DAR File No.: 28679
Filed: 04/27/2006, 07:38
Received by: NLRULE ANALYSIS
Purpose of the rule or reason for the change:
This rulemaking removes the requirement for assisted living facilities to build a two-room laundry facility. The proposed rule would only require one room for laundry processing, combining the soiled and clean processes into the same room.
Summary of the rule or change:
The proposed rule amendments will change the requirements for assisted living facility construction of laundry facilities. It will take out the requirement for these facilities to have two separate rooms for laundry processing. The rule will still require that all other laundry processing requirements remain the same, and will add a dimension to the pre-wash sink to ensure that it is large enough to meet the needs of the facilities. The rule currently requires a soiled and clean laundry room to process laundry.
State statutory or constitutional authorization for this rule:
Title 26, Chapter 21
Anticipated cost or savings to:
the state budget:
There is no anticipated cost to the state budget. This rule amendment will only affect providers of new assisted living facilities.
local governments:
There is no anticipated cost to the local governments. This rule amendment will only affect providers of new assisted living facilities. No local governments operate assisted living facilities.
other persons:
There will be an anticipated cost savings to assisted living providers that are building new facilities. The average size of a soiled linen room is approximately 12' X 12'. The average construction cost per square foot is $100, which adds up to a savings of approximately $14,400 per new project. There are about five new assisted living projects that submit plans to the Department of Health every year. The overall savings to new providers is estimated at $72,000 per year.
Compliance costs for affected persons:
There will be no cost to any persons from this rule amendment. The rule will decrease the construction requirements of assisted living facilities, resulting in a cost savings to new providers.
Comments by the department head on the fiscal impact the rule may have on businesses:
This rule change will decrease construction costs without compromising resident safety. A. Richard Melton, Acting Executive Director
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:
Health
Health Systems Improvement, Licensing
CANNON HEALTH BLDG
288 N 1460 W
SALT LAKE CITY UT 84116-3231Direct questions regarding this rule to:
Joel Hoffman at the above address, by phone at 801-538-6165, by FAX at 801-538-6163, or by Internet E-mail at jhoffman@utah.gov
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:
06/14/2006
This rule may become effective on:
06/15/2006
Authorized by:
David N. Sundwall, Executive Director
RULE TEXT
R432. Health, Health Systems Improvement, Licensing.
R432-6. Assisted Living Facility General Construction.
R432-6-22. Mechanical, Heating, Cooling and Ventilation Systems.
(1) The HVAC system design shall prevent large temperature differentials, high velocity supply, excessive noise, and air stagnation.
(2) Air supply and exhaust in rooms for which no minimum total air change rate is mandated by Table 2 may vary to zero in response to room load.
(3) Mechanical ventilation shall be provided for interior spaces independent of thermostat-controlled demands.
(a) Minimum total air change, room temperature, and temperature control shall comply with standards in Table 2.
(b) To maintain asepsis and odor control, airflow supply and exhaust shall be controlled to ensure movement of air from clean to less clean areas.
(c) Rooms containing heat-producing equipment shall be insulated and ventilated to prevent the floor surface above or the walls of adjacent occupied areas from exceeding a temperature of ten degrees Fahrenheit above ambient room temperature.
(d) All rooms and occupiable areas in the facility shall have provisions for ventilation. Natural window ventilation may be used for ventilation of nonsensitive areas and resident rooms when weather conditions permit, but mechanical ventilation shall be provided during periods of temperature extremes.
(e) The heating system shall be capable of maintaining temperatures of 80 degrees F. in areas occupied by residents.
(f) The cooling system shall be capable of maintaining temperatures of 72 degrees F. in areas occupied by residents.
(g) Equipment must be available to provide essential heating during a loss of normal heating capability. All emergency heating devices shall be approved by the local fire jurisdiction.
(h) Fans serving exhaust systems shall be located at the discharge end and shall be readily serviceable. Exhaust fans may be on the inlet side if individually ducted directly to the outside.
(i) Fresh air intakes shall be located at least 10 feet from exhaust outlets of ventilating systems, combustion equipment stacks, plumbing vents, or areas subject to vehicular exhaust or other noxious fumes.
(j) All ventilation, air conditioning systems and air delivery equipment, including through wall units, shall be equipped with filters in accordance with Table 2.
(k) Gravity exhaust may be used where conditions permit for boiler rooms, central storage, and other nonresident areas.
(l) The ventilation system shall be air tested and balanced prior to the final Department construction inspection. The initial test results and air balancing report shall be maintained for Department review.
TABLE 2
Ventilation Requirements
AREA AIR MINIMUM MINIMUM ALL AIR
DESIGNATION MOVEMENT AIR TOTAL AIR EXHAUSTED
IN CHANGES CHANGES OUTSIDE
RELATION OF PER HOUR
TO OUTDOOR
ADJACENT AIR PER
AREAS HOUR TO
ROOM
Bath and N Optional 10 YES
Shower
Rooms
Clean P Optional 2 Optional
Linen
Storage
Dietary V Optional 2 Optional
Day
Storage
Food E 2 10 YES
Preparation
Center
Janitors' N Optional 10 YES
Closets
Laundry V 2 10 YES
Corridor E Optional 2 Optional
Grooming N 2 2 YES
Area
Resident E Greater 2 Optional
Room of one air
change or
minimum 20 CFM/
person
Soiled N Optional 10 YES
Linen
[Sorting]holding
and
Storage
Toilet N Optional 10 YES
Rooms
Ware N Optional 10 YES
Washing
Common E 2 2 Optional
Areas
E = Equal; N = Negative; P = Positive; V = Variable(m) The requirements of Table 2 do not apply to limited capacity facilities. Limited capacity facilities shall provide exhaust for kitchens and bathrooms.
(n) If an existing building bathroom or toilet room is not exhausted to the outside, the licensee may submit a Request for Agency Action Variance to the Table 2 requirements at the time of initial licensing.
(4) All areas for resident care, and those areas providing direct service or clean supplies shall provide at least one filter bed with a minimum of 30% efficiency.
(5) All administrative, bulk storage, soiled holding, food preparation and laundries shall provide at least one filter bed with a minimum of 25% efficiency.
R432-6-210. Linen Services.
(1) Each facility shall have space and equipment to store and process clean and soiled linen as required for resident care. Laundry may be done within the facility, in a building on or off-site, or in a commercial or shared laundry.
(2) If laundry is done off the site, the following shall be provided:
(a) a room for receiving and holding soiled linen until ready for pickup or processing;
(b) a central, clean linen storage room(s); and
(c) a lavatory in each area where unbagged, soiled linen is handled.
(3) If a large or small facility processes its own laundry on-site, the following shall be provided:
(a) a laundry room for receiving, holding, washing, drying, and sorting soiled linens, with the following:
(i) a pre-wash [
clinical]sink at least 13 inches deep by 20 inches wide;[facilities](ii) [
and]a separate hand washing [facilities]sink;[
(b)](iii) [a laundry processing room with]washer(s) and dryer(s); and[
(c) rooms (a) and (b) above must be separated by a door with a self closing device installed;(d)](iv) storage for laundry supplies;[
(e)](b) arrangement of equipment that will permit an orderly workflow and minimize cross-traffic that might mix clean and soiled operations; and[
(f)](c) a central, clean linen storage room(s);[(g) Facilities may provide holding rooms on each level for bagged, soiled linen.](4) If a limited capacity facility processes its own laundry on-site, the following shall be provided:
(a) a room to store and process both clean and soiled linen;
(b) a washer and dryer; and
(c) a utility sink in the laundry room.
(5) Each facility shall provide a minimum of one washing machine, one clothes dryer, and ironing equipment in good working order for resident use.
KEY: health facilities
Date of Enactment or Last Substantive Amendment: [
December 19, 2002]2006Notice of Continuation: January 8, 2004
Authorizing and Implemented or Interpreted Law: 26-21-5; 26-21-16
Document Information
- Effective Date:
- 6/15/2006
- Publication Date:
- 05/15/2006
- Type:
- Special Notices
- Filed Date:
- 04/27/2006
- Agencies:
- Health,Health Systems Improvement, Licensing
- Rulemaking Authority:
Title 26, Chapter 21
- Authorized By:
- David N. Sundwall, Executive Director
- DAR File No.:
- 28679
- Related Chapter/Rule NO.: (1)
- R432-6. Assisted Living Facility General Construction.