DAR File No.: 34244
Filed: 03/10/2011 04:27:50 PMRULE ANALYSIS
Purpose of the rule or reason for the change:
The rule amendment has been modified in response to written comments received from the public.
Summary of the rule or change:
Minor changes have been made to the proposed rule amendment in response to comments received. (DAR NOTE: This change in proposed rule has been filed to make additional changes to a proposed amendment that was published in the December 15, 2010, issue of the Utah State Bulletin, on page 8. Underlining in the rule below indicates text that has been added since the publication of the proposed rule mentioned above; strike-out indicates text that has been deleted. You must view the change in proposed rule and the proposed amendment together to understand all of the changes that will be enforceable should the agency make this rule effective.)
State statutory or constitutional authorization for this rule:
- Section 1-4-104
Anticipated cost or savings to:
the state budget:
There is no change from the original rule filing. (No significant cost or savings)
local governments:
There is no change from the original rule filing. (No significant cost or savings)
small businesses:
There is no change from the original rule filing. (No significant cost or savings)
persons other than small businesses, businesses, or local governmental entities:
There is no change from the original rule filing. (No significant cost or savings)
Compliance costs for affected persons:
There is no change from the original rule filing. (No significant cost or savings)
Comments by the department head on the fiscal impact the rule may have on businesses:
The changes in the proposed rule amendment will help drinking water systems who wish to revise or update their disinfection practices to one of the emerging disinfection treatment technologies. There is no change in cost impact from the original rule filing to small businesses, businesses, local government entities, or the regulated community. (No significant cost or savings.)
Amanda Smith, Executive Director
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:
Environmental Quality
Drinking Water
195 N 1950 W
SALT LAKE CITY, UT 84116-3085Direct questions regarding this rule to:
- Ying-Ying Macauley at the above address, by phone at 801-536-4188, by FAX at 801-536-4211, or by Internet E-mail at ymacauley@utah.gov
- Bob Hart at the above address, by phone at 801-536-0054, by FAX at 801-536-4211, or by Internet E-mail at bhart@utah.gov
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:
05/02/2011
This rule may become effective on:
05/09/2011
Authorized by:
Ken Bousfield, Director
RULE TEXT
R309. Environmental Quality, Drinking Water.
R309-520. Facility Design and Operation: Disinfection.
. . . . . . .
R309-520-4. Primary Disinfectants.
Primary disinfection is the means to provide adequate levels of inactivation of pathogenic micro organisms within the treatment process. The effectiveness of chemical disinfectants is measured as a function of the concentration and time of contact, a "CT" value in units such as mg/L-min. The effectiveness of UV disinfection is determined through validation testing of[
the same UV reactor design as proposed] each model and specific configuration of UV reactor proposed in the design, as described in R309-520-8.Only four disinfectants: chlorine (i.e., gas, hypochlorite solution, and hypochlorite tablets), ozone, ultraviolet light, and chlorine dioxide are approved herein as allowable primary disinfectants of drinking water.
. . . . . . .
R309-520-6. General.
(1) Continuous Disinfection.
Continuous disinfection is required of all ground water sources that do not otherwise continuously meet standards of bacteriologic quality. Intermittent or batch disinfection, commonly used for disinfecting new water tanks, waterlines, well casings, etc., is not acceptable for ongoing drinking water delivery service. Surface water sources, and ground water sources under direct influence (UDI) of surface water, shall be disinfected as a part of the treatment requirements for conventional surface water treatment or alternative surface water treatment.
Disinfection is not an acceptable remedy to inadequate drinking water system facilities. Systems that practice source disinfection, and whose sources are exclusively ground water sources, as defined in R309-505-8, shall meet the requirements of R309-105-10(1), Chemical Addition.
(2) ANSI/NSF Standard 60 Certification.
All chemicals, including chlorine (i.e., gas, hypochlorite solution, hypochlorite tablets, granules, and powder), chloramines, and chemicals used to generate chlorine dioxide, added to drinking water supplied by a public water system shall be certified as complying with ANSI/NSF Standard 60, Drinking Water Treatment Chemicals.
(3) Appropriate Use of Primary and Secondary Disinfectants.
Surface water, or groundwater under the direct influence of surface water, shall be filtered and disinfected.
Only ground water not under the influence of surface water can be adequately disinfected with primary disinfectants, or primary and secondary disinfectants, alone. Surface waters, as well as ground water under the direct influence of surface water, require conventional surface water treatment or alternative surface water treatment methods.
(4) Required Disinfectant Dose and Contact Time.
Minimum cyst and virus reductions for that approved primary chemical disinfectants must achieve are specified in R309-200-5(7)(a), Disinfection, and reiterated in R309-200-7(2), namely 4-log virus removal or inactivation, 3-log Giardia lamblia cyst removal or inactivation, and 2-log Cryptosporidium removal or inactivation for water sources in bin 1 classification per R309-215-15(11)(c). Minimum doses and contact times for primary chemical disinfectants are standardized as "CT" values as defined in R309-110-4, Definitions.
(5) Site Selection.
Disinfection installations shall be sited to permit convenient year-round access. These installations shall initially be sited with due consideration of possible danger to nearby population and of possible jeopardy from seismic fault zones.
. . . . . . .
R309-520-8. Ultraviolet Light.
(1) General Requirements.
This rule shall apply to the public drinking water systems that use ultraviolet (UV) disinfection for inactivation of Cryptosporidium, Giardia, and virus. The Executive Secretary may reduce the requirements of [
validation testing,] monitoring and reporting on a case by case basis for the water systems that use UV as ancillary means of disinfection and do not claim credit for UV disinfection or [the water systems with UV facility of limited capacity]for water systems using UV without a SCADA system and treating less than 30 gallons per minute.Terminology used in this rule is based on the definitions in the EPA Ultraviolet Disinfection Guidance Manual for the Final Long Term 2 Enhanced Surface Water Treatment Rule (2006 Final UVDGM).
(a) Water systems using surface water or ground water under the influence of surface water shall not use UV as the sole means of disinfection. For these types of water systems, at least one alternative primary disinfectant must be used for virus disinfection, and a secondary disinfectant shall be provided to maintain a disinfectant residual in the distribution system.
(b) The following requirements apply to the water systems that wish to receive credit for UV disinfection:
(i) The water system shall submit a UV plan which clearly identifies the dose monitoring strategy, such as the UV intensity setpoint approach, the calculated dose approach or an alternative approach.
(ii) The water system shall identify the goals for the UV facility as part of a comprehensive disinfection strategy, including target pathogens, target log inactivation, and corresponding required UV dose per Table 215-5 in R309-215-15(19)(d).
(iii) The water system shall submit a UV reactor validation report in accordance with R309-520-8(2), to the Executive Secretary for review prior to obtaining approval for installation of UV facility.
(iv) The water system must demonstrate that the reactor is delivering the required UV dose using a validated dose monitoring system and continue to comply with the monitoring and reporting requirements specified in R309-215-15(19) and (20).
(2) Validation Testing.
[
Validation testing must conform to the guidelines in Chapter 5 Validation of UV Reactors of the EPA Ultraviolet Disinfection Guidance Manual for the Final Long Term 2 Enhanced Surface Water Treatment Rule (2006 Final UVDGM).] The Executive Secretary may accept a validation report that was conducted based on the 2003 draft UV Disinfection Guidance Manual on a case-by-case basis.
(a) [
Each type]Each model and specific configuration of UV reactor must undergo off-site, full-scale validation testing by an independent third party test facility prior to being approved for use. The validation testing shall be conducted in qualified test facilities that are deemed acceptable by NSF, EPA, or the Executive Secretary.(b) Validation testing results shall provide data, including calculations and tables or graphical plots, on dose delivery by the UV reactor under design conditions of flow rate, UV transmittance (UVT), UV intensity, lamp status, power ballast setting, as well as consideration of lamp aging and lamp fouling. The validation report shall demonstrate that the monitoring algorithm is valid over the range expected with the application. The data is used to define the dose monitoring algorithm for the UV reactor and the operating conditions that can be monitored by a utility to ensure that the UV dose required for a given pathogen inactivation credit is delivered.
(c) The UV reactor validation report shall include:
(i) Description of the reactor and validation test set-up, including general arrangement and layout drawings of the reactor and validation test piping arrangement.
(ii) Description of the methods used to empirically validate the reactor.
(iii) Description of the dose monitoring equation for the reactor to achieve the target pathogen inactivation credit and related graphical plots showing how the equation was derived from measured doses obtained through validation testing under varying test conditions.
(iv) Range of validated conditions for flow, UVT, UV dose, and lamp status.
(v) Description and rationale for selecting the challenge organism used in validation testing, and analysis to define operating dose for pathogen inactivation credit.
(vi) Tabulated data, analysis, and Quality assurance/quality control (QA/QC) measures during validation testing.
(vii) A licensed professional engineer's third party oversight certification indicating that the testing and data analyses in the validation report are conducted in a technically sound manner and without bias.
(viii) The validation report shall be companied with completed Checklists 5.1 through 5.5 included in the EPA Ultraviolet Disinfection Guidance Manual for the Final Long Term 2 Enhanced Surface Water Treatment Rule (2006 Final UVDGM).
(3) Design Criteria
(a) A water system considering UV disinfection shall gather sufficient water quality data prior to design. The water samples shall be representative of the source water to be treated by the UV facility. Frequent testing may be required if significant variation or seasonal trending in water quality is expected.
(b) The following water quality parameters should be considered in UV facility planning:
(i) UV Transmittance or UV Absorbance
(ii) Calcium
(iii) Alkalinity
(iv) Hardness
(v) Iron
(vi) Manganese
(vii) Turbidity
(viii) pH
(ix) Oxidation-Reduction Potential (ORP)
(x) Particle content and algae
(c) The design flow rate and UVT used to size the UV system shall be selected to provide the required dose at least 95 percent of the time, accounting for seasonal variations of flow and UVT combinations. Specifying a matrix of flow and UVT conditions for the UV reactors may be necessary.
(d) The water system may consider increasing the delivered dose beyond the required UV dose listed in Table 215-5 in R309-215-15(19)(d) to provide flexibility and conservatism.
(e) UV reactor inlet and outlet configurations shall meet the validated hydraulic distribution of flow conditions or be more hydraulically conservative. This can be achieved using one of the following approaches:
(i) The inlet and outlet configuration shall meet one of the conditions specified in Section 3.6.2 of the 2006 Final UVDGM.
(ii) Computational fluid dynamics (CFD)-based modeling may be used to demonstrate that the given conditions of inlet and outlet piping with the UV installation provides equal or greater dose delivery. The CFD modeling shall be conducted at the minimum and maximum values of the validated range of flow, UVT, and lamp status.
(f) The UV disinfection system shall be capable of applying the required design dose with a failed or out-of-service reactor. The design shall account for an on-line backup UV reactor or an operating scheme to apply the design dose with one reactor out of service.
(g) It shall be possible to isolate each reactor for maintenance.
(h) Signals and alarms shall be provided for the operation of the UV facility for the parameters necessary for dose monitoring algorithm, such as low UV dose, high flow rate, low UVT, UVT monitoring failure, UV sensor failure, off specification event, Ground Fault Interrupt (GFI), high water temperature, and low water level.
(i) All materials used in constructing or coating the UV reactors that come in contact with water shall be certified NSF Standard 61 - Drinking Water System Components - Health Effects.
(j) Any chemicals used in the cleaning of the UV reactor components in contact with the drinking water such as quartz sleeves shall be certified as meeting the ANSI/NSF Standard 60 - Drinking Water Treatment Chemicals - Health Effects.
(k) A flow or time delay shall be provided to permit a sufficient time for tube warm-up, per manufacturer recommendations, before water flows from the unit upon start up. The flow or time delay shall be included in the design so they do not result in excessive off specification conditions.
(l) To ensure a continuous supply of power, a backup power supply of sufficient capacity shall be provided for the UV disinfection system. If power quality problems, such as frequent power interruptions or brownouts, or remote location with unknown power quality, is anticipated, power conditioning equipment, such as uninterruptible power supply (UPS), shall be included in the design.
(m) The design shall include a redundant disinfection mechanism that will apply an approved primary disinfectant to achieve the CT or log removal/inactivation required for compliance if a UV facility is off specification or offline within a maximum response time of 15 minutes. One example of such response is to shut down the off- specification UV train and either bring a parallel UV train on line or initiate a back-up primary disinfection system within 15 minutes, so the continuous duration of an off- specification event is limited to no more than 15 minutes.
(n) UV disinfection units rated at 30 gallons per minute or less shall be certified as meeting the ANSI/NSF Standard 55, Class A , or other equivalent or more stringent validation or certification standards that are deemed acceptable by the Executive Secretary.
(o) The dose monitoring approach used for UV facility must be reviewed and accepted by the Executive Secretary. Typically the calculated dose approach is suitable for large systems or systems with significant flow variation, and the UV intensity setpoint approach is for small systems or systems with fixed flow rate. The dose monitoring approaches need to be consistent with the guidelines stated in the 2006 Final UVDGM.
(p) If Programmable Logic Controller (PLC) or SCADA interface is used for UV reactor's process control, the programming shall be in accordance with the validated dose monitoring algorithm and the validated conditions. The algorithm shall use inputs of flow, UV intensity sensor readings, lamps status, and/or UVT equal to or more conservative than values measured during the operation of the UV system. If the measured UVT is above the validated range, the maximum validated UVT shall be used as the input to the dose algorithm. If the measured flow rate is below the validated range, the minimum validated flow rate shall be used as the input to the dose algorithm. If the dose algorithm uses relative lamp output determined from the UV intensity sensor readings as an input, the relative lamp output should be based on the measured UVT, even if it exceeds the maximum validated UVT.
(q) The UV reactor's PLC or microprocessor shall be programmed to record off specification events for the following conditions:
(i) Delivered UV dose less than the required dose,
(ii) Flow greater than the validated range,
(iii) UVT less than the validated range,
(iv) Lamp status outside the validated range,
(v) Failure of UV sensors, flow meters, or on-line UVT monitors used in the dose calculation. Laboratory measurements of UVT may be used temporarily in the program until the on-line UVT monitor is repaired.
(4) Operation and Maintenance
The operation and maintenance tasks and the frequency of performing them can be specific to the UV equipment installed. The water systems with approved UV installations should follow the manufacturer's recommendation or the operation and maintenance guidelines stated in Section 6.2 through 6.5 of the 2006 Final UVDGM.
(a) Startup testing.
(i) The UV reactor manufacturer must provide a site-specific operation and maintenance manual, which shall include the procedure for starting up and shutting down the UV treatment system.
(ii) Provide schedules and performance standards for start-up testing and initial operation. Schedules shall include anticipated start-up date and proposed testing duration. Performance standards should reference applicable regulations and specific equipment capabilities.
(iii) Operators shall receive site-specific training on the operation of the UV disinfection system.
(b) An incident plan shall be developed to address lamp breakage and release of mercury, response to alarms, power supply interruptions, activation of standby equipment, failure of systems, etc.
(c) To verify that the UV reactors are operated within the validated limits, selected parameters should be monitored. The routine operation and maintenance shall include the monitoring and calibration requirements listed in R309-215-15(19) and (20) and are in accordance with the monitoring and reporting protocol approved by the Executive Secretary. For very small UV systems, the Executive Secretary may consider granting exception to allow reduced monitoring and reporting on a case-by-case basis.
. . . . . . .
KEY: drinking water, primary disinfectants, secondary disinfectants, operation and maintenance
Date of Enactment or Last Substantive Amendment: 2011
Notice of Continuation: March 22, 2010
Authorizing, and Implemented or Interpreted Law: 19-4-104
Document Information
- Effective Date:
- 5/9/2011
- Publication Date:
- 04/01/2011
- Filed Date:
- 03/10/2011
- Agencies:
- Environmental Quality,Drinking Water
- Rulemaking Authority:
Section 1-4-104
- Authorized By:
- Ken Bousfield, Director
- DAR File No.:
- 34244
- Related Chapter/Rule NO.: (1)
- R309-520. Facility Design and Operation: Disinfection.