No. 28578 (Amendment): R710-3-3. Amendments and Additions  

  • DAR File No.: 28578
    Filed: 03/29/2006, 08:33
    Received by: NL

     

    RULE ANALYSIS

    Purpose of the rule or reason for the change:

    The Utah Fire Prevention Board met on January 10, 2006, in a regularly scheduled Board meeting and proposed to amend Subsection R710-3-3(3.1.4), by adding an exception that allowed Group R-4 occupancies with an approved fire alarm system to not be required to install an automatic fire sprinkler system under certain conditions.

     

    Summary of the rule or change:

    A summary of the proposed amendment to Subsection R710-3-3(3.1.4) is as follows: Group R-4 occupancies that do not exceed 4,500 gross square feet in size and do not have more than 16 residents are not required to install an automatic fire sprinkler system if the facility has an approved interconnected fire alarm system throughout. This exception has been in Rule R710-9 for several years and the Board felt it also needed to be installed in the rule it specifically impacts.

     

    State statutory or constitutional authorization for this rule:

    Section 53-7-204

     

    Anticipated cost or savings to:

    the state budget:

    There is no aggregate anticipated cost or savings to the state budget because this proposed amendment does not affect the state budget. The proposed change has been in use for a number of years and this is a clarification by adding the existing rule to the rule it specifically impacts.

     

    local governments:

    There is no aggregate anticipated cost or savings to local government because this proposed amendment does not affect local government. The proposed change has been effect for a number of years and this is a clarification by adding the existing rule to the rule it specifically impacts.

     

    other persons:

    There is no aggregate anticipated cost or savings to other persons because this proposed amendment does not affect other persons. This proposed amendment has been in effect for several years in the general Rule R710-9 and the Board wished to have it placed in this rule to make sure it wouldn't be missed if the specific rule was only used by the Assisted Living Facility owner.

     

    Compliance costs for affected persons:

    There is no compliance cost for affected persons with the enactment of this rule amendment. Those affected by this rule amendment are associated with the Department of Human Services and have been using this rule amendment allowance for several years.

     

    Comments by the department head on the fiscal impact the rule may have on businesses:

    There is no fiscal impact on businesses for the enactment of this rule amendment. Robert L. Flowers, Commissioner

     

    The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:

    Public Safety
    Fire Marshal
    5272 S COLLEGE DR
    MURRAY UT 84123-2611

     

    Direct questions regarding this rule to:

    Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at bhallada@utah.gov

     

    Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:

    05/15/2006

     

    This rule may become effective on:

    05/16/2006

     

    Authorized by:

    Ron L. Morris, Utah State Fire Marshal

     

     

    RULE TEXT

    R710. Public Safety, Fire Marshal.

    R710-3. Assisted Living Facilities.

    R710-3-3. Amendments and Additions.

    3.1 General Requirements

    3.1.1 All facilities shall be inspected annually and obtain a certificate of fire clearance signed by the AHJ.

    3.1.2 All facility administrators shall develop emergency plans and preparedness as required in IFC, Chapter 4.

    3.1.3 IFC, Chapter 9, Sections 907.3.1.2 and 907.3.1.8 is deleted.

    3.1.4 IFC, Chapter 9, Section 903.2.7 is amended to add the following: Exception: Group R-4 fire areas not more than 4500 gross square feet and not containing more than 16 residents, provided the building is equipped throughout with an approved fire alarm system that is interconnected and receives its primary power from the building wiring and a commercial power system. This Exception does not apply to Type II Limited Capacity Assisted Living Facilities.

    3.2 Type I Assisted Living Facilities

    3.2.1 Type I Limited Capacity Assisted Living Facilities shall be constructed in accordance with IBC, Residential Group R-3, and maintained in accordance with the IBC and IFC.

    3.2.2 Type I Limited Capacity Assisted Living Facility required exits shall not be secured with dead bolts, chains, or hasps. Deadbolts that are interconnected with the latch, and provide simultaneous retraction of both the deadbolt and the latch, by the turning of the latch, is permitted.

    3.2.3 Residents in Type I Limited Capacity Assisted Living Facilities shall be housed on the first story only, unless an approved outside exit leading to the ground level is provided from any upper or lower level. Split entry/split level type homes in which stairs to the lower and upper level are equal or nearly equal, may have residents housed on both levels when approved by the AHJ.

    3.2.4 In Type I Limited Capacity Assisted Living Facilities, resident rooms on the ground level, shall have escape or rescue windows as required in IFC, Chapter 10, Section 1025.

    3.2.5 In Type I Limited Capacity Assisted Living Facilities an approved independent smoke detector shall be installed and maintained by location as required in IFC, Chapter 9, Section 907.2.10.1.2.

    3.2.6 Type I Small Assisted Living Facilities shall be constructed in accordance with IBC, Residential Group R-4, and maintained in accordance with the IBC and IFC.

    3.2.7 Type I Small Assisted Living Facility required exits shall not be secured with dead bolts, chains, or hasps. Deadbolts that are interconnected with the latch, and provide simultaneous retraction of both the deadbolt and the latch, by the turning of the latch, is permitted.

    3.2.8 Type I Large Assisted Living Facilities shall be constructed in accordance with IBC, Institutional Group I-1, and maintained in accordance with the IBC and IFC.

    3.2.8.1 An automatic fire sprinkler system shall be provided throughout buildings classified as Group I. Listed quick response or residential sprinkler heads shall be installed in patient or resident sleeping areas.

    3.2.9 In a Type I Assisted Living Facility, non-ambulatory persons are permitted after receiving approval for a variance from the Utah Department of Health as allowed in Utah Administrative Code, R432-2-18.

    3.3 Type II Assisted Living Facilities

    3.3.1 Type II Limited Capacity Assisted Living Facilities shall be constructed in accordance with IBC, Residential Group R-4, and maintained in accordance with the IBC and IFC.

    3.3.2 Type II Limited Capacity Assisted Living Facilities shall have an approved automatic fire extinguishing system installed in compliance with the IBC and IFC, or provide a staff to a resident ratio of one to one on a 24 hour basis.

    3.3.3 Type II Small Assisted Living Facilities shall be constructed in accordance with IBC, Institutional Group I-1, and maintained in accordance with the IBC and IFC.

    3.3.3.1 An automatic fire sprinkler system shall be provided throughout buildings classified as Group I. Listed quick response or residential sprinkler heads shall be installed in patient or resident sleeping areas.

    3.3.4 Type II Small Assisted Living Facilities shall have a minimum corridor width of six feet.

    3.3.4.1 Type II Small Assisted Living Facilities licensed before November 16, 2004, shall have a minimum corridor width of six feet or a path of egress that is acceptable to the AHJ.

    3.3.5 Type II Large Assisted Living Facilities shall be constructed in accordance with IBC, Institutional Group I-2, and maintained in accordance with the IBC and IFC.

    3.3.5.1 An automatic fire sprinkler system shall be provided throughout buildings classified as Group I. Listed quick response or residential sprinkler heads shall be installed in patient or resident sleeping areas.

    3.3.6 In Type II Assisted Living Facilities, where the clinical needs of the patients require specialized security, approved access controlled egress doors may be installed when all of the following are met:

    3.3.6.1 The controlled egress doors shall unlock upon activation of the automatic fire sprinkler system or the automatic fire detection system.

    3.3.6.2 The facility staff can unlock the controlled egress doors by either sensor or keypad.

    3.3.6.3 The controlled egress doors shall unlock upon loss of power.

    3.3.7 In Type II Assisted Living Facilities, where the clinical needs of the patients require approved, listed delayed egress locks, they shall be installed on doors as allowed in IBC, Section 1008.1.8.6. Section 1008.1.8.6(3) is deleted.

    3.3.8 In a Type II Assisted Living Facility, non-ambulatory persons are permitted after receiving approval for a variance from the Utah Department of Health as allowed in Utah Administrative Code, R432-2-18.

    3.4 Residential Treatment Assisted Living Facilities

    3.4.1 Residential Treatment Limited Capacity Assisted Living Facility shall be constructed in accordance with IBC, Residential Group R-3, and maintained in accordance with the IBC and IFC.

    3.4.2 Residential Treatment Limited Capacity Assisted Living Facility required exits shall not be secured with dead bolts, chains, or hasps. Deadbolts that are interconnected with the latch, and provide simultaneous retraction of both the deadbolt and the latch, by the turning of the latch, is permitted.

    3.4.3 Residents in Residential Treatment Limited Capacity Assisted Living Facilities shall be housed on the first story only, unless an approved outside exit leading to the ground level is provided from any upper or lower level. Split entry/split level type homes in which stairs to the lower and upper level are equal or nearly equal, may have residents housed on both levels when approved by the AHJ.

    3.4.4 In Residential Treatment Limited Capacity Assisted Living Facilities, resident rooms on the ground level, shall have escape or rescue windows as required in IBC, Chapter 10, Section 1025.

    3.4.5 In Residential Treatment Limited Capacity Assisted Living Facilities an approved independent smoke detector shall be installed and maintained by location as required in IFC, Chapter 9, Section 907.2.10.1.2.

    3.4.6 Residential Treatment Small Assisted Living Facilities shall be constructed in accordance with IBC, Residential Group R-4, and maintained in accordance with the IBC and IFC.

    3.4.7 Residential Treatment Small Assisted Living Facility required exits shall not be secured with dead bolts, chains, or hasps. Deadbolts that are interconnected with the latch, and provide simultaneous retraction of both the deadbolt and the latch, by the turning of the latch, is permitted.

    3.4.8 Residential Treatment Large Assisted Living Facilities shall be constructed in accordance with IBC, Institutional Group I-1, and maintained in accordance with the IBC and IFC.

    3.4.8.1 An automatic fire sprinkler system shall be provided throughout buildings classified as Group I. Listed quick response or residential sprinkler heads shall be installed in patient or resident sleeping areas.

    3.4.9 In a Residential Treatment Assisted Living Facility, non-ambulatory persons are permitted after meeting the requirements listed in Utah Administrative Code, R501-2-11, and receiving approval from the Office of Licensing, Utah Department of Human Services.

     

    KEY: assisted living facilities

    Date of Enactment or Last Substantive Amendment: [March 4, 2005]May 16, 2006

    Notice of Continuation: June 19, 2002

    Authorizing, and Implemented or Interpreted Law: 53-7-204

     

     

     

     

Document Information

Effective Date:
5/16/2006
Publication Date:
04/15/2006
Filed Date:
03/29/2006
Agencies:
Public Safety,Fire Marshal
Rulemaking Authority:

Section 53-7-204

 

Authorized By:
Ron L. Morris, Utah State Fire Marshal
DAR File No.:
28578
Related Chapter/Rule NO.: (1)
R710-3-3. Amendments and Additions.