for other configurations where roof snow load exceeds 30 psff 2 = 0 for roof snow loads of 30 psf (1.44kN/m 2) or less.Where A = Elevation above sea level at the location of the structure (ft/1000).(39) In Section 1605.3.1 and section 1605.3.2, Exception number 2 in each section is deleted and replaced with the following:2. Flat roof snow loads of 30 pounds per square foot (1.44 kNm 2) or less need not be combined with seismic loads. Where flat roof snow loads exceed 30 pounds per square foot (1.44 kNm 2), the snow loads may be reduced in accordance with the following in load combinations including both snow and seismic loads. W s as calculated below, shall be combined with seismic loads.W s = (0.20 + 0.025(A-5))P f is greater than or equal to 0.20 P fWhereW s = Weight of snow to be included in seismic calculations;A = Elevation above sea level at the location of the structure (ft/1000)P f = Design roof snow load, psfFor the purpose of this section, snow load shall be assumed uniform on the roof footprint without including the effects of drift or sliding. The Importance Factor, I, used in calculating P f may be considered 1.0 for use in the formula for W s.(40) In Table 1607.1 number 9 is deleted and replaced with the following:TABLE 1607.1 NUMBER 9Occupancy or Use Uniform Concentrated
(psf) (lbs)
9. Decks, except residential Same as occupancy
servedh
9.1 Residential decks 60 psf(41) Section 1608.1 is deleted and replaced with the following:1608.1 General. Except as modified in section 1608.1.1, 1608.1.2, and 1608.1.3 design snow loads shall be determined in accordance with Section 7 of ASCE 7, but the design roof load shall not be less than that determined by Section 1607.(42) Section 1608.1.1 is added as follows:1608.1.1 Section 7.4.5 of Section 7 of ASCE 7 referenced in Section 1608.1 of the IBC is deleted and replaced with the following:Section 7.4.5 Ice Dams and Icicles Along Eaves. Where ground snow loads exceed 75 psf, eaves shall be capable of sustaining a uniformly distributed load of 2p f on all overhanging portions. No other loads except dead loads shall be present on the roof when this uniformly distributed load is applied. All building exits under down-slope eaves shall be protected from sliding snow and ice.(43) Section 1608.1.2 is added as follows:1608.1.2 Utah Snow Loads. The ground snow load, P g, to be used in the determination of design snow loads for buildings and other structures shall be determined by using the following formula: P g = (P o 2 + S 2(A-A o) 2) 0.5 for A greater than A o, and P g = P o for A less than or equal to A o.WHEREP g = Ground snow load at a given elevation (psf)P o = Base ground snow load (psf) from Table No. 1608.1.2(a)S = Change in ground snow load with elevation (psf/100 ft.) From Table No. 1608.1.2(a)A = Elevation above sea level at the site (ft./1000)A o = Base ground snow elevation from Table 1608.1.2(a) (ft./1000)The building official may round the roof snow load to the nearest 5 psf. The ground snow load, P g, may be adjusted by the building official when a licensed engineer or architect submits data substantiating the adjustments. A record of such action together with the substantiating data shall be provided to the division for a permanent record.The building official may also directly adopt roof snow loads in accordance with Table 1608.1.2(b), provided the site is no more than 100 ft. higher than the listed elevation.Where the minimum roof live load in accordance with section 1607.11 is greater than the design roof snow load, such roof live load shall be used for design, however, it shall not be reduced to a load lower than the design roof snow load. Drifting need not be considered for roof snow loads less than 20 psf.(44) Table 1608.1.2(a) and Table 1608.1.2(b) are added as follows:TABLE NO. 1608.1.2(a)
STATE OF UTAH - REGIONAL SNOW LOAD FACTORS
COUNTY Po S A o
Beaver 43 63 6.2
Box Elder 43 63 5.2
Cache 50 63 4.5
Carbon 43 63 5.2
Daggett 43 63 6.5
Davis 43 63 4.5
Duchesne 43 63 6.5
Emery 43 63 6.0
Garfield 43 63 6.0
Grand 36 63 6.5
Iron 43 63 5.8
Juab 43 63 5.2
Kane 36 63 5.7
Millard 43 63 5.3
Morgan 57 63 4.5
Piute 43 63 6.2
Rich 57 63 4.1
Salt Lake 43 63 4.5
San Juan 43 63 6.5
Sanpete 43 63 5.2
Sevier 43 63 6.0
Summit 86 63 5.0
Tooele 43 63 4.5
Uintah 43 63 7.0
Utah 43 63 4.5
Wasatch 86 63 5.0
Washington 29 63 6.0
Wayne 36 63 6.5
Weber 43 63 4.5TABLE NO. 1608.1.2(b)
RECOMMENDED SNOW LOADS FOR SELECTED UTAH CITIES AND TOWNS(2)
Roof Snow Ground Snow
Load (PSF) Load (PSF)
Beaver County
Beaver 5920 ft. 43 62
Box Elder County
Brigham City 4300 ft. 30 43
Tremonton 4290 ft. 30 43
Cache County
Logan 4530 ft. 35 50
Smithfield 4595 ft. 35 50
Carbon County
Price 5550 ft. 30 43
Daggett County
Manila 5377 ft. 30 43
Davis County
Bountiful 4300 ft. 30 43
Farmington 4270 ft. 30 43
Layton 4400 ft. 30 43
Fruit Heights 4500 ft. 40 57
Duchesne County
Duchesne 5510 ft. 30 43
Roosevelt 5104 ft. 30 43
Emery County
Castledale 5660 ft. 30 43
Green River 4070 ft. 25 36
Garfield County
Panguitch 6600 ft. 30 43
Grand County
Moab 3965 ft. 25 36
Iron County
Cedar City 5831 ft. 30 43
Juab County
Nephi 5130 ft. 30 43
Kane County
Kanab 5000 ft. 25 36
Millard County
Millard 5000 ft. 30 43
Delta 4623 ft. 30 43
Morgan County
Morgan 5064 ft. 40 57
Piute County
Piute 5996 ft. 30 43
Rich County
Woodruff 6315 ft. 40 57
Salt Lake County
Murray 4325 ft. 30 43
Salt Lake City 4300 ft. 30 43
Sandy 4500 ft. 30 43
West Jordan 4375 ft. 30 43
West Valley 4250 ft. 30 43
San Juan County
Blanding 6200 ft. 30 43
Monticello 6820 ft. 35 50
Sanpete County
Fairview 6750 ft. 35 50
Mt. Pleasant 5900 ft. 30 43
Manti 5740 ft. 30 43
Ephraim 5540 ft. 30 43
Gunnison 5145 ft. 30 43
Sevier County
Salina 5130 ft. 30 43
Richfield 5270 ft. 30 43
Summit County
Coalville 5600 ft. 60 86
Kamas 6500 ft. 70 100
Park City 6800 ft. 100 142
Park City 8400 ft. 162 231
Summit Park 7200 ft. 90 128
Tooele County
Tooele 5100 ft. 30 43
Uintah County
Vernal 5280 ft. 30 43
Utah County
American Fork 4500 ft. 30 43
Orem 4650 ft. 30 43
Pleasant Grove 5000 ft. 30 43
Provo 5000 ft. 30 43
Spanish Fork 4720 ft. 30 43
Wasatch County
Heber 5630 ft. 60 86
Washington County
Central 5209 ft. 25 36
Dameron 4550 ft. 25 36
Leeds 3460 ft. 20 29
Rockville 3700 ft. 25 36
Santa Clara 2850 ft. 15 (1) 21
St. George 2750 ft. 15 (1) 21
Wayne County
Loa 7080 ft. 30 43
Hanksville 4308 ft. 25 36
Weber County
North Ogden 4500 ft. 40 57
Ogden 4350 ft. 30 43
NOTES
(1) The IBC requires a minimum live load - See 1607.11.2.
(2) This table is informational only in that actual site
elevations may vary. Table is only valid if site elevation is
within 100 feet of the listed elevation.(45) Section 1608.1.3 is added as follows:1608.1.3 Thermal Factor. The value for the thermal factor, C t, used in calculation of p f shall be determined from Table 7.3 in ASCE 7.Exception: Except for unheated structures, the value of C t need not exceed 1.0 when ground snow load, P g is calculated using Section 1608.1.2 as amended.(46) Section 1608.2 is deleted and replaced with the following:1608.2 Ground Snow Loads. The ground snow loads to be used in determining the design snow loads for roofs in states other than Utah are given in Figure 1608.2 for the contiguous United States and Table 1608.2 for Alaska. Site-specific case studies shall be made in areas designated CS in figure 1608.2. Ground snow loads for sites at elevations above the limits indicated in Figure 1608.2 and for all sites within the CS areas shall be approved. Ground snow load determination for such sites shall be based on an extreme value statistical analysis of data available in the vicinity of the site using a value with a 2-percent annual probability of being exceeded (50-year mean recurrence interval). Snow loads are zero for Hawaii, except in mountainous regions as approved by the building official.(47) In Section 1609.1.1 a new exception number 5 is added as follows:5. The wind design procedure as found in Section 1616 through 1624 of the 1997 Uniform Building Code may be used as an alternative wind design procedure for:(a) items 1 through 3 listed in Table 16-H of the 1997 Uniform Building Code provided that the building or component being designed meets the limits for the Simplified Method as defined in ASCE 6.4.1.1 and 6.4.1.2 of ASCE 7; or(b) items 4 through 7 listed in Table 16-H of the 1997 Uniform Building Code.The Importance Factor, I, shall be determined in accordance with Table 6-1 of ASCE 7.(48) Section 1613.7 is added as follows:1613.7 ASCE 12.7.2 and 12.14.18.1 of Section 12 of ASCE 7 referenced in Section 1613.1, Definition of W, Item 4 is deleted and replaced with the following:4. Where the flat roof snow load, P f, exceeds 30 psf, the snow load included in seismic design shall be calculated, in accordance with the following formula: W s = (0.20 + 0.025(A-5))P f is greater than or equal to 0.20 P fWHERE:W s = Weight of snow to be included in seismic calculations;A = Elevation above sea level at the location of the structure (ft/1000)P f = Design roof snow load, psfFor the purposes of this section, snow load shall be assumed uniform on the roof footprint without including the effects of drift or sliding. The Importance Factor, I, used in calculating P f may be considered 1.0 for use in the formula for W s.(49) A new Section 1613.8 is added as follows:1613.8 ASCE 7, Section 13.5.6.2.2 paragraph (e) is modified to read as follows:(e) Penetrations shall have a sleeve or adapter through the ceiling tile to allow for free movement of at least 1 inch (25 mm) in all horizontal directions.Exceptions:1. Where rigid braces are used to limit lateral deflections.2. At fire sprinkler heads in frangible surfaces per NFPA 13.(50) Section 1805.5 is deleted and replaced with the following:1805.5 Foundation walls. Concrete and masonry foundation walls shall be designed in accordance with Chapter 19 or 21, respectively. Foundation walls that are laterally supported at the top and bottom and within the parameters of Tables 1805.5(1) through 1805.5(5) are permitted to be designed and constructed in accordance with Sections 1805.5.1 through 1805.5.5. Concrete foundation walls may also be constructed in accordance with Section 1805.5.8.(51) A new section 1805.5.8 is added as follows:1805.5.8 Empirical foundation design. Group R, Division 3 Occupancies three stories or less in height, and Group U Occupancies, which are constructed in accordance with Section 2308, or with other methods employing repetitive wood-frame construction or repetitive cold-formed steel structural member construction, shall be permitted to have concrete foundations constructed in accordance with Table 1805.5(6).(52) Table 1805.5(6) is added as follows:Table 1805.5(6), entitled "Empirical Foundation Walls, dated January 1, 2007, published by the Department of Commerce, Division of Occupational and Professional Licensing is hereby adopted and incorporated by reference. Table 1805.5(6) identifies foundation requirements for empirical walls.(53) A new section 2306.1.5 is added as follows:2306.1.5 Load duration factors. The allowable stress increase of 1.15 for snow load, shown in Table 2.3.2, Frequently Used Load Duration Factors, C d, of the National Design Specifications, shall not be utilized at elevations above 5,000 feet (1524 M).(54) In Section 2308.6 the following exception is added:Exception: Where foundation plates or sills are bolted or anchored to the foundation with not less than 1/2 inch (12.7 mm) diameter steel bolts or approved anchors, embedded at least 7 inches (178 mm) into concrete or masonry and spaced not more than 32 inches (816 mm) apart, there shall be a minimum of two bolts or anchor straps per piece located not less than 4 inches (102 mm) from each end of each piece. A properly sized nut and washer shall be tightened on each bolt to the plate.(55) Section 2506.2.1 is deleted and replaced with the following:2506.2.1 Other materials. Metal suspension systems for acoustical and lay-in panel ceilings shall conform with ASTM C635 listed in Chapter 35 and Section 13.5.6 of ASCE 7-05, as amended in Section 1613.8, for installation in high seismic areas.(56) In Section 2902.1, the title for Table 2902.1 is deleted and replaced with the following and footnote e is added as follows: Table 2902.1, Minimum Number of Required Plumbing Facilities a, e.FOOTNOTE: e. When provided, in public toilet facilities there shall be an equal number of diaper changing facilities in male toilet rooms and female toilet rooms.(57) Section 3006.5 Shunt Trip, the following exception is added:Exception: Hydraulic elevators and roped hydraulic elevators with a rise of 50 feet or less.(58) A new section 3403.2.4 is added as follows:3403.2.4 Parapet bracing, wall anchors, and other appendages. Buildings constructed prior to 1975 shall have parapet bracing, wall anchors, and appendages such as cornices, spires, towers, tanks, signs, statuary, etc. evaluated by a licensed engineer when said building is undergoing reroofing, or alteration of or repair to said feature. Such parapet bracing, wall anchors, and appendages shall be evaluated in accordance with 75% of the seismic forces as specified in Section 1613. When allowed by the local building official, alternate methods of equivalent strength as referenced in Subsection R156-56-701(2) will be considered when accompanied by engineer sealed drawings, details and calculations. When found to be deficient because of design or deteriorated condition, the engineer's recommendations to anchor, brace, reinforce, or remove the deficient feature shall be implemented.EXCEPTIONS:1. Group R-3 and U occupancies.2. Unreinforced masonry parapets need not be braced according to the above stated provisions provided that the maximum height of an unreinforced masonry parapet above the level of the diaphragm tension anchors or above the parapet braces shall not exceed one and one-half times the thickness of the parapet wall. The parapet height may be a maximum of two and one-half times its thickness in other than Seismic Design Categories D, E, or F.(59) Section 3406.4 is deleted and replaced with the following:3406.4 Change in Occupancy. When a change in occupancy results in a structure being reclassified to a higher Occupancy Category (as defined in Table 1604.5), or when such change of occupancy results in a design occupant load increase of 100% or more, the structure shall conform to the seismic requirements for a new structure.Exceptions:1. Specific seismic detailing requirements of this code or ASCE 7 for a new structure shall not be required to be met where it can be shown that the level of performance and seismic safety is equivalent to that of a new structure. Such analysis shall consider the regularity, overstrength, redundancy and ductility of the structure within the context of the existing and retrofit (if any) detailing providing. Alternatively, the building official may allow the structure to be upgraded in accordance with referenced sections as found in Subsection R156-56-701(2).2. When a change of use results in a structure being reclassified from Occupancy Category I or II to Occupancy Category III and the structure is located in a seismic map area where S DS is less than 0.33, compliance with the seismic requirements of this code and ASCE 7 are not required.3. Where design occupant load increase is less than 25 occupants and the Occupancy Category does not change.(60) The exception in 3409.1 is deleted and replaced with the following:Exception: Type B dwelling or sleeping units required by section 1107 are not required to be provided in existing buildings and facilities, except when an existing occupancy is changed to R-2.(61) In Section 3409.4, number 7 is added as follows:7. When a change of occupancy in a building or portion of a building results in a Group R-2 occupancy as determined in section 1107.6.2, not less than 20 percent of the dwelling or sleeping units shall be Type B dwelling or sleeping units. These dwelling or sleeping units may be located on any floor of the building provided with an accessible route. Two percent, but not less than one, of the dwelling or sleeping units shall be Type A dwelling units.(62) The following referenced standard is added under NFPA in chapter 35:TABLEReferenced in code
Number Title Section number
720-05 Recommended Practice for the 907.2.10, 907.2.10.5
Installation of Household Carbon
Monoxide (CO) Warning EquipmentR156-56-802. Statewide Amendments to the IRC.The following are adopted as amendments to the IRC to be applicable statewide:(1) All statewide amendments to the IBC under Section R156-56-801, the NEC under Section R156-56-806, the IPC under Section R156-56-803, the IMC under Section R156-56-804, the IFGC under Section R156-56-805 and the IECC under Section R156-56-807 which may be applied to detached one and two family dwellings and multiple single family dwellings shall be applicable to the corresponding provisions of the IRC. All references to the ICC Electrical Code are deleted and replaced with the National Electrical Code adopted under Section R156-56-701(1)(b).(2) Section 106.3.2 is deleted and replaced with the following:106.3.2 Previous approval. If a lawful permit has been issued and the construction of which has been pursued in good faith within 180 days after the effective date of the code and has not been abandoned, then the construction may be completed under the code in effect at the time of the issuance of the permit.(3) In Section 109, a new section is added as follows:R109.1.5 Weather-resistive barrier and flashing inspections. An inspection shall be made of the weather-resistive barrier as required by Section R703.1 and flashings as required by Section R703.8 to prevent water from entering the weather-resistant exterior wall envelope.The remaining sections are renumbered as follows:R109.1.6 Other inspectionsR109.1.6.1 Fire-resistance-rated construction inspectionR109.1.6.2 Reinforced masonry, insulating concrete form (ICF) and conventionally formed concrete wall inspectionR109.1.7 Final inspection.(4) Section R114.1 is deleted and replaced with the following:R114.1 Notice to owner. Upon notice from the building official that work on any building or structured is being prosecuted contrary to the provisions of this code or other pertinent laws or ordinances or in an unsafe and dangerous manner, such work shall be immediately stopped. The stop work order shall be in writing and shall be given to the owner of the property involved, or to the owner's agent or to the person doing the work; and shall state the conditions under which work will be permitted to resume.(5) In Section R202, the definition of "Backsiphonage" is deleted and replaced with the following:BACKSIPHONAGE: The backflow of potentially contaminated, polluted or used water into the potable water system as a result of the pressure in the potable water system falling below atmospheric pressure of the plumbing fixtures, pools, tanks or vats connected to the potable water distribution piping.(6) In Section R202 the following definition is added:CERTIFIED BACKFLOW PREVENTER ASSEMBLY TESTER: A person who has shown competence to test Backflow prevention assemblies to the satisfaction of the authority having jurisdiction under Subsection 19-4-104(4), Utah Code Ann. (1953), as amended.(7) In Section R202 the definition of "Cross Connection" is deleted and replaced with the following:CROSS CONNECTION. Any physical connection or potential connection or arrangement between two otherwise separate piping systems, one of which contains potable water and the other either water of unknown or questionable safety or steam, gas or chemical, whereby there exists the possibility for flow from one system to the other, with the direction of flow depending on the pressure differential between the two systems(see "Backflow, Water Distribution").(8) In Section R202 the following definition is added:HEAT exchanger (Potable Water). A device to transfer heat between two physically separated fluids (liquid or steam), one of which is potable water.(9) In Section R202 the definition of "Potable Water" is deleted and replaced with the following:POTABLE WATER. Water free from impurities present in amounts sufficient to cause disease or harmful physiological effects and conforming to the Titles 19-4 and 19-5, Utah Code Ann. (1953), as amended and the regulations of the public health authority having jurisdiction.(10) In Section R202, the following definition is added:S-Trap. A trap having it's weir installed above the inlet of the vent connection.(11) In Section R202 the definition of "Water Heater" is deleted and replaced with the following:WATER HEATER. A closed vessel in which water is heated by the combustion of fuels or electricity and is withdrawn for use externally to the system at pressures not exceeding 160 psig (1100 kPa (gage)), including the apparatus by which heat is generated, and all controls and devices necessary to prevent water temperatures from exceeding 210 degrees Fahrenheit (99 degrees Celsius).(12) Figure R301.2(5) is deleted and replaced with Table R301.2(5a) and Table R301.2(5b) as follows:TABLE NO. R301.2(5a)
STATE OF UTAH - REGIONAL SNOW LOAD FACTORS
COUNTY Po S A o
Beaver 43 63 6.2
Box Elder 43 63 5.2
Cache 50 63 4.5
Carbon 43 63 5.2
Daggett 43 63 6.5
Davis 43 63 4.5
Duchesne 43 63 6.5
Emery 43 63 6.0
Garfield 43 63 6.0
Grand 36 63 6.5
Iron 43 63 5.8
Juab 43 63 5.2
Kane 36 63 5.7
Millard 43 63 5.3
Morgan 57 63 4.5
Piute 43 63 6.2
Rich 57 63 4.1
Salt Lake 43 63 4.5
San Juan 43 63 6.5
Sanpete 43 63 5.2
Sevier 43 63 6.0
Summit 86 63 5.0
Tooele 43 63 4.5
Uintah 43 63 7.0
Utah 43 63 4.5
Wasatch 86 63 5.0
Washington 29 63 6.0
Wayne 36 63 6.5
Weber 43 63 4.5TABLE NO. R301.2(5b)
RECOMMENDED SNOW LOADS FOR SELECTED UTAH CITIES AND TOWNS(2)
Roof Snow Ground Snow
Load (PSF) Load (PSF)
Beaver County
Beaver 5920 ft. 43 62
Box Elder County
Brigham City 4300 ft. 30 43
Tremonton 4290 ft. 30 43
Cache County
Logan 4530 ft. 35 50
Smithfield 4595 ft. 35 50
Carbon County
Price 5550 ft. 30 43
Daggett County
Manila 5377 ft. 30 43
Davis County
Bountiful 4300 ft. 30 43
Farmington 4270 ft. 30 43
Layton 4400 ft. 30 43
Fruit Heights 4500 ft. 40 57
Duchesne County
Duchesne 5510 ft. 30 43
Roosevelt 5104 ft. 30 43
Emery County
Castledale 5660 ft. 30 43
Green River 4070 ft. 25 36
Garfield County
Panguitch 6600 ft. 30 43
Grand County
Moab 3965 ft. 25 36
Iron County
Cedar City 5831 ft. 30 43
Juab County
Nephi 5130 ft. 30 43
Kane County
Kanab 5000 ft. 25 36
Millard County
Millard 5000 ft. 30 43
Delta 4623 ft. 30 43
Morgan County
Morgan 5064 ft. 40 57
Piute County
Piute 5996 ft. 30 43
Rich County
Woodruff 6315 ft. 40 57
Salt Lake County
Murray 4325 ft. 30 43
Salt Lake City 4300 ft. 30 43
Sandy 4500 ft. 30 43
West Jordan 4375 ft. 30 43
West Valley 4250 ft. 30 43
San Juan County
Blanding 6200 ft. 30 43
Monticello 6820 ft. 35 50
Sanpete County
Fairview 6750 ft. 35 50
Mt. Pleasant 5900 ft. 30 43
Manti 5740 ft. 30 43
Ephraim 5540 ft. 30 43
Gunnison 5145 ft. 30 43
Sevier County
Salina 5130 ft. 30 43
Richfield 5270 ft. 30 43
Summit County
Coalville 5600 ft. 60 86
Kamas 6500 ft. 70 100
Park City 6800 ft. 100 142
Park City 8400 ft. 162 231
Summit Park 7200 ft. 90 128
Tooele County
Tooele 5100 ft. 30 43
Uintah County
Vernal 5280 ft. 30 43
Utah County
American Fork 4500 ft. 30 43
Orem 4650 ft. 30 43
Pleasant Grove 5000 ft. 30 43
Provo 5000 ft. 30 43
Spanish Fork 4720 ft. 30 43
Wasatch County
Heber 5630 ft. 60 86
Washington County
Central 5209 ft. 25 36
Dameron 4550 ft. 25 36
Leeds 3460 ft. 20 29
Rockville 3700 ft. 25 36
Santa Clara 2850 ft. 15 (1) 21
St. George 2750 ft. 15 (1) 21
Wayne County
Loa 7080 ft. 30 43
Hanksville 4308 ft. 25 36
Weber County
North Ogden 4500 ft. 40 57
Ogden 4350 ft. 30 43
NOTES
(1) The IRC requires a minimum live load - See R301.6.
(2) This table is informational only in that actual site
elevations may vary. Table is only valid if site elevation
is within 100 feet of the listed elevation.(13) Section R301.6 is deleted and replaced with the following:R301.6 Utah Snow Loads. The ground snow load, P g, to be used in the determination of design snow loads for buildings and other structures shall be determined by using the following formula: P g = (P o 2 + S 2(A-A o) 2) 0.5 for A greater than A o, and P g = P o for A less than or equal to A o.WHEREP g = Ground snow load at a given elevation (psf)P o = Base ground snow load (psf) from Table No. R301.2(5a)S = Change in ground snow load with elevation (psf/100 ft.) From Table No. R301.2(5a)A = Elevation above sea level at the site (ft./1000)A o = Base ground snow elevation from Table R301.2(5a) (ft./1000)The building official may round the roof snow load to the nearest 5 psf. The ground snow load, P g, may be adjusted by the building official when a licensed engineer or architect submits data substantiating the adjustments. A record of such action together with the substantiating data shall be provided to the division for a permanent record.The building official may also directly adopt roof snow loads in accordance with Table R301.2(5b), provided the site is no more than 100 ft. higher than the listed elevation.Where the minimum roof live load in accordance with Table R301.6 is greater than the design roof snow load, such roof live load shall be used for design, however, it shall not be reduced to a load lower than the design roof snow load. Drifting need not be considered for roof snow loads less than 20 psf.(14) Section R304.3 is deleted and replaced with the following:R304.3 Minimum dimensions. Habitable rooms shall not be less than 7 feet (2134 mm) in any horizontal dimension.Exception: Kitchens shall have a clear passageway of not less than 3 feet (914 mm) between counter fronts and appliances or counter fronts and walls.(15) Section R311.5.3 is deleted and replaced with the following:R311.5.3 Stair treads and risers.R311.5.3.1 Riser height. The maximum riser height shall be 8 inches (203 mm). The riser shall be measured vertically between leading edges of the adjacent treads. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm).R311.5.3.2 Tread depth. The minimum tread depth shall be 9 inches (228 mm). The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). Winder treads shall have a minimum tread depth of 10 inches (254 mm) measured as above at a point 12 inches (305 mm) from the side where the treads are narrower. Winder treads shall have a minimum tread depth of 6 inches (152 mm) at any point. Within any flight of stairs, the greatest winder tread depth at the 12 inch (305 mm) walk line shall not exceed the smallest by more than 3/8 inch (9.5 mm).R311.5.3.3 Profile. The radius of curvature at the leading edge of the tread shall be no greater than 9/16 inch (14.3 mm). A nosing not less than 3/4 inch (19 mm) but not more than 1 1/4 inches (32 mm) shall be provided on stairways with solid risers. The greatest nosing projection shall not exceed the smallest nosing projection by more than 3/8 inches (9.5 mm) between two stories, including the nosing at the level of floors and landings. Beveling of nosing shall not exceed 1/2 inch (12.7 mm). Risers shall be vertical or sloped from the underside of the leading edge of the tread above at an angle not more than 30 degrees (0.51 rad) from the vertical. Open risers are permitted, provided that the opening between treads does not permit the passage of a 4-inch diameter (102 mm) sphere.Exceptions.1. A nosing is not required where the tread depth is a minimum of 10 inches (254 mm).2. The opening between adjacent treads is not limited on stairs with a total rise of 30 inches (762 mm) or less.(16) Section R313 is deleted and replaced with the following:Section R313 SMOKE AND CARBON MONOXIDE ALARMSR313.1 Single- and multiple-station smoke alarms. Single- and multiple-station smoke alarms shall be installed in the following locations:1. In each sleeping room.2. Outside of each separate sleeping area in the immediate vicinity of the bedrooms.3. On each additional story of the dwelling, including basements and cellars but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.All smoke alarms shall be listed and installed in accordance with the provisions of this code and the household fire warning equipment provision of NFPA 72.R313.2 Carbon monoxide alarms. In new residential structures regulated by this code that are equipped with fuel burning appliances, carbon monoxide alarms shall be installed on each habitable level. All carbon monoxide detectors shall be listed and comply with U.L. 2034 and shall be installed in accordance with provisions of this code and NFPA 720.R313.3 Interconnection of alarms. When multiple alarms are required to be installed within an individual dwelling unit, the alarm devices shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed. Approved combination smoke- and carbon-monoxide detectors shall be permitted.R313.4 Power source. In new construction, the required alarms shall receive their primary power from the building wiring when such wiring is served from a commercial source, and when primary power is interrupted, shall receive power from a battery. Wiring shall be permanent and without a disconnecting switch other than those required for overcurrent protection. Alarms shall be permitted to be battery operated when installed in buildings without commercial power or in buildings that undergo alterations, repairs, or additions regulated by Section R313.5R313.5 Alterations, repairs and additions. When interior alterations, repairs or additions requiring a permit occur, or when one or more sleeping rooms are added or created in existing dwellings, the individual dwelling unit shall be provided with alarms located as required for new dwellings; the alarms shall be interconnected and hard wired.Exceptions:1. Alarms in existing areas shall not be required to be interconnected and hard wired where the alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space, or basement available which could provide access for hard wiring and interconnection without the removal of interior finishes.2. Repairs to the exterior surfaces of dwellings are exempt from the requirements of this section.(17) In Section R403.1.6 exception 4 is added as follows:4. When anchor bolt spacing does not exceed 32 inches (813 mm) apart, anchor bolts may be placed with a minimum of two bolts per plate section located not less than 4 inches (102 mm) from each end of each plate section at interior bearing walls, interior braced wall lines and at all exterior walls.(18) In Section R403.1.6.1 the following exception is added at the end of Item 2 and Item 3:Exception: When anchor bolt spacing does not exceed 32 inches (816 mm) apart, anchor bolts may be placed with a minimum of two bolts per plate section located not less than 4 inches (102 mm) from each end of each plate section at interior bearing walls, interior braced wall lines and at all exterior walls.(19) New Sections R404.0, R404.0.1 and R404.0.2 are added before Section 404.1 as follows:R404.0 This section may be used as an alternative to complying with Sections R404.1 through R404.1.5.1.R404.0.1 Concrete and masonry foundation walls. Concrete and masonry foundation walls may be designed in accordance with IBC Chapters 19 or 21 respectively. Foundation walls that are laterally supported at the top and bottom within the parameters of IBC Tables 1805.5(1) through 1805.5(5) are permitted to be designed and constructed in accordance with IBC Sections 1805.5.1 through 1805.5.5. Concrete foundation walls may also be constructed in accordance with Section R404.0.2.R404.0.2 Empirical foundation design. Buildings constructed with repetitive wood frame construction or repetitive cold-formed steel structural member construction may be permitted to have concrete foundations constructed in accordance with IBC Table 1805.5(6). IBC Table 1805.5(6) entitled "Empirical Foundations Walls", dated January 1, 2007, published by the Department of Commerce, Division of Occupational and Professional Licensing, is hereby adopted and incorporated by reference. Table 1805.5(6) identifies foundation requirements for empirical walls.(20) Section R703.6 is deleted and replaced with the following:R703.6 Exterior plaster.R703.6.1 Lath. All lath and lath attachments shall be of corrosion-resistant materials. Expanded metal or woven wire lath shall be attached with 1 1/2 inch-long (38 mm), 11 gage nails having 7/16 inch (11.1 mm) head, or 7/8-inch-long (22.2 mm), 16 gage staples, spaced at no more than 6 inches (152 mm), or as otherwise approved.R703.6.2 Weather-resistant barriers. Weather-resistant barriers shall be installed as required in Section R703.2 and, where applied over wood-based sheathing, shall include a weather-resistive vapor permeable barrier with a performance at least equivalent to two layers of Grade D paper.R703.6.3 Plaster. Plastering with portland cement plaster shall be not less than three coats when applied over metal lath or wire lath and shall be not less than two coats when applied over masonry, concrete or gypsum backing. If the plaster surface is completely covered by veneer or other facing material or is completely concealed, plaster application need be only two coats, provided the total thickness is as set forth in Table R702.1(1). On wood-frame construction with an on-grade floor slab system, exterior plaster shall be applied in such a manner as to cover, but not extend below, lath, paper and screed.The proportion of aggregate to cementitious materials shall be as set forth in Table R702.1(3).R703.6.3.1 Weep screeds. A minimum 0.019-inch (0.5 mm) (No. 26 galvanized sheet gage), corrosion-resistant weep screed or plastic weep screed, with a minimum vertical attachment flange of 3 1/2 inches (89 mm) shall be provided at or below the foundation plate line on exterior stud walls in accordance with ASTM C 926. The weep screed shall be placed a minimum of 4 inches (102 mm) above the earth or 2 inches (51 mm) above paved areas and shall be of a type that will allow trapped water to drain to the exterior of the building. The weather-resistant barrier shall lap the attachment flange. The exterior lath shall cover and terminate on the attachment flange of the weep screed.(21) In Section R703.8, number 8 is added as follows:8. At the intersection of foundation to stucco, masonry, siding, or brick veneer with an approved corrosive-resistance flashing with a 1/2" drip leg extending past exterior side of the foundation.(22) A new Section G2401.2 is added as follows:G2401.2 Meter Protection. Fuel gas services shall be in an approved location and/or provided with structures designed to protect the fuel gas meter and surrounding piping from physical damage, including falling, moving, or migrating ice and snow. If an added structure is used, it must provide access for service and comply with the IBC or the IRC.(23) Section P2602.3 is added as follows:P2602.3 Individual water supply. Where a potable public water supply is not available, individual sources of potable water supply shall be utilized provided that the source has been developed in accordance with Sections 73-3-1 and 73-3-25, Utah Code Ann. (1953), as amended, as administered by the Department of Natural Resources, Division of Water Rights. In addition, the quality of the water shall be approved by the local health department having jurisdiction.(24) Section P2602.4 is added as follows:P2602.4 Sewer required. Every building in which plumbing fixtures are installed and all premises having drainage piping shall be connected to a public sewer where the sewer is within 300 feet of the property line in accordance with Section 10-8-38, Utah Code Ann, (1953), as amended; or an approved private sewage disposal system in accordance with Rule R317, Chapter 4, Utah Administrative Code, as administered by the Department of Environmental Quality, Division of Water Quality.(25) Section P2603.2.1 is deleted and replaced with the following:P2603.2.1 Protection against physical damage. In concealed locations where piping, other than cast-iron or galvanized steel, is installed through holes or notches in studs, joists, rafters, or similar members less than 1 1/2 inch (38 mm) from the nearest edge of the member, the pipe shall be protected by shield plates. Protective shield plates shall be a minimum of 1/16 inch-thick (1.6 mm) steel, shall cover the area of the pipe where the member is notched or bored, and shall be at least the thickness of the framing member penetrated.(26) In Section P2801.7 the word townhouses is deleted.(27) Section P2902.1.1 is added as follows:P2902.1.1 Backflow assembly testing. The premise owner or his designee shall have backflow prevention assemblies operation tested at the time of installation, repair and relocation and at least on an annual basis thereafter, or more frequently as required by the authority having jurisdiction. Testing shall be performed by a Certified Backflow Preventer Assembly Tester. The assemblies that are subject to this paragraph are the Spill Resistant Vacuum Breaker, the Pressure Vacuum Breaker Assembly, the Double Check Backflow Prevention Assembly, the Double Check Detector Assembly Backflow Preventer, the Reduced Pressure Principle Backflow Preventer, and Reduced Pressure Detector Assembly.(28) Table P2902.3 is deleted and replaced with the following:TABLE P2902.3
General Methods of Protection
Assembly Degree Application Installation Criteria
(applicable of
standard) Hazard
Air Gap High or Backsiphonage See Table P2902.3.1
(ASME A112.1.2) Low
Reduced High or Backpressure or a. The bottom of each
Pressure Low Backsiphonage RP assembly shall
Principle Backflow 1/2" - 16" be a minimum of 12
Preventer (AWWA inches above the
C511, USC-FCCCHR, ground or floor.
ASSE 1013 b. RP assemblies shall
CSA CNA/CSA-B64.4) NOT be installed in
and Reduced Pressure a pit.
Detector Assembly c. The relief valve on
(ASSE 1047, USC- each RP assembly
FCCCHR) shall not be
directly connected
to any waste
disposal line,
including sanitary
sewer, storm drains,
or vents.
d. The assembly shall
be installed in a
horizontal position
only unless listed
or approved for
vertical
installation.
Double Check Low Backpressure or a. If installed in a
Backflow Backsiphonage pit, the DC assembly
Prevention 1/2" - 16" shall be installed
Assembly with a minimum of
(AWWA C510, 12 inches of
USC-FCCCHR, clearance between
ASSE 1015) all sides of the
Double Check vault including
Detector Assembly the floor and roof
Backflow Preventer or ceiling with
(ASSE 1048, adequate room for
USC-FCCCHR) testing and
maintenance.
b. Shall be installed
in a horizontal
position unless
listed or approved
for vertical
installation.
Pressure High or Backsiphonage a. Shall not be
Vacuum Low 1/2" - 2" installed in an
Breaker area that could be
Assembly subjected to
(ASSE 1020, backpressure or
USC-FCCCHR) back drainage
conditions.
b. Shall be installed
a minimum of 12
inches above all
downstream piping
and the highest
point of use.
c. Shall not be
installed below
ground or in a
vault or pit.
d. Shall be installed
in a vertical
position only.
Spill High or Backsiphonage a. Shall not be
Resistant Low 1/4" - 2" installed in an
Vacuum area that could
Breaker be subjected to
(ASSE 1056, backpressure or
USC-FCCCHR) back drainage
conditions.
b. Shall be installed
a minimum of 12
inches above all
downstream piping
and the highest
point of use.
c. Shall not be
installed below
ground or in a
vault or pit.
d. Shall be installed
in a vertical
position only.
Atmospheric High or Backsiphonage a. Shall not be
Vacuum Low installed in an
Breaker area that could be
(ASSE 1001 subjected to
USC-FCCCHR, backpressure or back
CSA CAN/CSA-B64.1.1 drainage conditions.
b. Shall not be
installed where it
may be subjected to
continuous pressure
for more than 12
consecutive hours
at any time.
c. Shall be installed
a minimum of six
inches above all
downstream piping
and the highest
point of use.
d. Shall be installed
on the discharge
(downstream) side
of any valves.
e. The AVB shall be
installed in a
vertical position
only.
General The assembly owner,
Installation when necessary,
Criteria shall provide
devices or
structures to
facilitate testing,
repair, and/or
maintenance and to
insure the safety
of the backflow
technician.
Assemblies shall
not be installed
more than five feet
off the floor unless
a permanent platform
is installed.
The body of the
assembly shall not
be closer than 12
inches to any wall,
ceiling or
incumbrance, and
shall be accessible
for testing, repair
and/or maintenance.
In cold climates,
assemblies shall be
protected from
freezing by a means
acceptable to the
code official.
Assemblies shall
be maintained as
an intact assembly.(29) Table 2902.3a is added as follows:TABLE 2902.3a
Specialty Backflow Devices for low hazard use only
Device Degree of Application Applicable
Hazard Standard
Antisiphon-type Low Backsiphonage ASSE 1002
Water Closet Flush CSA CAN/
Tank Ball Cock CSA-B125
Dual check valve Low Backsiphonage ASSE 1024
Backflow Preventer or Backpressure
1/4" - 1"
Backflow Preventer Low Backsiphonage ASSE 1012
with Intermediate Residential or Backpressure CSA CAN/
Atmospheric Vent Boiler 1/4" - 3/4" CSA-B64.3
Dual check valve Low Backsiphonage ASSE 1022
type Backflow or Backpressure
Preventer for 1/4" - 3/8"
Carbonated Beverage
Dispensers/Post
Mix Type
Hose-connection Low Backsiphonage ASSE 1011
Vacuum Breaker 1/2", 3/4", 1" CSA CAN/
CSA-B64.2
Vacuum Breaker Low Backsiphonage ASSE 1019
Wall Hydrants, 3/4", 1" CSA CAN/
Frost-resistant, CSA-B64.2.2
Automatic Draining
Type
Laboratory Faucet Low Backsiphonage ASSE 1035
Backflow Preventer CSA CAN/
CSA-B64.7
Hose Connection Low Backsiphonage ASSE 1052
Backflow Preventer 1/2" - 1"
Installation Guidelines: The above specialty devices shall be
installed in accordance with their listing and the manufacturer's
instructions and the specific provisions of this chapter.(30) Section P3003.2.1 is added as follows:Section P3003.2.1 Improper Connections. No drain, waste, or vent piping shall be drilled and tapped for the purpose of making connections.(31) In Section P3103.6, the following sentence is added at the end of the paragraph:Vents extending through the wall shall terminate not less than 12 inches from the wall with an elbow pointing downward.(32) In Section P3104.4, the following sentence is added at the end of the paragraph:Horizontal dry vents below the flood level rim shall be permitted for floor drain and floor sink installations when installed below grade in accordance with Chapter 30, and Sections P3104.2 and P3104.3. A wall cleanout shall be provided in the vertical vent.(33) Chapter 43, Referenced Standards, is amended as follows:The following reference standard is added:TABLE
USC- Foundation for Cross-Connection Table P2902.3
FCCCHR Control and Hydraulic Research
9th University of Southern California
Edition Kaprielian Hall 300
Manual Los Angeles CA 90089-2531
of Cross
Connection
Control(34) In Chapter 43, the following standard is added under NFPA as follows:TABLE
720-05 Recommended Practice for the Installation R313.2
of Household Carbon Monoxide (CO) Warning
EquipmentR156-56-803. Statewide Amendments to the IPC.The following are adopted as amendments to the IPC to be applicable statewide:(1) In Section 202, the definition for "Backflow Backpressure, Low Head" is deleted in its entirety.(2) In Section 202, the definition for "Backsiphonage" is deleted and replaced with the following:Backsiphonage. The backflow of potentially contaminated, polluted or used water into the potable water system as a result of the pressure in the potable water system falling below atmospheric pressure of the plumbing fixtures, pools, tanks or vats connected to the potable water distribution piping.(3) In Section 202, the following definition is added:Certified Backflow Preventer Assembly Tester. A person who has shown competence to test Backflow prevention assemblies to the satisfaction of the authority having jurisdiction under Subsection 19-4-104(4), Utah Code Ann. (1953), as amended.(4) In Section 202, the definition for "Cross Connection" is deleted and replaced with the following:Cross Connection. Any physical connection or potential connection or arrangement between two otherwise separate piping systems, one of which contains potable water and the other either water of unknown or questionable safety or steam, gas or chemical, whereby there exists the possibility for flow from one system to the other, with the direction of flow depending on the pressure differential between the two systems (see "Backflow").(5) In Section 202, the following definition is added:Heat Exchanger (Potable Water). A device to transfer heat between two physically separated fluids (liquid or steam), one of which is potable water.(6) In Section 202, the definition for "Potable Water" is deleted and replaced with the following:Potable Water. Water free from impurities present in amounts sufficient to cause disease or harmful physiological effects and conforming to the Titles 19-4 and 19-5, Utah Code Ann. (1953), as amended and the regulations of the public health authority having jurisdiction.(7) In Section 202, the following definition is added:S-Trap. A trap having its weir installed above the inlet of the vent connection.(8) In Section 202, the definition for "Water Heater" is deleted and replaced with the following:Water Heater. A closed vessel in which water is heated by the combustion of fuels or electricity and is withdrawn for use external to the system at pressures not exceeding 160 psig (1100 kPa (gage)), including the apparatus by which heat is generated, and all controls and devices necessary to prevent water temperatures from exceeding 210 degrees Fahrenheit (99 degrees Celsius).(9) Section 304.3 Meter Boxes is deleted.(10) Section 305.5 is deleted and replaced with the following:305.5 Pipes through or under footings or foundation walls. Any pipe that passes under or through a footing or through a foundation wall shall be protected against structural settlement.(11) Section 305.8 is deleted and replaced with the following:305.8 Protection against physical damage. In concealed locations where piping, other than cast-iron or galvanized steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1/2 inches (38 mm) from the nearest edge of the member, the pipe shall be protected by shield plates. Protective shield plates shall be minimum of 1/16 inch-thick (1.6 mm) steel, shall cover the area of the pipe where the member is notched or bored, and shall be at least the thickness of the framing member penetrated.(12) Section 305.10 is added as follows:Section 305.10 Improper Connections. No drain, waste, or vent piping shall be drilled and tapped for the purpose of making connections.(13) Section 311.1 is deleted.(14) Section 312.9 is deleted in its entirety and replaced with the following:312.9 Backflow assembly testing. The premise owner or his designee shall have backflow prevention assemblies operation tested at the time of installation, repair and relocation and at least on an annual basis thereafter, or more frequently as required by the authority having jurisdiction. Testing shall be performed by a Certified Backflow Preventer Assembly Tester. The assemblies that are subject to this paragraph are the Spill Resistant Vacuum Breaker, the Pressure Vacuum Breaker Assembly, the Double Check Backflow Prevention Assembly, the Double Check Detector Assembly Backflow Preventer, the Reduced Pressure Principle Backflow Preventer, and Reduced Pressure Detector Assembly.(15) In Section 403.1 footnote e is added as follows:FOOTNOTE: e. When provided, in public toilet facilities there shall be an equal number of diaper changing facilities in male toilet rooms and female toilet rooms.(16) In Section 406.3, an exception is added as follows:Exception: Gravity discharge clothes washers, when properly trapped and vented, shall be allowed to be directly connected to the drainage system or indirectly discharge into a properly sized catch basin, trench drain, or other approved indirect waste receptor installed for the purpose of receiving such waste.(17) A new section 406.4 is added as follows:406.4 Automatic clothes washer metal safe pans. Metal safe pans, when installed under automatic clothes washers, shall only be allowed to receive the unintended discharge from a leaking appliance, valve, supply hose, or overflowing waste water from the clothes washer standpipe. Clothes washer metal safe pans shall not be used as indirect waste receptors to receive the discharge of waste water from any other equipment, appliance, appurtenance, drain pipe, etc. Each safe pan shall be provided with an approved trap seal primer, conforming to ASSE 1018 or 1044 or a deep seal trap. The sides of the safe pan shall be no less than 1 1/2" high and shall be soldered at the joints to provide a water tight seal.406.4.1 Safe pan outlet. The safe pan outlet shall be no less than 1 1/2" in diameter and shall be located in a visible and accessible location to facilitate cleaning and maintenance. The outlet shall be flush with the surface of the pan so as not to allow water retention within the pan.(18) Section 412.1 is deleted and replaced with the following:412.1 Approval. Floor drains shall be made of ABS, PVC, cast-iron, stainless steel, brass, or other approved materials that are listed for the use.(19) Section 412.5 is added as follows:412.5 Public toilet rooms. All public toilet rooms shall be equipped with at least one floor drain.(20) Section 418.1 is deleted and replaced with the following:418.1 Approval. Sinks shall conform to ANSI Z124.6, ASME A112.19.1M, ASME A112.19.2M, ASME A112.19.3M, ASME A112.19.4M, ASME A112.19.9M, CSA B45.1, CSA B45.2, CSA B45.3, CSA B45.4 or NSF 2.(21) Section 504.6.2 is deleted and replaced with the following:504.6.2 Material. Relief valve discharge piping shall be of those materials listed in Tables 605.4 and 605.5 and meet the requirements for Sections 605.4 and 605.5 or shall be tested, rated and approved for such use in accordance with ASME A112.4.1. Piping from safety pan drains shall meet the requirements of Section 804.1 and be constructed of those materials listed in Section 702.(22) Section 504.7.2 is deleted and replaced with the following:504.7.2 Pan drain termination. The pan drain shall extend full-size and terminate over a suitably located indirect waste receptor, floor drain or extend to the exterior of the building and terminate not less than 6 inches (152 mm) and not more than 24 inches (610 mm) above the adjacent ground surface. When permitted by the administrative authority, the pan drain may be directly connected to a soil stack, waste stack, or branch drain. The pan drain shall be individually trapped and vented as required in Section 907.1. The pan drain shall not be directly or indirectly connected to any vent. The trap shall be provided with a trap primer conforming to ASSE 1018 or ASSE 1044.(23) A new section 504.7.3 is added as follows:504.7.3 Pan Designation. A water heater pan shall be considered an emergency receptor designated to receive the discharge of water from the water heater only and shall not receive the discharge from any other fixtures, devises or equipment.(24) Section 602.3 is deleted and replaced with the following:602.3 Individual water supply. Where a potable public water supply is not available, individual sources of potable water supply shall be utilized provided that the source has been developed in accordance with Sections 73-3-1, 73-3-3, and 73-3-25, Utah Code Ann. (1953), as amended, as administered by the Department of Natural Resources, Division of Water Rights. In addition, the quality of the water shall be approved by the local health department having jurisdiction. The source shall supply sufficient quantity of water to comply with the requirements of this chapter.(25) Sections 602.3.1, 602.3.2, 602.3.3, 602.3.4, 602.3.5 and 602.3.5.1 are deleted in their entirety.(26) Section 604.4.1 is added as follows:604.4.1 Metering faucets. Self closing or metering faucets shall provide a flow of water for at least 15 seconds without the need to reactivate the faucet.(27) Section 606.5 is deleted and replaced with the following:606.5 Water pressure booster systems. Water pressure booster systems shall be provided as required by Section 606.5.1 through 606.5.11.(28) Section 606.5.11 is added as follows:606.5.11 Prohibited installation. In no case shall a booster pump be allowed that will lower the pressure in the public main to less than 20 psi.(29) In Section 608.1, the following sentence is added at the end of the paragraph:Connection without an air gap between potable water piping and sewer-connected waste shall not exist under any condition.(30) Table 608.1 is deleted and replaced with the following:TABLE 608.1
General Methods of Protection
Assembly Degree Application Installation Criteria
(applicable of
standard) Hazard
Air Gap High or Backsiphonage See Table 608.15.1
(ASME A112.1.2) Low
Reduced High or Backpressure or a. The bottom of each
Pressure Low Backsiphonage RP assembly shall
Principle Backflow 1/2" - 16" be a minimum of 12
Preventer (AWWA inches above the
C511, USC-FCCCHR, ground or floor.
ASSE 1013 b. RP assemblies shall
CSA CNA/CSA-B64.4) NOT be installed in
and Reduced Pressure a pit.
Detector Assembly c. The relief valve on
(ASSE 1047, USC- each RP assembly
FCCCHR) shall not be
directly connected
to any waste
disposal line,
including sanitary
sewer, storm drains,
or vents.
d. The assembly shall
be installed in a
horizontal position
only unless listed
or approved for
vertical
installation.
Double Check Low Backpressure or a. If installed in a
Backflow Backsiphonage pit, the DC assembly
Prevention 1/2" - 16" shall be installed
Assembly with a minimum of
(AWWA C510, 12 inches of
USC-FCCCHR, clearance between
ASSE 1015) all sides of the
Double Check vault including
Detector Assembly the floor and roof
Backflow Preventer or ceiling with
(ASSE 1048, adequate room for
USC-FCCCHR) testing and
maintenance.
b. Shall be installed
in a horizontal
position unless
listed or approved
for vertical
installation.
Pressure High or Backsiphonage a. Shall not be
Vacuum Low 1/2" - 2" installed in an
Breaker area that could be
Assembly subjected to
(ASSE 1020, backpressure or
USC-FCCCHR) back drainage
conditions.
b. Shall be installed
a minimum of 12
inches above all
downstream piping
and the highest
point of use.
c. Shall not be
installed below
ground or in a
vault or pit.
d. Shall be installed
in a vertical
position only.
Spill High or Backsiphonage a. Shall not be
Resistant Low 1/4" - 2" installed in an
Vacuum area that could
Breaker be subjected to
(ASSE 1056, backpressure or
USC-FCCCHR) back drainage
conditions.
b. Shall be installed
a minimum of 12
inches above all
downstream piping
and the highest
point of use.
c. Shall not be
installed below
ground or in a
vault or pit.
d. Shall be installed
in a vertical
position only.
Atmospheric High or Backsiphonage a. Shall not be
Vacuum Low installed in an
Breaker area that could be
(ASSE 1001 subjected to
USC-FCCCHR, backpressure or back
CSA CAN/CSA-B64.1.1 drainage conditions.
b. Shall not be
installed where it
may be subjected to
continuous pressure
for more than 12
consecutive hours
at any time.
c. Shall be installed
a minimum of six
inches above all
downstream piping
and the highest
point of use.
d. Shall be installed
on the discharge
(downstream) side
of any valves.
e. The AVB shall be
installed in a
vertical position
only.
General The assembly owner,
Installation when necessary,
Criteria shall provide
devices or
structures to
facilitate testing,
repair, and/or
maintenance and to
insure the safety
of the backflow
technician.
Assemblies shall
not be installed
more than five feet
off the floor unless
a permanent platform
is installed.
The body of the
assembly shall not
be closer than 12
inches to any wall,
ceiling or
incumbrance, and
shall be accessible
for testing, repair
and/or maintenance.
In cold climates,
assemblies shall be
protected from
freezing by a means
acceptable to the
code official.
Assemblies shall
be maintained as
an intact assembly.(31) Table 608.1.1 is added as follows:TABLE 608.1.1Specialty Backflow Devices for low hazard use only
Device Degree of Application Applicable
Hazard Standard
Antisiphon-type Low Backsiphonage ASSE 1002
Water Closet Flush CSA CAN/
Tank Ball Cock CSA-B125
Dual check valve Low Backsiphonage ASSE 1024
Backflow Preventer or Backpressure
1/4" - 1"
Backflow Preventer Low Backsiphonage ASSE 1012
with Intermediate Residential or Backpressure CSA CAN/
Atmospheric Vent Boiler 1/4" - 3/4" CSA-B64.3
Dual check valve Low Backsiphonage ASSE 1022
type Backflow or Backpressure
Preventer for 1/4" - 3/8"
Carbonated Beverage
Dispensers/Post
Mix Type
Hose-connection Low Backsiphonage ASSE 1011
Vacuum Breaker 1/2", 3/4", 1" CSA CAN/
CSA-B64.2
Vacuum Breaker Low Backsiphonage ASSE 1019
Wall Hydrants, 3/4", 1" CSA CAN/
Frost-resistant, CSA-B64.2.2
Automatic Draining
Type
Laboratory Faucet Low Backsiphonage ASSE 1035
Backflow Preventer CSA CAN/
CSA-B64.7
Hose Connection Low Backsiphonage ASSE 1052
Backflow Preventer 1/2" - 1"
Installation Guidelines: The above specialty devices shall be
installed in accordance with their listing and the manufacturer's
instructions and the specific provisions of this chapter.(32) In Section 608.3.1, the following sentence is added at the end of the paragraph:All piping and hoses shall be installed below the atmospheric vacuum breaker.(33) Section 608.7 is deleted in its entirety.(34) In Section 608.8, the following sentence is added at the end of the paragraph:In addition each nonpotable water outlet shall be labeled with the words "CAUTION: UNSAFE WATER, DO NOT DRINK".(35) In Section 608.11, the following sentence is added at the end of the paragraph:The coating shall conform to NSF Standard 61 and application of the coating shall comply with the manufacturers instructions.(36) Section 608.13.3 is deleted and replaced with the following:608.13.3 Backflow preventer with intermediate atmospheric vent. Backflow preventers with intermediate atmospheric vents shall conform to ASSE 1012 or CAS CAN/CAS-B64.3. These devices shall be permitted to be installed on residential boilers only where subject to continuous pressure conditions. The relief opening shall discharge by air gap and shall be prevented from being submerged.(37) Section 608.13.4 is deleted in its entirety.(38) Section 608.13.9 is deleted in its entirety.(39) Section 608.15.3 is deleted and replaced with the following:608.15.3 Protection by a backflow preventer with intermediate atmospheric vent. Opening and outlets to residential boilers only shall be protected by a backflow preventer with an intermediate atmospheric vent.(40) Section 608.15.4 is deleted and replaced with the following:608.15.4 Protection by a vacuum breaker. Openings and outlets shall be protected by atmospheric-type or pressure-type vacuum breakers. The critical level of the atmospheric vacuum breaker shall be set a minimum of 6 inches (152 mm) above the flood level rim of the fixture or device. The critical level of the pressure vacuum breaker shall be set a minimum of 12 inches (304 mm) above the flood level rim of the fixture or device. Ball cocks shall be set in accordance with Section 425.3.1. Vacuum breakers shall not be installed under exhaust hoods or similar locations that will contain toxic fumes or vapors. Pipe-applied vacuum breakers shall be installed not less than 6 inches (152 mm) above the flood level rim of the fixture, receptor or device served. No valves shall be installed downstream of the atmospheric vacuum breaker.(41) Section 608.15.4.2 is deleted and replaced with the following:608.15.4.2 Hose connections. Sillcocks, hose bibbs, wall hydrants and other openings with a hose connection shall be protected by an atmospheric-type or pressure-type vacuum breaker or a permanently attached hose connection vacuum breaker. Add-on-type backflow prevention devices shall be non-removable. In climates where freezing temperatures occur, a listed self-draining frost proof hose bibb with an integral backflow preventer shall be used.(42) In Section 608.16.2, the first sentence of the paragraph is deleted and replaced as follows:608.16.2 Connections to boilers. The potable water supply to the residential boiler shall be equipped with a backflow preventer with an intermediate atmospheric vent complying with ASSE 1012 or CSA CAN/CSA B64.3.(43) Section 608.16.3 is deleted and replaced with the following:608.16.3 Heat exchangers. Heat exchangers shall be separated from potable water by double-wall construction. An air gap open to the atmosphere shall be provided between the two walls.Exceptions:1. Single wall heat exchangers shall be permitted when all of the following conditions are met:a. It utilizes a heat transfer medium of potable water or contains only substances which are recognized as safe by the United States Food and Drug Administration (FDA);b. The pressure of the heat transfer medium is maintained less than the normal minimum operating pressure of the potable water system; andc. The equipment is permanently labeled to indicate only additives recognized as safe by the FDA shall be used.2. Steam systems that comply with paragraph 1 above.3. Approved listed electrical drinking water coolers.(44) In Section 608.16.4.1, add the following exception:Exception: All class 1 and 2 systems containing chemical additives consisting of strictly glycerine (C.P. or U.S.P. 96.5 percent grade) or propylene glycol shall be protected against backflow with a double check valve assembly. Such systems shall include written certification of the chemical additives at the time of original installation and service or maintenance.(45) Section 608.16.7 is deleted and replaced with the following:608.16.7 Chemical dispensers. Where chemical dispensers connect to the water distribution system, the water supply system shall be protected against backflow in accordance with Section 608.13.1, Section 608.13.2, Section 608.13.5, Section 608.13.6 or Section 608.13.8.(46) Section 608.16.8 is deleted and replaced with the following:608.16.8 Portable cleaning equipment. Where the portable cleaning equipment connects to the water distribution system, the water supply system shall be protected against backflow in accordance with Section 608.13.1, Section 608.13.2 or Section 608.13.8.(47) Section 608.16.9 is deleted and replaced with the following:608.16.9 Dental pump equipment or water syringe. Where dental pumping equipment or water syringes connects to the water distribution system, the water supply system shall be protected against backflow in accordance with Section 608.13.1, Section 608.13.2, Section 608.13.5, Section 608.13.6 or Section 608.13.8.(48) Section 608.16.11 is added as follows:608.16.11 Automatic and coin operated car washes. The water supply to an automatic or coin operated car wash shall be protected in accordance with Section 608.13.1 or Section 608.13.2.(49) Section 608.17 is deleted in its entirety.(50) Section 701.2 is deleted and replaced with the following:701.2 Sewer required. Every building in which plumbing fixtures are installed and all premises having drainage piping shall be connected to a public sewer where the sewer is within 300 feet of the property line in accordance with Section 10-8-38, Utah Code Ann., (1953), as amended; or an approved private sewage disposal system in accordance with Rule R317-4, Utah Administrative Code, as administered by the Department of Environmental Quality, Division of Water Quality.(51) Section 802.3.2 is deleted in its entirety and replaced with the following:802.3.2 Open hub waste receptors. Waste receptors for clear water waste shall be permitted in the form of a hub or pipe extending not more than 1/2 inch above a water impervious floor and are not required to have a strainer.(52) Section 901.3 is deleted and replaced with the following:901.3 Chemical waste vent system. The vent system for a chemical waste system shall be independent of the sanitary vent system and shall terminate separately through the roof to the open air or to an air admittance valve provided at least one chemical waste vent in the system terminates separately through the roof to the open air.(53) Section 904.1 is deleted and replaced with the following:904.1 Roof extensions. All open vent pipes that extend through a roof shall be terminated at least 12 inches (304.8 mm) above the roof, except that where a roof is to be used for any purpose other than weather protection, the vent extension shall be run at least 7 feet (2134 mm) above the roof.(54) In Section 904.6, the following sentence is added at the end of the paragraph:Vents extending through the wall shall terminate not less than 12 inches from the wall with an elbow pointing downward.(55) In Section 905.4, the following sentence is added at the end of the paragraph:Horizontal dry vents below the flood level rim shall be permitted for floor drain and floor sink installations when installed in accordance with Sections 702.2, 905.2 and 905.3 and provided with a wall clean out.(56) In Section 917.8 the following exception is added:Exception: Air admittance valves shall be permitted in non-neutralized special waste systems provided that they conform to the requirements in Sections 901.3 and 702.5, are tested to ASTM F1412, and are certified by ANSI/ASSE.(57) Section 1104.2 is deleted and replaced with the following:1104.2 Combining storm and sanitary drainage prohibited. The combining of sanitary and storm drainage systems is prohibited.(58) Section 1108 is deleted in its entirety.(59) The Referenced Standard NFPA 99c-02 in Chapter 13 is deleted and replaced with NFPA 99c-05.(60) The Referenced Standard NSF-2003e in Chapter 13 is amended to add Section 608.11 to the list of Referenced in code section number.(61) In Chapter 13, Referenced Standards, the following referenced standard is added:TABLE
USC- Foundation for Cross-Connection Table 608.1
FCCCHR Control and Hydraulic Research
9th University of Southern California
Edition Kaprielian Hall 300
Manual Los Angeles CA 90089-2531
of Cross
Connection
Control(62) Appendix C of the IPC, Gray Water Recycling Systems as amended herein shall not be adopted by any local jurisdiction until such jurisdiction has requested Appendix C as amended to be adopted as a local amendment and such local amendment has been approved as a local amendment under these rules.(63) In jurisdictions which have adopted Appendix C as amended as a local amendment as provided herein, Section 301.3 of the IPC is deleted and replaced with the following:301.3 Connection to the drainage system. All plumbing fixtures, drains, appurtenances and appliances used to receive or discharge liquid wastes or sewage shall be directly connected to the drainage system of the building or premises, in accordance with the requirements of this Code. This section shall not be construed to prevent indirect waste systems provided for in Chapter 8.Exception: Bathtubs, showers, lavatories, clothes washers and laundry sinks shall not be required to discharge to the sanitary drainage system where such fixtures discharge to a gray water recycling system meeting all the requirements as specified in Appendix C as amended by these rules.(64) Appendix C is deleted and replaced with the following, to be effective only in jurisdictions which have adopted Appendix C as amended as a local amendment under these rules:Appendix C, Gray Water Recycling Systems, C101 Gray Water Recycling SystemsC101.1 General, recycling gray water within a building. In R1, R2 and R4 occupancies and one- and two-family dwellings, gray water recycling systems are prohibited.In commercial occupancies, recycled gray water shall only be utilized for the flushing of water closets and urinals that are located in the same building as the gray water recycling system, provided the following conditions are met:1. Such systems comply with Sections C101.1 through C101.14 as amended by these rules.2. The commercial establishment demonstrates that it has and will have qualified staff to oversee the gray water recycling systems. Qualified staff is defined as level 3 waste water treatment plan operator as specified by the Department of Environmental Quality.3. Gray water recycling systems shall only receive non hazardous waste discharge of bathtubs, showers, lavatories, clothes washers and laundry sinks such as chemicals having a pH of 6.0 to 9.0, or non flammable or non combustible liquids, liquids without objectionable odors, non-highly pigmented liquids, or other liquids that will not interfere with the operation of the sewer treatment facilities.C101.2 Permit required. A permit for any gray water recycling system shall not be issued until complete plans prepared by a licensed engineer, with appropriate data satisfactory to the Code Official, have been submitted and approved. No changes or connections shall be made to either the gray water recycling system or the potable water system within any site containing a gray water recycling system, without prior approved by the Code Official. A permit may also be required by the local health department to monitor compliance with this appendix for system operator standards and record keeping.C101.3 Definition. The following term shall have the meaning shown herein.GRAY WATER. Waste water discharged from lavatories, bathtubs, showers, clothes washers and laundry sinks.C101.4 Installation. All drain, waste and vent piping associated with gray water recycling systems shall be installed in full compliance with this code.C101.5 Gray Water Reservoir. Gray water shall be collected in an approved reservoir construction of durable, nonabsorbent and corrosion-resistant materials. The reservoir shall be a closed and gas-tight vessel. Gas tight access openings shall be provided to allow inspection and cleaning of the reservoir interior. The holding capacity of the reservoir shall be a minimum of twice the volume of water required to meet the daily flushing requirements of the fixtures supplied by the gray water, but not less than 50 gallons (189 L). The reservoir shall be sized to limit the retention time of gray water to 72 hours maximum.C101.6 Filtration. Gray water entering the reservoir shall pass through an approved cartridge filter or other method approved by the Code Official.C101.7 Disinfection. Gray water shall be disinfected by an approved method that employs one or more disinfectants such as chlorine, iodine or ozone. A minimum of 1 ppm free residual chlorine shall be maintained in the gray water recycling system reservoir. Such disinfectant shall be automatically dispensed. An alarm shall be provided to shut down the gray water recycling system if disinfectant levels are not maintained at the required levels.C101.8 Makeup water. Potable water shall be supplied as a source of makeup water for the gray water recycling system. The potable water supply to any building with a gray water recycling system shall be protected against backflow by an RP backflow assembly installed in accordance with this code. There shall be full-open valve on the makeup water supply to the reservoir. The potable water supply to the gray water reservoir shall be protected by an air gap installed in accordance with this code.C101.9 Overflow. The reservoir shall be equipped with an overflow pipe of the same diameter as the influent pipe for the gray water. The overflow shall be directly connected to the sanitary drainage system.C101.10 Drain. A drain shall be located at the lowest point of the reservoir and shall be directly connected to the sanitary drainage system. The drain shall be the same diameter as the overflow pipe required by Section C101.9 and shall be provided with a full-open valve.C101.11 Vent required. The reservoir shall be provided with a vent sized in accordance with Chapter 9 based on the size of the reservoir influent pipe.C101.12 Coloring. The gray water shall be automatically dyed blue or green with a food grade vegetable dye before such water is supplied to the fixtures.C101.13 Identification. All gray water distribution piping and reservoirs shall be identified as containing non-potable water. Gray water recycling system piping shall be permanently colored purple or continuously wrapped with purple-colored Mylar tape. The tape or permanently colored piping shall be imprinted in black, upper case letters with the words "CAUTION: GRAY WATER, DO NOT DRINK."All equipment areas and rooms for gray water recycling system equipment shall have a sign posted in a conspicuous place with the following text: TO CONSERVE WATER, THIS BUILDING USES GRAY WATER TO FLUSH TOILETS AND URINALS, DO NOT CONNECT TO THE POTABLE WATER SYSTEM. The location of the signage shall be determined by the Code Official.C101.14 Removal from service. All gray water recycling systems that are removed from service shall have all connections to the reservoir capped and routed back to the building sewer. All gray water distribution lines shall be replaced with new materials.C201.1 Outside the building. Gray water reused outside the building shall comply with the requirements of the Department of Environmental Quality Rule R317.R156-56-804. Statewide Amendments to the IMC.The following are adopted as amendments to the IMC to be applicable statewide:R156-56-805. Statewide Amendments to the IFGC.The following are adopted as amendments to the IFGC to be applicable statewide:(1) The following paragraph is added at the end of Section 305.1305.1 General. After natural gas, space and water heating appliances have been adjusted for altitude and the Btu content of the natural gas, the installer shall apply a sticker in a visible location indicating that the proper adjustments to such appliances have been made. The adjustments for altitude and the Btu content of the natural gas shall be done in accordance with the manufacturer's installation instructions and the gas utility's approved practices.(2) Chapter 4, Section 401 General, a new section 401.9 is added as follows:401.9 Meter protection. Fuel gas services shall be in an approved location and/or provided with structures designed to protect the fuel gas meter and surrounding piping from physical damage, including falling, moving, or migrating ice and snow. If an added structure is used, it must still provide access for service and comply with the IBC or the IRC.R156-56-806. Statewide Amendments to the NEC.The following are adopted as amendments to the NEC to be applicable statewide:R156-56-807. Statewide Amendments to the IECC.The following are adopted as amendments to the IECC to be applicable statewide:(1) In Section 504.4, the following exception is added:Exception: Heat traps, other than the arrangement of piping and fittings, shall be prohibited unless a means of controlling thermal expansion can be ensured as required in the IPC Section 607.3.R156-56-808. Installation and Safety Requirements for Mobile Homes Built Prior to June 15, 1976.(1) Mobile homes built prior to June 15, 1976 which are subject to relocation, building alteration, remodeling or rehabilitation shall comply with the following:(a) Exits and egress windows(i) Egress windows. The home has at least one egress window in each bedroom, or a window that meets the minimum specifications of the U.S. Department of Housing and Urban Development's (HUD) Manufactured Homes Construction and Safety Standards (MHCSS) program as set forth in 24 C.F.R. Parts 3280, 3283 and 3283, MHCSS 3280.106 and 3280.404 for manufactured homes. These standards require the window to be at least 22 inches in the horizontal or vertical position in its least dimension and at least five square feet in area. The bottom of the window opening shall be no more than 36 inches above the floor, and the locks and latches and any window screen or storm window devices that need to be operated to permit exiting shall not be located more than 54 inches above the finished floor.(ii) Exits. The home is required to have two exterior exit doors, located remotely from each other, as required in MHCSS 3280.105. This standard requires that single-section homes have the doors no less than 12 feet, center-to-center, from each other, and multisection home doors no less than 20 feet center-to center from each other when measured in a straight line, regardless of the length of the path of travel between the doors. One of the required exit doors must be accessible from the doorway of each bedroom and no more than 35 feet away from any bedroom doorway. An exterior swing door shall have a 28-inch-wide by 74-inch-high clear opening and sliding glass doors shall have a 28-inch-wide by 72-inch-high clear opening. Each exterior door other than screen/storm doors shall have a key-operated lock that has a passage latch; locks shall not require the use of a key or special tool for operation from the inside of the home.(b) Flame spread(i) Walls, ceilings and doors. Walls and ceilings adjacent to or enclosing a furnace or water heater shall have an interior finish with a flame-spread rating not exceeding 25. Sealants and other trim materials two inches or less in width used to finish adjacent surfaces within these spaces are exempt from this provision, provided all joints are supported by framing members or materials with a flame spread rating of 25 or less. Combustible doors providing interior or exterior access to furnace and water heater spaces shall be covered with materials of limited combustibility (i.e. 5/16-inch gypsum board, etc.), with the surface allowed to be interrupted for louvers ventilating the space. However, the louvers shall not be of materials of greater combustibility than the door itself (i.e., plastic louvers on a wooden door). Reference MHCSS 3280.203.(ii) Exposed interior finishes. Exposed interior finishes adjacent to the cooking range (surfaces include vertical surfaces between the range top and overhead cabinets, the ceiling, or both) shall have a flame-spread rating not exceeding 50, as required by MHCSS 3280.203. Backsplashes not exceeding six inches in height are exempted. Ranges shall have a vertical clearance above the cooking top of not less than 24 inches to the bottom of combustible cabinets, as required by MHCSS 3280.204(e).(c) Smoke detectors(i) Location. A smoke detector shall be installed on any ceiling or wall in the hallway or space communicating with each bedroom area between the living area and the first bedroom door, unless a door separates the living area from that bedroom area, in which case the detector shall be installed on the living-area side, as close to the door as practicable, as required by MHCSS 3280.208. Homes with bedroom areas separated by anyone or combination of common-use areas such as a kitchen, dining room, living room, or family room (but not a bathroom or utility room) shall be required to have one detector for each bedroom area. When located in the hallways, the detector shall be between the return air intake and the living areas.(ii) Switches and electrical connections. Smoke detectors shall have no switches in the circuit to the detector between the over-current protection device protecting the branch circuit and the detector. The detector shall be attached to an electrical outlet box and connected by a permanent wiring method to a general electrical circuit. The detector shall not be placed on the same branch circuit or any circuit protected by a ground-fault circuit interrupter.(d) Solid-fuel-burning stoves/fireplaces(i) Solid-fuel-burning fireplaces and fireplace stoves. Solid-fuel-burning, factory-built fireplaces and fireplace stoves may be used in manufactured homes, provided that they are listed for use in manufactured homes and installed according to their listing/manufacturer's instructions and the minimum requirements of MHCSS 3280.709(g).(ii) Equipment. A solid-fuel-burning fireplace or fireplace stove shall be equipped with an integral door or shutters designed to close the fire chamber opening and shall include complete means for venting through the roof, a combustion air inlet, a hearth extension, and means to securely attach the unit to the manufactured home structure.(A) Chimney. A listed, factory-built chimney designed to be attached directly to the fireplace/fireplace stove and equipped with, in accordance with the listing, a termination device and spark arrester, shall be required. The chimney shall extend at least three feet above the part of the roof through which it passes and at least two feet above the highest elevation of any part of the manufactured home that is within 10 feet of the chimney.(B) Air-intake assembly and combustion-air inlet. An air-intake assembly shall be installed in accordance with the terms of listings and the manufacturer's instruction. A combustion air inlet shall conduct the air directly into the fire chamber and shall be designed to prevent material from the hearth from dropping on the area beneath the manufactured home.(C) Hearth. The hearth extension shall be of noncombustible material that is a minimum of 3/8-inch thick and shall extend a minimum of 16 inches in front and eight inches beyond each side of the fireplace/fireplace stove opening. The hearth shall also extend over the entire surface beneath a fireplace stove and beneath an elevated and overhanging fireplace.(e) Electrical wiring systems(i) Testing. All electrical systems shall be tested for continuity in accordance with MHCSS 3280.810, to ensure that metallic parts are properly bonded; tested for operation, to demonstrate that all equipment is connected and in working order; and given a polarity check, to determine that connections are proper.(ii) 5.2 Protection. The electrical system shall be properly protected for the required amperage load. If the unit wiring employs aluminum conductors, all receptacles and switches rated at 20 amperes or less that are directly connected to the aluminum conductors shall be marked CO/ALA. Exterior receptacles, other than heat tape receptacles, shall be of the ground-fault circuit interrupter (GFI) type. Conductors of dissimilar metals (copper/aluminum or copper-clad aluminum) must be connected in accordance with National Electrical Code (NEC) Section 110-14.(f) Replacement furnaces and water heaters(i) Listing. Replacement furnaces or water heaters shall be listed for use in a manufactured home. Vents, roof jacks, and chimneys necessary for the installation shall be listed for use with the furnace or water heater.(ii) Securement and accessibility. The furnace and water heater shall be secured in place to avoid displacement. Every furnace and water heater shall be accessible for servicing, for replacement, or both as required by MHCSS 3280.709(a).(iii) Installation. Furnaces and water heaters shall be installed to provide complete separation of the combustion system from the interior atmosphere of the manufactured home, as required by MHCSS.(A) Separation. The required separation may be achieved by the installation of a direct-vent system (sealed combustion system) furnace or water heater or the installation of a furnace and water heater venting and combustion systems from the interior atmosphere of the home. There shall be no doors, grills, removable access panels, or other openings into the enclosure from the inside of the manufactured home. All openings for ducts, piping, wiring, etc., shall be sealed.(B) Water heater. The floor area in the area of the water heater shall be free from damage from moisture to ensure that the floor will support the weight of the water heater.]R156-56-[
820]801 . Statewide Amendments to the IEBC.The following are adopted as amendments to the IEBC to be applicable statewide:
(1) In Section 101.5 the exception is deleted.
(2) [
Section R106.3.2 is deleted and replaced with the following:R106.3.2 Previous approval. If a lawful permit has been issued and the construction of which has been pursued in good faith within 180 days after the effective date of the code and has not been abandoned, then the construction may be completed under the code in effect at the time of the issuance of the permit.(3)] In Section 202 the definition for existing buildings is deleted and replaced with the following:EXISTING BUILDING. A building lawfully erected [
prior to January 1, 2002]under a prior adopted code, or one which is deemed a legal non-conforming building by the code official, and one which is not a dangerous building.(3) In Section 605.1, Exception number 3, the following is added at the end of the sentence:
"unless undergoing a change of occupancy classification."
(4) Section [
606.2.2]606.2.1 is deleted and replaced with the following:[
602.2.2]606.2.1 Parapet bracing, wall anchors, and other appendages. Buildings constructed prior to 1975 shall have parapet bracing, wall anchors, and appendages such as cornices, spires, towers, tanks, signs, statuary, etc. evaluated by a licensed engineer when said building is undergoing reroofing, or alteration of or repair to said feature. Such parapet bracing, wall anchors, and appendages shall be evaluated in accordance with the reduced International Building Code level seismic forces as specified in IEBC Section [506.1.1.3]101.5.4.2 and design procedures of Section [506.1.1.1]101.5.4. When found to be deficient because of design or deteriorated condition, the engineer's recommendations to anchor, brace, reinforce, or remove the deficient feature shall be implemented.EXCEPTIONS:
1. Group R-3 and U occupancies.
2. Unreinforced masonry parapets need not be braced according to the above stated provisions provided that the maximum height of an unreinforced masonry parapet above the level of the diaphragm tension anchors or above the parapet braces shall not exceed one and one-half times the thickness of the parapet wall. The parapet height may be a maximum of two and one-half times its thickness in other than Seismic Design Categories D, E, or F.[
(5) Section 705.3.1.2 is deleted and replaced with the following:705.3.1.2 Fire escapes required. When more than one exit is required, an existing fire escape complying with Section 705.3.1.2.1 shall be accepted as providing one of the required means of egress.705.3.1.2.1 Fire escape access and details. Fire escapes shall comply with all of the following requirements:1. Occupants shall have unobstructed access to the fire escapes without having to pass through a room subject to locking.2. Access to an existing fire escape shall be through a door, except that windows shall be permitted to provide access from single dwelling units or sleeping units in Group R-1, R-2, and I-1 occupancies or to provide access from spaces having a maximum occupant load of 10 in other occupancy classifications.3. Existing fire escapes shall be permitted only where exterior stairs cannot be utilized because of lot lines limiting the stair size or because of the sidewalks, alleys, or roads at grade level.4. Openings within 10 feet (3048 mm) of fire escape stairs shall be protected by fire assemblies having minimum 3/4-hour fire-resistance ratings.Exception: Opening protection shall not be required in buildings equipped throughout with an approved automatic sprinkler system.5. In all buildings of Group E occupancy, up to and including the 12th grade, buildings of Group I occupancy, rooming houses, and childcare centers, ladders of any type are prohibited on fire escapes used as a required means of egress.(6) Section 906.1 is deleted and replaced with the following:906.1 General. Accessibility in portions of buildings undergoing a change of occupancy classification shall comply with Section 605 and 912.8.]([
7]5) Section 907.3.1 is deleted and replaced with the following:907.3.1 Compliance with the International Building Code. When a building or portion thereof is subject to a change of occupancy such that a change in the nature of the occupancy results in a higher seismic occupancy based on Table 1604.5 of the International Building Code; or where such change of occupancy results in a reclassification of a building to a higher hazard category as shown in Table 912.4; or where a change of a Group M occupancy to a Group A, [
ETM]E, F, M, R-1, R-2, or R-4 occupancy with two-thirds or more of the floors involved in Level 3 alteration work; or when such change of occupancy results in a design occupant load increase of 100% or more, the building shall conform to the seismic requirements of the International Building Code for the new seismic use group.Exceptions 1-4 remain unchanged.
5. Where the design occupant load increase is less than 25 occupants and the occupancy category does not change.
([
8]6) In Section 912.7.3 exception 2 is deleted.([
9]7) In Section 912.8 number 7 is added as follows:7. When a change of occupancy in a building or portion of a building results in a Group R-2 occupancy, not less than 20 percent of the dwelling or sleeping units shall be Type B dwelling or sleeping units. These dwelling or sleeping units may be located on any floor of the building provided with an accessible route. Two percent, but not less than one unit, of the dwelling or sleeping units shall be Type A dwelling units.
[
R156-56-901. Local Amendments to the IBC.The following are adopted as amendments to the IBC to be applicable to the following jurisdictions:(1) City of Farmington:(a) A new Section (F)903.2.14 is added as follows:(F)903.2.14 Group R, Division 3 Occupancies. An automatic sprinkler system shall be installed throughout every dwelling in accordance with NFPA 13-D, when any of the following conditions are present:1. The structure is over two stories high, as defined by the building code;2. The nearest point of structure is more than 150 feet from the public way;3. The total floor area of all stories is over 5,000 square feet (excluding from the calculation the area of the basement and/or garage); or4. The structure is located on a street constructed after March 1, 2000 that has a gradient over 12% and, during fire department response, access to the structure will be gained by using such street. (If the access is intended to be from a direction where the steep gradient is not used, as determined by the Chief, this criteria shall not apply).Such sprinkler system shall be installed in basements, but need not be installed in garages, under eves or in enclosed attic spaces, unless required by the Chief.(b) A new Section 907.20 is added as follows:907.20 Alarm Circuit Supervision. Alarm circuits in alarm systems provided for commercial uses (defined as other than one- and two-family dwellings and townhouses) shall have Class "A" type of supervision. Specifically, Type "B" or End-of-line resistor and horn supervised systems are not allowed.(c) NFPA 13-02 is amended to add the following new sections:6.8.6 FDC Security Locks Required. All Fire Department connections installed for fire sprinkler and standpipe systems shall have approved security locks.6.10 Fire Pump Disconnect Signs. When installing a fire pump, red plastic laminate signs shall be installed in the electrical service panel, if the pump is wired separately from the main disconnect. These signs shall state: "Fire Pump Disconnect ONLY" and "Main Breaker DOES NOT Shut Off Fire Pump".14.1.1.5 Plan Preparation Identification. All plans for fire sprinkler systems, except for manufacturer's cut sheets of equipment shall include the full name of the person who prepared the drawings. When the drawings are prepared by a registered professional engineer, the engineer's signature shall also be included.15.1.2.5 Verification of Water Supply:15.1.2.5.1 Fire Flow Tests. Fire flow tests for verification of water supply shall be conducted and witnessed for all applications other than residential unless directed otherwise by the Chief. For residential water supply, verification shall be determined by administrative procedure.15.1.2.5.2 Accurate and Verifiable Criteria. The design calculations and criteria shall include an accurate and verifiable water supply.17.8.4 Testing and Inspection of Systems. Testing and inspection of sprinkler systems shall include, but are not limited to:Commercial:FLUSH-Witness Underground Supply Flush;ROUGH Inspection-Installation of Riser, System Piping, Head Locations and all Components, Hydrostatic Pressure Test;FINAL Inspection-Head Installation and Escutcheons, Inspectors Test Location and Flow, Main Drain Flow, FDC Location and Escutheon, Alarm Function, Spare Parts, Labeling of Components and Signage, System Completeness, Water Supply Pressure Verification, Evaluation of Any Unusual Parameter.(2) City of North Salt LakeA new Section (F)903.2.14 is added as follows:(F)903.2.14 Group R, Division 3 Occupancies. An automatic sprinkler system shall be installed throughout every dwelling in accordance with NFPA 13-D, when the following condition is present:1. The structure is over 6,200 square feet.Such sprinkler system shall be installed in basements, but need not be installed in garages, under eves, or in enclosed attic spaces, unless required by the fire chief.(3) Park City Corporation and Park City Fire District:(a) Section (F)903.2 is deleted and replaced with the following:(F)903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the location described in this section.All new construction having more than 6,000 square feet on any one floor, except R-3 occupancy.All new construction having more than two (2) stories, except R-3 occupancy.All new construction having three (3) or more dwelling units, including units rented or leased, and including condominiums or other separate ownership.All new construction in the Historic Commercial Business zone district, regardless of occupancy.All new construction and buildings in the General Commercial zone district where there are side yard setbacks or where one or more side yard setbacks is less than two and one half (2.5) feet per story of height.All existing building within the Historic District Commercial Business zone.(b) In Table 1505.1, the following is added as footnotes d and e:d. Wood roof covering assemblies are prohibited in R-3 occupancies in areas with a combined rating of more than 11 using Tables 1505.1.1 and 1505.1.2 with a score of 9 for weather factors.e. Wood roof covering assemblies shall have a Class A rating in occupancies other than R-3 in areas with a combined rating of more than 11 using Tables 1505.1.1 and 1505.1.2 with a score of 9 for weather factors. The owner of the building shall enter into a written and recorded agreement that the Class A rating of the roof covering assembly will not be altered through any type of maintenance process.TABLE 1505.1.1
WILDFIRE HAZARD SEVERITY SCALE
RATING SLOPE VEGETATION
1 less than or equal to 10% Pinion-juniper
2 10.1 - 20% Grass-sagebrush
3 greater than 20% Mountain brush or softwoodsTABLE 1505.1.2
PROHIBITION/ALLOWANCE OF WOOD ROOFING
Rating R-3 Occupancy All Other Occupancies
less than or
equal to 11 wood roof covering wood roof covering
assemblies per assemblies per
Table 1505.1 are Table 1505.1 are
allowed allowed
greater than or
equal to 12 wood roof covering wood roof covering
is prohibited assemblies with a
Class A rating are
allowed(c) Appendix C is adopted.(4) Sandy City(a) Section (F)903.2.14 is added as follows:(F)903.2.14 An automatic sprinkler system shall be installed in accordance with NFPA 13 throughout buildings containing all occupancies where fire flow exceeds 2,000 gallons per minute, based on Table B105.1 of the 2006 International Fire Code. Exempt locations as indicated in Section 903.3.1.1.1 are allowed.Exception: Automatic fire sprinklers are not required in buildings used solely for worship, Group R Division 3, Group U occupancies and buildings complying with the International Residential Code unless otherwise required by the International Fire Code.(b) Appendix L is added to the IBC and adopted as follows:Appendix L BUILDINGS AND STRUCTURES CONSTRUCTED IN AREAS DESIGNATED AS WILDLAND-URBAN INTERFACE AREASAL 101.1 General. Buildings and structures constructed in areas designated as Wildland-Urban Interface Areas by Sandy City shall be constructed using ignition resistant construction as determined by the Fire Marshal. Section 502 of the 2006 International Wildland-Urban Interface Code (IWUIC), as promulgated by the International Code Council, shall be used to determine Fire Hazard Severity. The provisions listed in Chapter 5 of the 2006 International Wildland-Urban Interface Code, as modified herein, shall be used to determine the requirements for Ignition Resistant Construction.(i) In Section 504 of the IWUIC Class I IGNITION-RESISTANT CONSTRUCTION a new Section 504.1.1 is added as follows:504.1.1 General. Subsections 504.5, 504.6, and 504.7 shall only be required on the exposure side of the structure, as determined by the Fire Marshal, where defensible space is less than 50 feet as defined in Section 603 of the 2006 International Wildland-Urban Interface Code.(ii) In Section 505 of the IWUIC Class 2 IGNITION-RESISTANT CONSTRUCTION Subsections 505.5 and 505.7 are deleted.R156-56-902. Local Amendments to the IRC.The following are adopted as amendments to the IRC to be applicable to the following jurisdictions:(1) All local amendments to the IBC under Section R156-56-901, the NEC under Section R156-56-906, the IPC under Section R156-56-903, the IMC under Section R156-56-904, the IFGC under Section R156-56-905 and the IECC under Section R156-56-907 which may be applied to detached one and two family dwellings and multiple single family dwellings shall be applicable to the corresponding provisions of the IRC for the local jurisdiction to which the local amendment has been made. All references to the ICC Electrical Code are deleted and replaced with the National Electrical Code adopted under Section R156-56-701(1)(b).(2) City of Farmington:R325 Automatic Sprinkler Systems.(a) Sections R325.1 and R325.2 are added as follows:R325.1 When required. An automatic sprinkler system shall be installed throughout every dwelling in accordance with NFPA 13-D, when any of the following conditions are present:1. the structure is over two stories high, as defined by the building code;2. the nearest point of structure is more than 150 feet from the public way;3. the total floor area of all stories is over 5,000 square feet (excluding from the calculation the area of the basement and/or garage); or4. the structure is located on a street constructed after March 1, 2000 that has a gradient over 12% and, during fire department response, access to the structure will be gained by using such street. (If the access is intended to be from a direction where the steep gradient is not used, as determined by the Chief, this criteria shall not apply).R325.2 Installation requirements and standards. Such sprinkler system shall be installed in basements, but need not be installed in garages, under eves or in enclosed attic spaces, unless required by the Chief. Such system shall be installed in accordance with NFPA 13-D.(b) In Chapter 43, Referenced Standards, the following NFPA referenced standards are added as follows:TABLEADD
13D-02 Installation of Sprinkler Systems in
One- and Two-family Dwellings and
Manufactured Homes, as amended by these rules
13R-02 Installation of Sprinkler Systems in
Residential Occupancies Up to and
Including Four Stories in Height
101-03 Life Safety Code(c) NFPA 13D-02 is amended to add the following new sections:1.15 Reference to NFPA 13-D. All references to NFPA 13-D in the codes, ordinances, rules or regulations governing NFPA 13-D systems shall be read to refer to "modified NFPA 13-D" to reference the NFPA 13-D as amended by additional regulations adopted by Farmington City.4.6 Testing and Inspection of Systems. Testing and inspection of sprinkler systems shall include, but are not limited to:Residential:ROUGH Inspection-Verify Water Supply Piping Size and Materials, Installation of Riser, System Piping, Head Locations and all Components, Hydrostatic Pressure Test.FINAL Inspection-Inspectors Test Flow, System Completeness, Spare Parts, Labeling of Components and Signage, Alarm Function, Water Supply Pressure Verification.5.2.2.3 Exposed Piping of Metal. Exposed Sprinkler Piping material in rooms of dwellings shall be of Metal.EXCEPTIONS:a. CPVC Piping is allowed in unfinished mechanical and storage rooms only when specifically listed for the application as installed.b. CPVC Piping is allowed in finished, occupied rooms used for sports courts or similar uses only when the ceiling/floor framing above is constructed entirely of non-combustible materials, such as a concrete garage floor on metal decking.5.2.2.4 Water Supply Piping Material. Water Supply Piping from where the water line enters the dwelling adjacent to and inside the foundation to the fire sprinkler contractor point-of-connection shall be metal, suitable for potable plumbing systems. See Section 7.1.4 for valve prohibition in such piping. Piping down stream from the point-of-connection used in the fire sprinkler system, including the riser, shall conform to NFPA 13-D standards.5.4 Fire Pump Disconnect Signs. When installing a Fire Pump, Red Plastic Laminate Signs shall be installed in the electrical service panel, if the pump is wired separately from the main disconnect. These signs shall state: "Fire Pump Disconnect ONLY" and "Main Breaker DOES NOT Shut Off Fire Pump".7.1.4 Valve Prohibition. NFPA 13-d, Section 7.1 is hereby modified such that NO VALVE is permitted from the City Water Meter to the Fire Sprinkler Riser Control.7.6.1 Mandatory Exterior Alarm. Every dwelling that has a fire sprinkler system shall have an exterior alarm, installed in an approved location. The alarm shall be of the combination horn/strobe or electric bell/strobe type, approved for outdoor use.8.1.05 Plan Preparation Identification. All plans for fire sprinkler systems, except for manufacturer's cut sheets of equipment, shall include the full name of the person who prepared the drawings. When the drawings are prepared by a registered professional engineer, the engineer's signature shall also be included.8.7 Verification of Water Supply:8.7.1 Fire Flow Tests: Fire Flow Tests for verification of Water Supply shall be conducted and witnesses for all applications other than residential, unless directed otherwise by the Chief. For residential Water Supply, verification shall be determined by administrative procedure.8.7.2 Accurate and Verifiable Criteria. The design calculations and criteria shall include an accurate and verifiable Water Supply.(3) Morgan City Corp:In Section R105.2 Work Exempt From Permit, the following is added:10. Structures intended to house farm animals, or for the storage of feed associated with said farm animals when all the following criteria is met:a. The parcel of property involved is zoned for the keeping of farm animals or has grand fathered animal rights.b. The structure is setback not less than 50 feet from the rear or side of dwellings, and not less than 10 feet from property lines and other structures.c. The structure does not exceed 1000 square feet of floor area, and is limited to 20 feet in height. Height is measured from the average grade to the highest point of the structure.d. Before construction, a site plan is submitted to, and approved by the building official.Electrical, plumbing, and mechanical permits shall be required when that work is included in the structure.(4) Morgan County:In Section R105.2 Work Exempt From Permit, the following is added:10. Structures intended to house farm animals, or for the storage of feed associated with said farm animals when all the following criteria is met:a. The parcel of property involved is zoned for the keeping of farm animals or has grand fathered animal rights.b. The structure is set back not less than required by the Morgan County Zoning Ordinance for such structures, but not less than 10 feet from property lines and other structures.c. The structure does not exceed 1000 square feet of floor area, and is limited to 20 feet in height. Height is measured from the average grade to the highest point of the structure.d. Before construction, a Land Use Permit must be applied for, and approved, by the Morgan County Planning and Zoning Department.Electrical, plumbing, and mechanical permits shall be required when that work is included in the structure.(5) City of North Salt Lake:Sections R325.1 and R325.2 are added as follows:R325.1 When Required. An automatic sprinkler system shall be installed throughout every dwelling when the following condition is present:1. The structure is over 6,200 square feet.R325.2 Installation requirements and standards. Such sprinkler system shall be installed in basements, but need not be installed in garages, under eves, or in enclosed attic spaces, unless required by the fire chief. Such system shall be installed in accordance with NFPA 13-D.(6) Park City Corporation:Appendix P is adopted.(7) Park City Corporation and Park City Fire District:(a) Section R905.7 is deleted and replaced with the following:R905.7 Wood shingles. The installation of wood shingles shall comply with the provisions of this section.Wood roof covering is prohibited in areas with a combined rating of more than 11 using the following tables with a score of 9 for weather factors.TABLE
WILDFIRE HAZARD SEVERITY SCALE
RATING SLOPE VEGETATION
1 less than or equal to 10% Pinion-juniper
2 10.1 - 20% Grass-sagebrush
3 greater than 20% Mountain brush or softwoods
PROHIBITION/EXEMPTION TABLERATING WOOD ROOF PROHIBITION
less than or equal to 11 wood roofs are allowed
greater than or equal to 12 wood roofs are prohibited(b) Section R905.8 is deleted and replaced with the following:R905.8 Wood Shakes. The installation of wood shakes shall comply with the provisions of this section. Wood roof covering is prohibited in areas with a combined rating of more than 11 using the following tables with a score of 9 for weather factors.TABLE
WILDFIRE HAZARD SEVERITY SCALE
RATING SLOPE VEGETATION
1 less than or equal to 10% Pinion-juniper
2 10.1 - 20% Grass-sagebrush
3 greater than 20% Mountain brush or softwoods
PROHIBITION/EXEMPTION TABLE
RATING WOOD ROOF PROHIBITION
less than or equal to 11 wood roofs are allowed
greater than or equal to 12 wood roofs are prohibited(c) Appendix K is adopted.(8) Sandy CityA new Section R325 is added to the IRC as follows:Section R325 IGNITION RESISTANT CONSTRUCTIONR325.1 General. Buildings and structures constructed in areas designated as Wildland-Urban Interface Areas by Sandy City shall be constructed using ignition resistant construction as determined by the Fire Marshal. Section 502 of the 2006 International Wildland-Urban Interface Code (IWUIC), as promulgated by the International Code Council, shall be used to determine Fire Hazard Severity. The provisions listed in Chapter 5 of the 2006 IWUIC, as modified herein, shall be used to determine the requirements for Ignition Resistant Construction.(i) In Section 504 of the IWUIC Class I IGNITION-RESISTANT CONSTRUCTION a new Section 504.1.1 is added as follows:504.1.1 General. Subsections 504.5, 504.6, and 504.7 shall only be required on the exposure side of the structure, as determined by the Fire Marshal, where defensible space is less than 50 feet as defined in Section 603 of the 2006 IWUIC.(ii) In Section 505 of the IWUIC Class 2 IGNITION-RESISTANT CONSTRUCTION Subsections 505.5 and 505.7 are deleted.R156-56-903. Local Amendments to the IPC.The following are adopted as amendments to the IPC to be applicable to the following jurisdictions:(1) Salt Lake CityAppendix C of the IPC as specified and amended in R156-56-803(62), (63) and (64).(2) South Jordan(a) Section 312.9.2 is deleted and replaced with the following:312.9.2 Testing. Reduced pressure principle backflow preventer assemblies, double check-valve assemblies, pressure vacuum breaker assemblies, reduced pressure detector fire protection backflow prevention assemblies, double check detector fire protection backflow prevention assemblies, hose connection backflow preventers, and spill-proof vacuum breakers shall be tested at the time of installation, immediately after repairs or relocation and at least annually. The testing procedure shall be performed in accordance with one of the following standards: ASSE 5013, ASSE 5015, ASSE 5020, ASSE 5047, ASSE 5048, ASSE 5052, ASSE 5056, CSA B64.10 or CSA B64.10.1. Assemblies, other than the reduced pressure principle assembly, protecting lawn irrigation systems that fail the annual test shall be replaced with a reduced pressure principle assembly.(b) Section 608.16.5 is deleted and replaced with the following:608.16.5 Connections to lawn irrigation systems. The potable water supply to lawn irrigation systems shall be protected against backflow by a reduced pressure principle backflow preventer.R156-56-904. Local Amendment to the IMC.The following are adopted as amendments to the IMC to be applicable to the following jurisdictions:R156-56-905. Local Amendment to the IFGC.The following are adopted as amendments to the IFGC to be applicable to the following jurisdictions:R156-56-906. Local Amendment to the NEC.The following are adopted as amendments to the NEC to be applicable to the following jurisdictions:R156-56-907. Local Amendment to the IECC.The following are adopted as amendments to the IECC to be applicable to the following jurisdictions:]R156-56-[
920] 802 . Local Amendment to the IEBC.The following are adopted as amendments to the IEBC to be applicable to the following jurisdictions:
None.
KEY: contractors, building codes, building inspections, licensing
Date of Enactment or Last Substantive Amendment: [
August 24, 2009]2010Notice of Continuation: March 29, 2007
Authorizing, and Implemented or Interpreted Law: 58-1-106(1)(a); 58-1-202(1)(a); 58-56-1; 58-56-4(2); 58-56-6(2)(a)[
; 58-56-18]; 58-56-19
Document Information
- Hearing Meeting:
- 06/09/2010 09:00 AM, State Office Building, 450 N State Street, Room 4112, Salt Lake City, UT
- Effective Date:
- 6/21/2010
- Publication Date:
- 05/15/2010
- Filed Date:
- 04/22/2010
- Agencies:
- Commerce,Occupational and Professional Licensing
- Rulemaking Authority:
Section 58-56-1
Subsection 58-1-106(1)(a)
Subsection 58-56-6(2)(a)
Subsection 58-1-202(1)(a)
Section 58-56-19
Subsection 58-56-4(2)
- Authorized By:
- Mark Steinagel, Director
- DAR File No.:
- 33566
- Related Chapter/Rule NO.: (1)
- R156-56. Utah Uniform Building Standard Act Rules.