No. 32445 (Amendment): R309-500. Facility Design and Operation: Plan Review,Operation and Maintenance Requirements
DAR File No.: 32445
Filed: 03/16/2009, 02:44
Received by: NLRULE ANALYSIS
Purpose of the rule or reason for the change:
The change in Section R309-500-5 is to allow upgrading pipelines or tapping with corporation stops be considered as on-going operation and maintenance procedures. The change in Subsection R309-500-6(3)(b) is to require previously approved standard installation drawings for waiving plan submittal.
Summary of the rule or change:
The change in Section R309-500-5 is to allow upgrading existing deteriorated pipelines or tapping with corporation stops be considered as on-going operation and maintenance procedures and be exempt from plan review requirements. The changes in Subsection R309-500-6(3)(b) are to require previously approved standard installation drawings for waiving plan submittal in addition to the system designated professional engineer responsible for the entire water system.
State statutory or constitutional authorization for this rule:
Section 19-4-104
Anticipated cost or savings to:
the state budget:
Little to none--This amendment allows upgrading pipelines to be exempt from plan review requirements and specifies the requirements of obtaining plan submittal waiver. It will not increase workload or require additional personnel or other funds from the state budget.
local governments:
Little to none--This amendment allows upgrading pipelines to be exempt from plan review requirements and specifies the requirements of obtaining plan submittal waiver. It will not increase workload or require additional personnel or other funds from local government.
small businesses and persons other than businesses:
Little to none--This amendment allows upgrading pipelines to be exempt from plan review requirements and specifies the requirements of obtaining plan submittal waiver. It will not increase workload or require additional personnel or other funds from small businesses.
Compliance costs for affected persons:
Little to none--This amendment allows upgrading pipelines to be exempt from plan review requirements and specifies the requirements of obtaining plan submittal waiver. It will not increase workload or require additional personnel or other funds from consumers.
Comments by the department head on the fiscal impact the rule may have on businesses:
The department agrees that the proposed changes to this rule will have little to no detrimental impact on existing water systems or to new public water systems. William Sinclair, Acting Executive Director
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:
Environmental Quality
Drinking Water
150 N 1950 W
SALT LAKE CITY UT 84116-3085Direct questions regarding this rule to:
Ying-Ying Macauley or Bob Hart at the above address, by phone at 801-536-4188 or 801-536-0054, by FAX at 801-536-4211 or 801-536-4211, or by Internet E-mail at ymacauley@utah.gov or bhart@utah.gov
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:
05/01/2009
This rule may become effective on:
05/08/2009
Authorized by:
Ken Bousfield, Director
RULE TEXT
R309. Environmental Quality, Drinking Water.
R309-500. Facility Design and Operation: Plan Review, Operation and Maintenance Requirements.
R309-500-5. Public Drinking Water Project.
(1) Definition.
A public drinking water project, requiring the submittal of a project notification form along with plans and specifications, is any of the following:
(a) The construction of any facility for a proposed drinking water system (see 19-4-106(3) of the Utah Code or R309-500-4(1) above describing the authority of the Executive Secretary).
(b) Any addition to, or modification of, the facilities of an existing public drinking water system which may affect the quality or quantity of water delivered.
(c) Any activity, other than on-going operation and maintenance procedures, which may affect the quality or quantity of water delivered by an existing public drinking water system. Such activities include:
(i) the interior re-coating or re-lining of any raw or drinking water storage tank, or water storage chamber within any treatment facility,
(ii) the "in-situ" re-lining of any pipeline,
(iii) a change or addition of any primary coagulant water treatment chemical (excluding filter, flocculent or coagulant aids) when the proposed chemical does not appear on a list of chemicals pre-approved by the Executive Secretary for a specific treatment facility, and
(iv) the re-development of any spring or well source or replacement of a well pump with one of different capacity.
(2) On-going Operation and Maintenance Procedures.
On-going operation and maintenance procedures are not considered public drinking water projects and, accordingly, are not subject to the project notification, plan approval and operating permit requirements of this rule. However, these activities shall be carried out in accordance with all operation and maintenance requirements contained in R309-500 through R309-550 and specifically the disinfection, flushing and bacteriological sampling and testing requirements of ANSI/AWWA C651-05 for pipelines, ANSI/AWWA C652-02 for storage facilities, and ANSI/AWWA C654-03 for wells before they are placed back into service. The following activities are considered to be on-going operation and maintenance procedures:
(a) pipeline leak repair,
(b) replacement of existing deteriorated pipeline where the new pipeline segment is the same size as the old pipelineor the new segment is upgraded to meet the minimum pipeline sizes required by R309-550-5(4) or larger sizes as determined by a hydraulic analysis in accordance with R309-550-5(3),
(c) tapping existing water mains with corporation stops so as to make connection to new service laterals to individual structures,
(d)[
(c)] distribution pipeline additions where the pipeline size is the same as the main supplying the addition or the pipeline addition meets the minimum pipeline sizes required by R309-550-5(4) or larger sizes as determined by a hydraulic analysis in accordance with R309-550-5(3), the length is less than 500 feet and contiguous segments of new pipe total less than 1000 feet in any fiscal year,(e)[
(d)] entry into a drinking water storage facility for the purposes of inspection, cleaning and maintenance, and(f)[
(e)] replacement of equipment or pipeline appurtenances with the same type, size and rated capacity (fire hydrants, valves, pressure regulators, meters, service laterals, chemical feeders and booster pumps including deep well pumps).R309-500-6. Plan Approval Procedure.
(1) Project Notification.
The Division shall be notified prior to the construction of any "public drinking water project" as defined in R309-500-5(1) above. The notification may be prior to or simultaneous with submission of construction plans and specifications as required by R309-500-6(2) below. Notification shall be made by the management of the regulated public water system on a form provided by the Division. Information required by this form shall be determined by the Division and may include:
(a) whether the project is for a new or existing public drinking water system,
(b) the professional engineer, registered in the State of Utah, designing the project and his/her experience designing public drinking water projects within the state,
(c) the individual(s) who will be inspecting the project during construction and whether such inspection will be full-time or part time,
(d) whether required approvals or permits from other governmental agencies (e.g. local planning commissions, building inspectors, Utah Division of Water Rights)are awaiting approval by the Executive Secretary, the agency's name and contact person,
(e) the fire marshal, fire district or other entity having legal authority to specify requirements for fire suppression in the project area,
(f) for community and non-transient non-community public water systems or any public water system treating surface water, the name of the certified operator who is, or will be, in direct responsible charge of the water system,
(g) whether the water system has a registered professional engineer employed, appointed or designated as being directly responsible for the entire system design and his or her name and whether the system is requesting waiving of plan submittal under conditions of R309-500-6 (3),
(h) the anticipated construction schedule, and
(i) a description of the type of legal entity responsible for the water system (i.e. corporation, political subdivision, mutual ownership, individual ownership, etc.) and the status of the entity with respect to the rules of the Utah Public Service Commission.
(2) Pre-Construction Requirements.
All of the following shall be accomplished before construction of any public drinking water project commences:
(a) Contract documents, plans and specifications for a public drinking water project shall be submitted to the Division at least 30 days prior to the date on which action is desired unless the system is eligible for and has requested waiving of plan submittal. Any submittal shall include engineering reports, pipe network hydraulic analyses, water consumption data, supporting information, evidence of rights-of-way and reference to any previously submitted master plans pertinent to the project, along with a description of a program for keeping existing water works facilities in operation during construction so as to minimize interruption of service.
(b) Plans and specifications shall be prepared for every anticipated public water system project. The design utilized shall conform to the requirements of R309-500 through R309-550. Furthermore, the plans and specification shall be sufficiently detailed to assure that the project shall be properly constructed. Drawings shall be compatible with Division's document storage and microfilming practice. Drawings which are illegible or of unusual size shall not be accepted for review. Drawing size shall not exceed 30" x 42" nor be less than 8-1/2" x 11".
(c) The plans and specifications shall be stamped and signed by a licensed professional engineer in accordance with Section 58-22-602(2) of the Utah Code.
(d) Plans and specifications shall be reviewed for conformance with R309-500 through R309-550. No work shall commence on a public water system project until a plan approval has been issued by the Executive Secretary unless conditions outlined in R309-500-6(3) are met and waiving of plan submittal has been requested. If construction or the ordering of substantial equipment has not commenced within one year, a renewal of the Plan Approval shall be obtained prior to proceeding with construction.
(e) If, in the judgment of the Executive Secretary, alternate designs or specific solutions can protect the public health to the same or greater extent as achieved in R309-500 through R309-550, the Executive Secretary may grant an exception thereto (see the third paragraph of R309-500-4(1)).
(f) Novel equipment or treatment techniques may be developed which are not specifically addressed by these rules. These may be accepted by the Executive Secretary if it can be shown that:
(i) the technique will produce water meeting the requirements of R309-200 of these rules,
(ii) the Executive Secretary has determined that it will protect public health to the same extent provided by comparable treatment processes outlined in these rules, and
(iii) the Executive Secretary has determined the technique is as reliable as any comparable treatment process outlined is these rules.
(3) Waiving of Plan Submittal Requirement.
With identification of a professional engineer, as indicated below, on a project notification form the plan submittal requirement may be waived for certain projects. In these instances, in lieu of plans and specifications, a "certification of rule conformance" shall be submitted along with the additional information required for an operating permit (see R309-500-9), signed by the professional engineer identified to Executive Secretary in (b) or, if the system has not employed, appointed, or designated such, the registered professional engineer who prepared the items in (a). Projects eligible for this waiving of plan submittal are:
(a) distribution system improvements (excluding pressure reducing valve stations and in-line booster pump stations) which conform to a "master plan" previously reviewed and approved by the Executive Secretary and installed in accordance with the [
"]system's standard installation drawings,["] also previously reviewed and approved by the Executive Secretary, or(b) distribution system improvements consisting solely of pipelines and pipeline appurtenances (excluding pressure reducing valve stations and in-line booster pump stations);
(i) less than or equal to 4 inches in diameter in water systems (without fire hydrants) serving solely a residential population less than 3,300;
(ii) less than or equal to 8 inches in diameter in water systems (with fire hydrants) providing water for mixed use (commercial, industrial, agricultural and/or residential) to a population less than 3,300;
(iii) less than or equal to 12 inches in diameter in water systems(with fire hydrants) providing water for mixed use to a population between 3,300 and 50,000;
(iv) less than or equal to 16 inches in diameter in water systems (with fire hydrants) providing water for mixed use to a population greater than 50,000.
Additionally, the above systems in (b) shall employ, appoint or designate a registered professional engineer who is directly responsible for the entire public water system design and identify this individual to the Executive Secretary as well as have standard installation drawings previously reviewed and approved by the Division before being eligible for waiving of plan submittal requirements.
KEY: drinking water, plan review, operation and maintenance requirements, permits
Date of Enactment or Last Substantive Amendment: [
August 15, 2001]2009Notice of Continuation: April 2, 2007
Authorizing, and Implemented or Interpreted Law: 19-4-104
Document Information
- Effective Date:
- 5/8/2009
- Publication Date:
- 04/01/2009
- Filed Date:
- 03/16/2009
- Agencies:
- Environmental Quality,Drinking Water
- Rulemaking Authority:
Section 19-4-104
- Authorized By:
- Ken Bousfield, Director
- DAR File No.:
- 32445
- Related Chapter/Rule NO.: (1)
- R309-500. Facility Design and Operation: Plan Review, Operation and Maintenance Requirements.