No. 29645 (Amendment): R309-215. Monitoring and Water Quality: Treatment Plant Monitoring Requirements  

  • DAR File No.: 29645
    Filed: 03/14/2007, 10:47
    Received by: NL

    RULE ANALYSIS

    Purpose of the rule or reason for the change:

    This amendment is to correct references and to clarify recent changes to the rule in response to comments from Region 8 of the United States Environmental Protection Agency. The clarification is needed to retain state primacy.

    Summary of the rule or change:

    The amendment corrects rule references and adds language inadvertently left out of the recent rule amendment to adopt the Federal Long Term 1 and 2 Surface Water Treatment Rules. (DAR NOTE: The recent amendment was under DAR No. 29366 in the January 15, 2007, issue of the Bulletin, and was effective 03/06/2007.)

    State statutory or constitutional authorization for this rule:

    Sections 19-4-104 and 63-46b-4, and 40 CFR 141 and 142

    Anticipated cost or savings to:

    the state budget:

    There is no impact to the state budget as the changes simply clarify existing language.

    local governments:

    There is no impact to local government as the changes simply clarify existing language.

    other persons:

    There is no impact to other persons as the changes simply clarify existing language.

    Compliance costs for affected persons:

    There is no impact to the compliance costs for affected persons as the changes simply clarify existing language.

    Comments by the department head on the fiscal impact the rule may have on businesses:

    The department agrees with the comments in the cost and compliance summaries above. Dianne R. Nielson, Executive Director

    The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:

    Environmental Quality
    Drinking Water
    150 N 1950 W
    SALT LAKE CITY UT 84116-3085

    Direct questions regarding this rule to:

    Patti Fauver at the above address, by phone at 801-536-4196, by FAX at 801-536-4211, or by Internet E-mail at pfauver@utah.gov

    Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:

    05/01/2007

    This rule may become effective on:

    05/08/2007

    Authorized by:

    Ken Bousfield, Acting Director

    RULE TEXT

    R309. Environmental Quality, Drinking Water.

    R309-215. Monitoring and Water Quality: Treatment Plant Monitoring Requirements.

    R309-215-9. Turbidity Monitoring and Reporting.

    Public water systems utilizing surface water and ground water under the direct influence of surface water shall monitor for turbidity in accordance with this section. Small surface water systems serving a population less than 10,000 shall monitor in accordance with subsections (1), (2), (3), (5) and (6). Large surface water systems serving 10,000 or more population shall monitor in accordance with subsections (1), (2), (3), (4) and (6).

    (1) Routine Monitoring Requirements for Treatment Facilities utilizing surface water sources or ground water sources under the direct influence of surface water.

    (a) All public water systems which use a treatment technique to treat water obtained in whole or in part from surface water sources or ground water sources under the direct influence of surface water shall monitor for turbidity at the treatment plant's clearwell outlet. This monitoring shall be independent of the individual filter monitoring required by R309-525-15(4)(b)(vi) and R309-525-15(4)(c)(vii). Where the plant facility does not have an internal clearwell, the turbidity shall be monitored at the inlet to a finished water reservoir external to the plant provided such reservoir receives only water from the treatment plant and, furthermore, is located before any point of consumer connection to the water system. If such external reservoir does not exist, turbidity shall then be monitored at a location immediately downstream of the treatment plant filters.

    (b) All treatment plants, with the exception of those utilizing slow sand filtration and other conditions indicated in section (c) below, shall be equipped with continuous turbidity monitoring and recording equipment for which the direct responsible charge operator will validate the continuous measurements for accuracy in accordance with paragraph (d) below. These plants shall continuously record the finished water turbidity of the combined filter effluent as well as each individual filter. All systems shall be equipped to continuously monitor the turbidity at each filter unless the treatment plant is only equipped with two filters and the turbidity is measured at the combined filter effluent (CFE). If there is a failure in continuous monitoring equipment the system shall conduct grab sampling every 4 hours in lieu of continuous monitoring, but for no more than five working days following the failure of equipment. Systems serving less than 10,000 population shall have no more than 14 days to conduct grab samples in lieu of continuous monitoring in order to correct any failing equipment. All surface water systems shall monitor the turbidity results of individual filters at a frequency no greater than every 15 minutes.

     

    . . . . . . .

     

    (5) Additional reporting and recordkeeping requirements for surface water systems serving less than 10,000 population.

    In addition to the reporting and recordkeeping requirements sub-sections (1), (2) and (3) above, a surface water system that provides conventional filtration treatment or direct filtration shall report monthly to the Division the information specified in paragraphs (a) and (b) of this section. In addition to the reporting and recordkeeping requirements above, a public water system subject to the requirements of this subpart that provides filtration approved under R309-530-8 or R309-530-9 shall report monthly to the Division the information specified in paragraphs (a) of this section. The reporting in paragraph (a) of this section is in lieu of the reporting specified above.

    (a) Turbidity measurements, as required in R309-200-5(5)(a), shall be reported within 10 days after the end of each month the system serves water to the public. Information that shall be reported includes:

    (i) The total number of filtered water turbidity measurements taken during the month.

    (ii) The number and percentage of filtered water turbidity measurements taken during the month which are less than or equal to 0.3 NTU or those levels established under R309-200-5(5)(a)(ii).

    (iii) The date and value of any turbidity measurements taken during the month which exceed 1 NTU for systems using conventional filtration treatment or direct filtration, or which exceed the maximum level set by the Executive Secretary under R309-530-8 or R309-530-9.

    (b) Systems shall maintain the results of individual filter monitoring taken under R309-215-9(1)(b) for at least three years. Systems shall record the results of individual filter monitoring every 15 minutes. Systems shall report that they have conducted individual filter turbidity monitoring within 10 days after the end of each month the system serves water to the public. Systems shall report individual filter turbidity measurement results within 10 days after the end of each month the system serves water to the public only if measurements demonstrate one or more of the conditions in paragraphs (b)(i) through (iv) of this section. Systems that use lime softening may apply to the Executive Secretary for alternative exceedance levels for the levels specified in paragraphs (b)(i) through (iv) of this section if they can demonstrate that higher turbidity levels in individual filters are due to lime carryover only and not due to degraded filter performance.

    (i) For any individual filter (or CFE for systems with 2 filters that monitor CFE in lieu of individual filters) that has a measured turbidity level of greater than 1.0 NTU in two consecutive measurements taken 15 minutes apart, the system shall report the filter number(s), the corresponding date(s), the turbidity values which exceeded 1.0 NTU, and the cause (if known) for the exceedance(s), to the Executive Secretary by the 10th of the following month.

    (ii) If a system was required to report to the Executive Secretary for three months in a row and turbidity exceeded 1.0 NTU in two consecutive recordings taken 15 minutes apart at the same filter (or CFE for systems with 2 filters that monitor CFE in lieu of individual filters), the system shall conduct a self-assessment of the filter within 14 days of the day the filter exceeded 1.0 NTU in two consecutive measurements for the third straight month unless a CPE as specified in paragraph (iii) of this section was required. Systems with 2 filters that monitor CFE in lieu of individual filters must conduct a self assessment on both filters. The self-assessment must consist of at least the following components: assessment of filter performance; development of a filter profile; identification and prioritization of factors limiting filter performance; assessment of the applicability of corrections; and preparation of a filter self-assessment report. If a self-assessment is required, the date that it was triggered and the date that it was completed.

    (iii) If a system was required to report to the Executive Secretary for two months in a row and turbidity exceeded 2.0 NTU in two consecutive measurements taken 15 minutes apart at the same filter (or CFE for systems with 2 filters that monitor CFE in lieu of individual filters), the system shall arrange to have a comprehensive performance evaluation (CPE) conducted by the Division or a third party approved by the Executive Secretary no later than 60 days following the day the filter exceeded 2.0 NTU in two consecutive measurements for the second straight month. If a CPE is required, the system must report a CPE required and the date it was triggered. If a CPE has been completed by the Division or a third party approved by the Executive Secretary within the 12 prior months or the system and Division are jointly participating in an ongoing Comprehensive Technical Assistance (CTA) project at the system, a new CPE is not required. If conducted, a CPE must be completed and submitted to the Division no later than 120 days following the day the filter exceeded 2.0 NTU in two consecutive measurements for the second straight month.

    (6) Additional reporting requirements.

    (a) If at any time the turbidity exceeds 1 NTU in representative samples of filtered water in a system using conventional filtration treatment or direct filtration, the system shall inform the Division as soon as possible, but no later than the end of the next business day.

    (b) If at any time the turbidity in representative samples of filtered water exceeds the maximum level set by the Executive Secretary under R309-530-8 or R309-530-9 for filtration technologies other than conventional filtration treatment, direct filtration, slow sand filtration, or diatomaceous earth filtration, the system shall inform the Division as soon as possible, but no later than the end of the next business day.

     

    R309-215-15. Enhanced Treatment for Cryptosporidium (Federal Subpart W).

    (1) General requirements.

    (a) The rule requirements of this section establish or extend treatment technique requirements in lieu of maximum contaminant levels for Cryptosporidium. These requirements are in addition to requirements for filtration and disinfection in R309-200 and other parts of R309-215.

     

    . . . . . . .

     

    (2) Source Water Monitoring Requirements.

     

    . . . . . . .

     

    (d) Monitoring avoidance.

    (i) Filtered systems are not required to conduct source water monitoring under this sub-section if the system will provide a total of at least 5.5-log of treatment for Cryptosporidium, equivalent to meeting the treatment requirements of Bin 4 in R309-215-15(12).

    (ii) If a system chooses to provide the level of treatment in paragraph (d)(i) of this section rather than start source monitoring, the system must notify the Executive Secretary in writing no later than the date the system is otherwise required to submit a sampling schedule for monitoring under R309-215-15(3). Alternatively, a system may choose to stop sampling at any point after it has initiated monitoring if it notifies the Executive Secretary in writing that it will provide this level of treatment. Systems must install and[an] operate technologies to provide this level of treatment by the applicable compliance dates in R309-215-15(13).

    (e) Plants operating only part of the year. Systems with surface water plants that operate for only part of the year must conduct source water monitoring in accordance with this subpart, but with the following modifications:

    (i) Systems must sample their source water only during the months that the plant operates unless the Executive Secretary specifies another monitoring period based on plant operating practices.

    (ii) Systems with plants that operate less than six months per year and that monitor for Cryptosporidium must collect at least six Cryptosporidium samples per year during each of two years of monitoring. Samples must be evenly spaced throughout the period the plant operates.

    (f)(i) New sources. A system that begins using a new source of surface water or GWUDI after the system is required to begin monitoring under paragraph (c) of this section must monitor the new source on a schedule the Executive Secretary approves. Source water monitoring must meet the requirements of this sub-section. The system must also meet the bin classification and Cryptosporidium treatment requirements of R309-215-15(11) and (12) for the new source on a schedule the Executive Secretary approves.

    (ii) The requirements of R309-215-15(2)(f) apply to surface water systems that begin operation after the monitoring start date applicable to the system's size under paragraph (c) of this section.

    (iii) The system must begin a second round of source water monitoring no later than 6 years following initial bin classification under R309-215-15(11).

    (g) Failure to collect any source water sample required under this section in accordance with the sampling schedule, sampling location, analytical method, approved laboratory, and reporting requirements of R309-215-15(3) through R309-215-15(7) is a monitoring violation.

    (h) Grandfathering monitoring data. Systems may use (grandfather) monitoring data collected prior to the applicable monitoring start date in paragraph (c) of this section to meet the initial source water monitoring requirements in paragraph (a) of this section. Grandfathered data may substitute for an equivalent number of months at the end of the monitoring period. All data submitted under this paragraph must meet the requirements in R309-215-15(8).

    (3) Sampling schedules.

    (a) Systems required to conduct source water monitoring under R309-215-15(2) must submit a sampling schedule that specifies the calendar dates when the system will collect each required sample.

    (i) Systems must submit sampling schedules no later than 3 months prior to the applicable date listed in R309-215-15(2)(c) for each round of required monitoring.

    (ii) (A) Systems serving at least 10,000 people must submit their sampling schedule for the initial round of source water monitoring under R309-215-15(2)(a) to EPA electronically at https:// intranet.epa.gov/lt2/.

    (B) If a system is unable to submit the sampling schedule electronically, the system may use an alternative approach for submitting the sampling schedule that EPA approves.

    (iii) Systems serving fewer than 10,000 people must submit their sampling schedules for the initial round of source water monitoring R309-215-15(2)(a) to the Executive Secretary.

    (iv) Systems must submit sampling schedules for the second round of source water monitoring R309-215-15(2)(b) to the Executive Secretary.

    (v) If EPA or the Executive Secretary does not respond to a system regarding its sampling schedule, the system must sample at the reported schedule.

    (b) Systems must collect samples within two days before or two days after the dates indicated in their sampling schedule (i.e., within a five-day period around the schedule date) unless one of the conditions of paragraph (b)(i) or (ii)[(b)(1) or (2)] of this section applies.

    (i) If an extreme condition or situation exists that may pose danger to the sample collector, or that cannot be avoided and causes the system to be unable to sample in the scheduled five-day period, the system must sample as close to the scheduled date as is feasible unless the Executive Secretary approves an alternative sampling date. The system must submit an explanation for the delayed sampling date to the Executive Secretary concurrent with the shipment of the sample to the laboratory.

    (ii)(A) If a system is unable to report a valid analytical result for a scheduled sampling date due to equipment failure, loss of or damage to the sample, failure to comply with the analytical method requirements, including the quality control requirements in R309-215-15(5), or the failure of an approved laboratory to analyze the sample, then the system must collect a replacement sample.

    (B) The system must collect the replacement sample not later than 21 days after receiving information that an analytical result cannot be reported for the scheduled date unless the system demonstrates that collecting a replacement sample within this time frame is not feasible or the Executive Secretary approves an alternative resampling date. The system must submit an explanation for the delayed sampling date to the Executive Secretary concurrent with the shipment of the sample to the laboratory.

    (c) Systems that fail to meet the criteria of paragraph (b) of this section for any source water sample required under R309-215-15(2) must revise their sampling schedules to add dates for collecting all missed samples. Systems must submit the revised schedule to the Executive Secretary for approval prior to when the system begins collecting the missed samples.

    (4) Sampling locations.

    (a) Systems required to conduct source water monitoring under R309-215-15(2) must collect samples for each plant that treats a surface water or GWUDI source. Where multiple plants draw water from the same influent, such as the same pipe or intake, the Executive Secretary may approve one set of monitoring results to be used to satisfy the requirements of R309-215-15(2) for all plants.

    (b) (i) Systems must collect source water samples prior to chemical treatment, such as coagulants, oxidants and disinfectants, unless the system meets the condition of paragraph (b)(ii) of this section.

    (ii) The Executive Secretary may approve a system to collect a source water sample after chemical treatment. To grant this approval, the Executive Secretary must determine that collecting a sample prior to chemical treatment is not feasible for the system and that the chemical treatment is unlikely to have a significant adverse effect on the analysis of the sample.

    (c) Systems that recycle filter backwash water must collect source water samples prior to the point of filter backwash water addition.

    (d) Bank filtration.

    (i) Systems that receive Cryptosporidium treatment credit for bank filtration under R309-200-5(5)(a)(ii) must collect source water samples in the surface water prior to bank filtration.

    (ii) Systems that use bank filtration as pretreatment to a filtration plant must collect source water samples from the well (i.e., after bank filtration). Use of bank filtration during monitoring must be consistent with routine operational practice. Systems collecting samples after a bank filtration process may not receive treatment credit for the bank filtration under R309-215-15(16)(c).

    (e) Multiple sources. Systems with plants that use multiple water sources, including multiple surface water sources and blended surface water and ground water sources, must collect samples as specified in paragraph (e)(i) or (ii) of this section. The use of multiple sources during monitoring must be consistent with routine operational practice.

    (i) If a sampling tap is available where the sources are combined prior to treatment, systems must collect samples from the tap.

    (ii) If a sampling tap where the sources are combined prior to treatment is not available, systems must collect samples at each source near the intake on the same day and must follow either paragraph (e)(ii)(A) or (B) of this section for sample analysis.

    (A) Systems may composite samples from each source into one sample prior to analysis. The volume of sample from each source must be weighted according to the proportion of the source in the total plant flow at the time the sample is collected.

    (B) Systems may analyze samples from each source separately and calculate a weighted average of the analysis results for each sampling date. The weighted average must be calculated by multiplying the analysis result for each source by the fraction the source contributed to total plant flow at the time the sample was collected and then summing these values.

    (f) Additional Requirements. Systems must submit a description of their sampling location(s) to the Executive Secretary at the same time as the sampling schedule required under R309-215-15(3). This description must address the position of the sampling location in relation to the system's water source(s) and treatment processes, including pretreatment, points of chemical treatment, and filter backwash recycle. If the Executive Secretary does not respond to a system regarding sampling location(s), the system must sample at the reported location(s).

    (5) Analytical methods.

    (a) Cryptosporidium. Systems must analyze for Cryptosporidium using Method 1623: Cryptosporidium and Giardia in Water by Filtration/IMS/FA, 2005, United States Environmental Protection Agency, EPA-815-R-05-002 or Method 1622: Cryptosporidium in Water by Filtration/IMS/FA, 2005, United States Environmental Protection Agency, EPA-815-R-05-001, which are incorporated by reference. You may obtain a copy of these methods online from http:// www.epa.gov/safewater/disinfection/lt2 or from the United States Environmental Protection Agency, Office of Ground Water and Drinking Water, 1201 Constitution Ave., NW, Washington, DC 20460 (Telephone: 800-426-4791). You may inspect a copy at the Water Docket in the EPA Docket Center, 1301 Constitution Ave., NW, Washington, DC, (Telephone: 202-566-2426) or at the National Archives and Records Administration (NARA). For information on the availability of this material at NARA, call 202-741-6030, or go to: http://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. You may also obtain a copy of these methods by contacting the Division of Drinking Water at 801-536-4200.

    (i) Systems must analyze at least a 10 L sample or a packed pellet volume of at least 2 mL as generated by the methods listed in paragraph (a) of this section. Systems unable to process a 10 L sample must analyze as much sample volume as can be filtered by two filters approved by EPA for the methods listed in paragraph (a) of this section, up to a packed pellet volume of at least 2 mL.

    (ii) (A) Matrix spike (MS) samples, as required by the methods in paragraph (a) of this section, must be spiked and filtered by a laboratory approved for Cryptosporidium analysis under R309-215-15(6).

    (B) If the volume of the MS sample is greater than 10 L, the system may filter all but 10 L of the MS sample in the field, and ship the filtered sample and the remaining 10 L of source water to the laboratory. In this case, the laboratory must spike the remaining 10 L of water and filter it through the filter used to collect the balance of the sample in the field.

    (iii) Flow cytometer-counted spiking suspensions must be used for MS samples and ongoing precision and recovery (OPR) samples.

    (b) E. coli. Systems must use methods for enumeration of E. coli in source water approved in R309-200-4(3) and (4).

    (i) The time from sample collection to initiation of analysis may not exceed 30 hours unless the system meets the condition of paragraph (b)([2]ii) of this section.

    (ii) The Executive Secretary may approve on a case-by-case basis the holding of an E. coli sample for up to 48 hours between sample collection and initiation of analysis if the Executive Secretary determines that analyzing an E. coli sample within 30 hours is not feasible. E. coli samples held between 30 to 48 hours must be analyzed by the Colilert reagent version of Standard Method 9223B as listed in R309-200-4(3) and (4).

    (iii) Systems must maintain samples between 0 deg.C and 10 deg. C during storage and transit to the laboratory.

    (c) Turbidity. Systems must use methods for turbidity measurement approved in R309-200-4(3) and (4).

    (6) Approved laboratories.

    (a) Cryptosporidium. Systems must have Cryptosporidium samples analyzed by a laboratory that is approved under EPA's Laboratory Quality Assurance Evaluation Program for Analysis of Cryptosporidium in Water or a laboratory that has been certified for Cryptosporidium analysis by an equivalent State laboratory certification program.

    (b) E. coli. Any laboratory certified by the EPA, the National Environmental Laboratory Accreditation Conference or the State for total coliform or fecal coliform analysis under R309-200-4(3) and (4) is approved for E. coli analysis under this subpart when the laboratory uses the same technique for E. coli that the laboratory uses for R309-200-4(3), (4) and in R444-14-4(1).[and (4).]

    (c) Turbidity. Measurements of turbidity must be made by a party approved by the State.

    (7) Reporting source water monitoring results.

    (a) Systems must report results from the source water monitoring required under R309-215-15(2) no later than 10 days after the end of the first month following the month when the sample is collected.

    (b) (i) All systems serving at least 10,000 people must report the results from the initial source water monitoring required under R309-215-15(2)(a) to EPA electronically at https:// intranet.epa.gov/lt2/.

    (ii) If a system is unable to report monitoring results electronically, the system may use an alternative approach for reporting monitoring results that EPA approves.

    (c) Systems serving fewer than 10,000 people must report results from the initial source water monitoring required under R309-215-15(2)(a) to the Executive Secretary.

    (d) All systems must report results from the second round of source water monitoring required under R309-215-15(2)(b) to the Executive Secretary.

    (e) Systems must report the applicable information in paragraphs (e)([1]i) and ([2]ii) of this section for the source water monitoring required under R309-215-15(2).

    (i) Systems must report the following data elements for each Cryptosporidium analysis:

    (A) PWS ID.

    (B) Facility ID.

    (C) Sample collection date.

    (D) Sample type (field or matrix spike).

    (E) Sample volume filtered (L), to nearest 1/4 L.

    (F) Was 100% of filtered volume examined.

    (G) [and the ]Number of oocysts counted.

    (H[G]) For matrix spike samples, systems must also report the sample volume spiked and estimated number of oocysts spiked. These data are not required for field samples.

    (I[H]) For samples in which less than 10 L is filtered or less than 100% of the sample volume is examined, systems must also report the number of filters used and the packed pellet volume.

    (J[I]) For samples in which less than 100% of sample volume is examined, systems must also report the volume of resuspended concentrate and volume of this resuspension processed through immunomagnetic separation.

    (ii) Systems must report the following data elements for each E. coli analysis:

    (A) PWS ID.

    (B) Facility ID.

    (C) Sample collection date.

    (D) Analytical method number.

    (E) Method type.

    (F) Source type (flowing stream, lake/reservoir, GWUDI).

    (G) E. coli/100 mL.

    (H) Turbidity.[

    (I)] (Systems serving fewer than 10,000 people that are not required to monitor for turbidity under R309-215-15(2) are not required to report turbidity with their E. coli results.)

    (8) Grandfathering previously collected data.

    (a) (i) Systems may comply with the initial source water monitoring requirements of R309-215-15(2)(a) by grandfathering sample results collected before the system is required to begin monitoring (i.e., previously collected data). To be grandfathered, the sample results and analysis must meet the criteria in this section and the Executive Secretary must approve.

    (ii) A filtered system may grandfather Cryptosporidium samples to meet the requirements of R309-215-15(2)(a) when the system does not have corresponding E. coli and turbidity samples. A system that grandfathers Cryptosporidium samples without E. coli and turbidity samples is not required to collect E. coli and turbidity samples when the system completes the requirements for Cryptosporidium monitoring under R309-215-15(2)(a).

    (b) E. coli sample analysis. The analysis of E. coli samples must meet the analytical method and approved laboratory requirements of R309-215-15(5) through R309-215-15(6)[141.705].

    (c) Cryptosporidium sample analysis. The analysis of Cryptosporidium samples must meet the criteria in this paragraph.

    (i) Laboratories analyzed Cryptosporidium samples using one of the analytical methods in paragraphs (c)(i)(A) through (D) of this section, which are incorporated by reference. You may obtain a copy of these methods on-line from the United States Environmental Protection Agency, Office of Ground Water and Drinking Water, 1201 Constitution Ave, NW, Washington, DC 20460 (Telephone: 800-426-4791). You may inspect a copy at the Water Docket in the EPA Docket Center, 1301 Constitution Ave., NW, Washington, DC, (Telephone: 202-566-2426) or at the National Archives and Records Administration (NARA). For information on the availability of this material at NARA, call 202-741-6030, or go to: http://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html. You may also obtain a copy of these methods by contacting the Division of Drinking Water at 801-536-4200.

    (A) Method 1623: Cryptosporidium and Giardia in Water by Filtration/IMS/ FA, 2005, United States Environmental Protection Agency, EPA-815-R-05-002.

    (B) Method 1622: Cryptosporidium in Water by Filtration/IMS/FA, 2005, United States Environmental Protection Agency, EPA-815-R-05-001.

    (C) Method 1623: Cryptosporidium and Giardia in Water by Filtration/IMS/ FA, 2001, United States Environmental Protection Agency, EPA-821-R-01-025.

    (D) Method 1622: Cryptosporidium in Water by Filtration/IMS/FA, 2001, United States Environmental Protection Agency, EPA-821-R-01-026.

    (E) Method 1623: Cryptosporidium and Giardia in Water by Filtration/IMS/ FA, 1999, United States Environmental Protection Agency, EPA-821-R-99-006.

    (F) Method 1622: Cryptosporidium in Water by Filtration/IMS/FA, 1999, United States Environmental Protection Agency, EPA-821-R-99-001.

    (ii) For each Cryptosporidium sample, the laboratory analyzed at least 10 L of sample or at least 2 mL of packed pellet or as much volume as could be filtered by 2 filters that EPA approved for the methods listed in paragraph (c)(1) of this section.

    (d) Sampling location. The sampling location must meet the conditions in R309-215-15(4).

    (e) Sampling frequency. Cryptosporidium samples were collected no less frequently than each calendar month on a regular schedule, beginning no earlier than January 1999. Sample collection intervals may vary for the conditions specified in R309-215-15(3)(b)(i) and (ii) if the system provides documentation of the condition when reporting monitoring results.

    (i) The Executive Secretary may approve grandfathering of previously collected data where there are time gaps in the sampling frequency if the system conducts additional monitoring the Executive Secretary specifies to ensure that the data used to comply with the initial source water monitoring requirements of R309-215-15(2)(a) are seasonally representative and unbiased.

    (ii) Systems may grandfather previously collected data where the sampling frequency within each month varied. If the Cryptosporidium sampling frequency varied, systems must follow the monthly averaging procedure in R309-215-15(11)(b)(v) when calculating the bin classification for filtered systems.

    (f) Reporting monitoring results for grandfathering. Systems that request to grandfather previously collected monitoring results must report the following information by the applicable dates listed in this paragraph. Systems serving at least 10,000 people must report this information to EPA unless the Executive Secretary approves reporting to the Executive Secretary rather than EPA. Systems serving fewer than 10,000 people must report this information to the Executive Secretary.

    (i) Systems must report that they intend to submit previously collected monitoring results for grandfathering. This report must specify the number of previously collected results the system will submit, the dates of the first and last sample, and whether a system will conduct additional source water monitoring to meet the requirements of R309-215-15(2)(a). Systems must report this information no later than the date the sampling schedule under R309-215-15(3) is required.

    (ii) Systems must report previously collected monitoring results for grandfathering, along with the associated documentation listed in paragraphs (f)(ii)(A) through (D) of this section, no later than two months after the applicable date listed in R309-215-15(2)(c).

    (A) For each sample result, systems must report the applicable data elements in R309-215-15(7).

    (B) Systems must certify that the reported monitoring results include all results the system generated during the time period beginning with the first reported result and ending with the final reported result. This applies to samples that were collected from the sampling location specified for source water monitoring under this subpart, not spiked, and analyzed using the laboratory's routine process for the analytical methods listed in this section.

    (C) Systems must certify that the samples were representative of a plant's source water(s) and the source water(s) have not changed. Systems must report a description of the sampling location(s), which must address the position of the sampling location in relation to the system's water source(s) and treatment processes, including points of chemical addition and filter backwash recycle.

    (D) For Cryptosporidium samples, the laboratory or laboratories that analyzed the samples must provide a letter certifying that the quality control criteria specified in the methods listed in paragraph (c)(i[1]) of this section were met for each sample batch associated with the reported results. Alternatively, the laboratory may provide bench sheets and sample examination report forms for each field, matrix spike, IPR, OPR, and method blank sample associated with the reported results.

    (g) If the Executive Secretary determines that a previously collected data set submitted for grandfathering was generated during source water conditions that were not normal for the system, such as a drought, the Executive Secretary may disapprove the data. Alternatively, the Executive Secretary may approve the previously collected data if the system reports additional source water monitoring data, as determined by the Executive Secretary, to ensure that the data set used under R309-215-15(11) represents average source water conditions for the system.

    (h) If a system submits previously collected data that fully meet the number of samples required for initial source water monitoring under R309-215-15(2)(a) and some of the data are rejected due to not meeting the requirements of this section, systems must conduct additional monitoring to replace rejected data on a schedule the Executive Secretary approves. Systems are not required to begin this additional monitoring until two months after notification that data have been rejected and additional monitoring is necessary.

    (9) Disinfection Profiling and Benchmarking Requirements - Requirements when making a significant change in disinfection practice.

    (a) Following the completion of initial source water monitoring under R309-215-15(2)(a), a system that plans to make a significant change to its disinfection practice, as defined in paragraph (b) of this section, must develop disinfection profiles and calculate disinfection benchmarks for Giardia lamblia and viruses as described in R309-215-15(10). Prior to changing the disinfection practice, the system must notify the Executive Secretary and must include in this notice the information in paragraphs (a)(i) through (iii) of this section.

    (i) A completed disinfection profile and disinfection benchmark for Giardia lamblia and viruses as described in R309-215-15(10).

    (ii) A description of the proposed change in disinfection practice.

    (iii) An analysis of how the proposed change will affect the current level of disinfection.

    (b) Significant changes to disinfection practice are defined as follows:

    (i) Changes to the point of disinfection;

    (ii) Changes to the disinfectant(s) used in the treatment plant;

    (iii) Changes to the disinfection process; or

    (iv) Any other modification identified by the Executive Secretary as a significant change to disinfection practice.

    (10) Developing the disinfection profile and benchmark.

    (a) Systems required to develop disinfection profiles under R309-215-15(9) must follow the requirements of this section. Systems must monitor at least weekly for a period of 12 consecutive months to determine the total log inactivation for Giardia lamblia and viruses. If systems monitor more frequently, the monitoring frequency must be evenly spaced. Systems that operate for fewer than 12 months per year must monitor weekly during the period of operation. Systems must determine log inactivation for Giardia lamblia through the entire plant, based on CT 99.9 values in Tables 1.1 through 1.6, 2.1 and 3.1 of Section 141.74(b) in the code of Federal Regulations as applicable (available from the Division). Systems must determine log inactivation for viruses through the entire treatment plant based on a protocol approved by the Executive Secretary.

    (b) Systems with a single point of disinfectant application prior to the entrance to the distribution system must conduct the monitoring in paragraphs (b)(i) through (iv) of this section. Systems with more than one point of disinfectant application must conduct the monitoring in paragraphs (b)(i) through (iv) of this section for each disinfection segment. Systems must monitor the parameters necessary to determine the total inactivation ratio, using analytical methods in R309-200-4(3) and (4).

    (i) For systems using a disinfectant other than UV, the temperature of the disinfected water must be measured at each residual disinfectant concentration sampling point during peak hourly flow or at an alternative location approved by the Executive Secretary.

    (ii) For systems using chlorine, the pH of the disinfected water must be measured at each chlorine residual disinfectant concentration sampling point during peak hourly flow or at an alternative location approved by the Executive Secretary.

    (iii) The disinfectant contact time(s) (t) must be determined during peak hourly flow.

    (iv) The residual disinfectant concentration(s) (C) of the water before or at the first customer and prior to each additional point of disinfectant application must be measured during peak hourly flow.

    (c) In lieu of conducting new monitoring under paragraph (b) of this section, systems may elect to meet the requirements of paragraphs (c)(i[1]) or (ii[2]) of this section.

    (i) Systems that have at least one year of existing data that are substantially equivalent to data collected under the provisions of paragraph (b) of this section may use these data to develop disinfection profiles as specified in this section if the system has neither made a significant change to its treatment practice nor changed sources since the data were collected. Systems may develop disinfection profiles using up to three years of existing data.

    (ii) Systems may use disinfection profile(s) developed under R309-215-14 in lieu of developing a new profile if the system has neither made a significant change to its treatment practice nor changed sources since the profile was developed. Systems that have not developed a virus profile under R309-251-14 must develop a virus profile using the same monitoring data on which the Giardia lamblia profile is based.

    (d) Systems must calculate the total inactivation ratio for Giardia lamblia as specified in paragraphs (d)(i) through (iii) of this section.

    (i) Systems using only one point of disinfectant application may determine the total inactivation ratio for the disinfection segment based on either of the methods in paragraph (d)(1)(i) or (ii) of this section.

    (A) Determine one inactivation ratio (CTcalc/CT99.9) before or at the first customer during peak hourly flow.

    (B) Determine successive CTcalc/ CT99.9 values, representing sequential inactivation ratios, between the point of disinfectant application and a point before or at the first customer during peak hourly flow. The system must calculate the total inactivation ratio by determining (CTcalc/CT99.9) for each sequence and then adding the (CTcalc/ CT99.9) values together to determine the sum of[(S] (CTcalc/CT99.9)[)].

    (ii) Systems using more than one point of disinfectant application before the first customer must determine the CT value of each disinfection segment immediately prior to the next point of disinfectant application, or for the final segment, before or at the first customer, during peak hourly flow. The (CTcalc/ CT99.9) value of each segment and the sum of[(S] (CTcalc/CT99.9)[)] must be calculated using the method in paragraph (d)(i)(B) of this section.

    (iii) The system must determine the total logs of inactivation by multiplying the value calculated in paragraph (d)(i) or (d)(ii) of this section by 3.0.

    (iv) Systems must calculate the log of inactivation for viruses using a protocol approved by the Executive Secretary.

    (e) Systems must use the procedures specified in paragraphs (e)(i) and (ii) of this section to calculate a disinfection benchmark.

    (i) For each year of profiling data collected and calculated under paragraphs (a) through (d) of this section, systems must determine the lowest mean monthly level of both Giardia lamblia and virus inactivation. Systems must determine the mean Giardia lamblia and virus inactivation for each calendar month for each year of profiling data by dividing the sum of daily or weekly Giardia lamblia and virus log inactivation by the number of values calculated for that month.

    (ii) The disinfection benchmark is the lowest monthly mean value (for systems with one year of profiling data) or the mean of the lowest monthly mean values (for systems with more than one year of profiling data) of Giardia lamblia and virus log inactivation in each year of profiling data.

    (11) Treatment Technique Requirements - Bin classification for filtered systems.

    (a) Following completion of the initial round of source water monitoring required under R309-215-15(2)(a), filtered systems must calculate an initial Cryptosporidium bin concentration for each plant for which monitoring was required. Calculation of the bin concentration must use the Cryptosporidium results reported under R309-215-15(2)(a) and must follow the procedures in paragraphs (b)(i) through (v) of this section.

    (b)(i) For systems that collect a total of at least 48 samples, the bin concentration is equal to the arithmetic mean of all sample concentrations.

    (ii) For systems that collect a total of at least 24 samples, but not more than 47 samples, the bin concentration is equal to the highest arithmetic mean of all sample concentrations in any 12 consecutive months during which Cryptosporidium samples were collected.

    (iii) For systems that serve fewer than 10,000 people and monitor for Cryptosporidium for only one year (i.e., collect 24 samples in 12 months), the bin concentration is equal to the arithmetic mean of all sample concentrations.

    (iv) For systems with plants operating only part of the year that monitor fewer than 12 months per year under R309-215-15(2)(e), the bin concentration is equal to the highest arithmetic mean of all sample concentrations during any year of Cryptosporidium monitoring.

    (v) If the monthly Cryptosporidium sampling frequency varies, systems must first calculate a monthly average for each month of monitoring. Systems must then use these monthly average concentrations, rather than individual sample concentrations, in the applicable calculation for bin classification in paragraphs (b)(i) through (iv) of this section.

    (c) Filtered systems must determine their initial bin classification from the following [table] and using the Cryptosporidium bin concentration calculated under paragraphs (a) and (b) of this section:

    (i) Systems that are required to monitor for Cryptosporidium under R309-215-15(2):

    (A) with a cryptosporidium concentration of less than 0.075 oocyst/L, the bin classification is Bin 1.

    (B) with a cryptosporidium concentration of 0.075 oocysts/L to less than 1.0 oocysts/L, the bin classification is Bin 2.

    (C) with a cryptosporidium concentration of 1.0 oocysts/L to less than 3.0 oocysts/L, the bin classification is Bin 3.

    (D) with a cryptosporidium concentration of equal to or greater than 3.0 oocysts/L, the bin classification is Bin 4.

    (ii) Systems serving fewer than 10,000 people and not required to monitor for Cryptosporidium under R309-215-15(2)(a)(iii), the concentration of cryptosporidium is not applicable and their bin classification is Bin 1.

    (iii) Based on calculations in paragraph (a) or (d) of this section, as applicable.

    (d) Following completion of the second round of source water monitoring required under R309-215-15(2)(b), filtered systems must recalculate their Cryptosporidium bin concentration using the Cryptosporidium results reported under R309-215-15(2)(b) and following the procedures in paragraphs (b)(i) through (iv) of this section. Systems must then redetermine their bin classification using this bin concentration and the table in paragraph (c) of this section.

    (e)(i) Filtered systems must report their initial bin classification under paragraph (c) of this section to the Executive Secretary for approval no later than 6 months after the system is required to complete initial source water monitoring based on the schedule in R309-215-15(2)(c).

    (ii) Systems must report their bin classification under paragraph (d) of this section to the Executive Secretary for approval no later than 6 months after the system is required to complete the second round of source water monitoring based on the schedule in R309-215-15(2)(c).

    (iii) The bin classification report to the Executive Secretary must include a summary of source water monitoring data and the calculation procedure used to determine bin classification.

    (f) Failure to comply with the conditions of paragraph (e) of this section is a violation of the treatment technique requirement.

    (12) Filtered system additional Cryptosporidium treatment requirements.

    (a) Filtered systems must provide the level of additional treatment for Cryptosporidium specified in this paragraph based on their bin classification as determined under R309-215-15(11) and according to the schedule in R309-215-15(13). The filtration treatment used by the system in this paragraph must be utilized in full compliance with the requirements of R309-200-5(5), R309-200-7, R309-215-8 and 9.

    (i) If the system bin classification is Bin 1 and the system uses:

    (A) Conventional filtration treatment including softening there is no additional cryptosporidium treatment required.

    (B) Direct filtration there is no additional cryptosporidium treatment required.

    (C) Slow sand or diatomaceous earth filtration there is no additional cryptosporidium treatment required.

    (D) Alternative filtration technologies there is no additional cryptosporidium treatment required.

    (ii) If the system bin classification is Bin 2 and the system uses:

    (A) Conventional filtration treatment including softening there is an additional 1-log cryptosporidium treatment required.

    (B) Direct filtration there is an additional 1.5-log cryptosporidium treatment required.

    (C) Slow sand or diatomaceous earth filtration there is an additional 1-log cryptosporidium treatment required.

    (D) Alternative filtration technologies there is an additional cryptosporidium treatment required as determined by the Executive Secretary such that the total Cryptosporidium removal an inactivation is at least 4.0-log.

    (iii) If the system bin classification is Bin 3 and the system uses:

    (A) Conventional filtration treatment including softening there is an additional 2-log cryptosporidium treatment required.

    (B) Direct filtration there is an additional 2.5-log cryptosporidium treatment required.

    (C) Slow sand or diatomaceous earth filtration there is an additional 2-log cryptosporidium treatment required.

    (D) Alternative filtration technologies there is an additional cryptosporidium treatment required as determined by the Executive Secretary such that the total Cryptosporidium removal an inactivation is at least 5.0-log.

    (iv) If the system bin classification is Bin 4 and the system uses:

    (A) Conventional filtration treatment including softening there is an additional 2.5-log cryptosporidium treatment required.

    (B) Direct filtration there is an additional 3-log cryptosporidium treatment required.

    (C) Slow sand or diatomaceous earth filtration there is an additional 2.5-log cryptosporidium treatment required.

    (D) Alternative filtration technologies there is an additional cryptosporidium treatment required as determined by the Executive Secretary such that the total Cryptosporidium removal an inactivation is at least 5.5-log.

    (b)(i) Filtered systems must use one or more of the treatment and management options listed in R309-215-15(14), termed the microbial toolbox, to comply with the additional Cryptosporidium treatment required in paragraph (a) of this section.

    (ii) Systems classified in Bin 3 and Bin 4 must achieve at least 1-log of the additional Cryptosporidium treatment required under paragraph (a) of this section using either one or a combination of the following: bag filters, bank filtration, cartridge filters, chlorine dioxide, membranes, ozone, or UV, as described in R309-215-15(15) through R309-215-15(19).

    (c) Failure by a system in any month to achieve treatment credit by meeting criteria in R309-215-15(15) through R309-215-15(19) for microbial toolbox options that is at least equal to the level of treatment required in paragraph (a) of this section is a violation of the treatment technique requirement.

    (d) If the Executive Secretary determines during a sanitary survey or an equivalent source water assessment that after a system completed the monitoring conducted under R309-215-15(2)(a) or R309-215-15(2)(b), significant changes occurred in the system's watershed that could lead to increased contamination of the source water by Cryptosporidium, the system must take actions specified by the Executive Secretary to address the contamination. These actions may include additional source water monitoring and/or implementing microbial toolbox options listed in R309-215-15(14).

    (13) Schedule for compliance with Cryptosporidium treatment requirements.

    (a) Following initial bin classification under R309-215-15(11)(c), filtered systems must provide the level of treatment for Cryptosporidium required under R309-215-15(12) according to the schedule in paragraph (c) of this section.

    (b) Cryptosporidium treatment compliance dates.

    (i) Systems that serve at least 100,000 people must comply with Cryptosporidium treatment requirements no later than April 1, 2012.

    (ii) Systems that serve from 50,000 to 99,999 people must comply with Cryptosporidium treatment requirements no later than October 1, 2012.

    (iii) Systems that serve from 10,000 to 49,999 people must comply with Cryptosporidium treatment requirements no later than October 1, 2013.

    (iv) Systems that serve less than 10,000 people must comply with Cryptosporidium treatment requirements no later than October 1, 2014.

    (v) The Executive Secretary may allow up to an additional two years for complying with the treatment requirement for systems making capital improvements.

    (c) If the bin classification for a filtered system changes following the second round of source water monitoring, as determined under R309-215-15(11)(d), the system must provide the level of treatment for Cryptosporidium required under R309-215-15(12) on a schedule the Executive Secretary approves.

    (14) Microbial toolbox options for meeting Cryptosporidium treatment requirements.

    (a) Systems receive the treatment credits listed in the table in paragraph (b) of this section by meeting the conditions for microbial toolbox options described in R309-215-15(15) through R309-215-15(19). Systems apply these treatment credits to meet the treatment requirements in R309-215-15(12).

    (b) The following sub-section summarizes options in the microbial toolbox and the Cryptosporidium treatment credit with design and implementation criteria.

    (i) Source Protection and Management Toolbox Options:

    (A) Watershed control program: 0.5-log credit for Executive Secretary-approved program comprising required elements, annual program status report to Executive Secretary, and regular watershed survey. [Unfiltered systems are not eligible for credit. ]Specific criteria are in R309-215-15(15) (a).

    (B) Alternative source/intake management: No prescribed credit. Systems may conduct simultaneous monitoring for treatment bin classification at alternative intake locations or under alternative intake management strategies. Specific criteria are in R309-215-15(15) (b).

    (ii) Pre Filtration Toolbox Options:

    (A) Presedimentation basin with coagulation: 0.5-log credit during any month that presedimentation basins achieve a monthly mean reduction of 0.5-log or greater in turbidity or alternative Executive Secretary-approved performance criteria. To be eligible, basins must be operated continuously with coagulant addition and all plant flow must pass through basins. Specific criteria are in R309-215-15(16) (a).

    (B) Two-stage lime softening: 0.5-log credit for two-stage softening where chemical addition and hardness precipitation occur in both stages. All plant flow must pass through both stages. Single-stage softening is credited as equivalent to conventional treatment. Specific criteria are in R309-215-15(16) (b).

    (C) Bank filtration: 0.5-log credit for 25-foot setback; 1.0-log credit for 50-foot setback; aquifer must be unconsolidated sand containing at least 10 percent fines; average turbidity in wells must be less than 1 NTU. Systems using wells followed by filtration when conducting source water monitoring must sample the well to determine bin classification and are not eligible for additional credit. Specific criteria are in R309-215-15(16) (c).

    (iii) Treatment Performance Toolbox Options:

    (A) Combined filter performance: 0.5-log credit for combined filter effluent turbidity less than or equal to 0.15 NTU in at least 95 percent of measurements each month. Specific criteria are in R309-215-15(17) (a).

    (B) Individual filter performance: 0.5-log credit (in addition to 0.5-log combined filter performance credit) if individual filter effluent turbidity is less than or equal to 0.15 NTU in at least 95 percent of samples each month in each filter and is never greater than 0.3 NTU in two consecutive measurements in any filter. Specific criteria are in R309-215-15(17) (b).

    (C) Demonstration of performance: Credit awarded to unit process or treatment train based on a demonstration to the Executive Secretary with a Executive Secretary-approved protocol. Specific criteria are in R309-215-15(17) (c).

    (iv) Additional Filtration Toolbox Options:

    (A) Bag or cartridge filters (individual filters): Up to 2-log credit based on the removal efficiency demonstrated during challenge testing with a 1.0-log factor of safety. Specific criteria are in R309-215-15(18) (a).

    (B) Bag or cartridge filters (in series): Up to 2.5-log credit based on the removal efficiency demonstrated during challenge testing with a 0.5-log factor of safety. Specific criteria are in R309-215-15(18) (a).

    (C) Membrane filtration: Log credit equivalent to removal efficiency demonstrated in challenge test for device if supported by direct integrity testing. Specific criteria are in R309-215-15(18) (b).

    (D) Second stage filtration: 0.5-log credit for second separate granular media filtration stage if treatment train includes coagulation prior to first filter. Specific criteria are in R309-215-15(18) (c).

    (E) Slow sand filters: 2.5-log credit as a secondary filtration step; 3.0-log credit as a primary filtration process. No prior chlorination for either option. Specific criteria are in R309-215-15(18) (d).

    (v) Inactivation Toolbox Options:

    (A) Chlorine dioxide: Log credit based on measured CT in relation to CT table. Specific criteria in R309-215-15(19) (b).

    (B) Ozone: Log credit based on measured CT in relation to CT table. Specific criteria in R309-215-15(19) (b).

    (C) UV: Log credit based on validated UV dose in relation to UV dose table; reactor validation testing required to establish UV dose and associated operating conditions. Specific criteria in R309-215-15(19) (d).

     

    . . . . . . .

     

    (18) Additional filtration toolbox components.

    (a) Bag and cartridge filters. Systems receive Cryptosporidium treatment credit of up to 2.0-log for individual bag or cartridge filters and up to 2.5-log for bag or cartridge filters operated in series by meeting the criteria in paragraphs (a)(i) through (x) of this section. To be eligible for this credit, systems must report the results of challenge testing that meets the requirements of paragraphs (a)(ii) through (ix) of this section to the Executive Secretary. The filters must treat the entire plant flow taken from a surface water source.

    (i) The Cryptosporidium treatment credit awarded to bag or cartridge filters must be based on the removal efficiency demonstrated during challenge testing that is conducted according to the criteria in paragraphs (a)(ii) through (a)(ix) of this section. A factor of safety equal to 1-log for individual bag or cartridge filters and 0.5-log for bag or cartridge filters in series must be applied to challenge testing results to determine removal credit. Systems may use results from challenge testing conducted prior to January 5, 2006 if the prior testing was consistent with the criteria specified in paragraphs (a)(ii) through (ix) of this section.

    (ii) Challenge testing must be performed on full-scale bag or cartridge filters, and the associated filter housing or pressure vessel, that are identical in material and construction to the filters and housings the system will use for removal of Cryptosporidium. Bag or cartridge filters must be challenge tested in the same configuration that the system will use, either as individual filters or as a series configuration of filters.

    (iii) Challenge testing must be conducted using Cryptosporidium or a surrogate that is removed no more efficiently than Cryptosporidium. The microorganism or surrogate used during challenge testing is referred to as the challenge particulate. The concentration of the challenge particulate must be determined using a method capable of discreetly quantifying the specific microorganism or surrogate used in the test; gross measurements such as turbidity may not be used.

    (iv) The maximum feed water concentration that can be used during a challenge test must be based on the detection limit of the challenge particulate in the filtrate (i.e., filtrate detection limit) and must be calculated using the following equation: Maximum Feed Concentration = 1 x 104 x (Filtrate Detection Limit).

    (v) Challenge testing must be conducted at the maximum design flow rate for the filter as specified by the manufacturer.

    (vi) Each filter evaluated must be tested for a duration sufficient to reach 100 percent of the terminal pressure drop, which establishes the maximum pressure drop under which the filter may be used to comply with the requirements of this subpart.

    (vii) Removal efficiency of a filter must be determined from the results of the challenge test and expressed in terms of log removal values using the following equation: LRV = LOG10(Cf)-LOG10(Cp) Where: LRV = log removal value demonstrated during challenge testing; Cf = the feed concentration measured during the challenge test; and Cp = the filtrate concentration measured during the challenge test. In applying this equation, the same units must be used for the feed and filtrate concentrations. If the challenge particulate is not detected in the filtrate, then the term Cp must be set equal to the detection limit.

    (viii) Each filter tested must be challenged with the challenge particulate during three periods over the filtration cycle: within two hours of start-up of a new filter; when the pressure drop is between 45 and 55 percent of the terminal pressure drop; and at the end of the cycle after the pressure drop has reached 100 percent of the terminal pressure drop. An LRV must be calculated for each of these challenge periods for each filter tested. The LRV for the filter (LRVfilter) must be assigned the value of the minimum LRV observed during the three challenge periods for that filter.

    (ix) If fewer than 20 filters are tested, the overall removal efficiency for the filter product line must be set equal to the lowest LRVfilter among the filters tested. If 20 or more filters are tested, the overall removal efficiency for the filter product line must be set equal to the 10th percentile of the set of LRVfilter values for the various filters tested. The percentile is defined by (i/(n+1)) where i is the rank of n individual data points ordered lowest to highest. If necessary, the 10th percentile may be calculated using linear interpolation.

    (x) If a previously tested filter is modified in a manner that could change the removal efficiency of the filter product line, challenge testing to demonstrate the removal efficiency of the modified filter must be conducted and submitted to the Executive Secretary.

    (b) Membrane filtration.

    (i) Systems receive Cryptosporidium treatment credit for membrane filtration that meets the criteria of this paragraph. Membrane cartridge filters that meet the definition of membrane filtration in R309-110 are eligible for this credit. The level of treatment credit a system receives is equal to the lower of the values determined under paragraph (b)(i)(A) and (B) of this section.

    (A) The removal efficiency demonstrated during challenge testing conducted under the conditions in paragraph (b)(ii) of this section.

    (B) The maximum removal efficiency that can be verified through direct integrity testing used with the membrane filtration process under the conditions in paragraph (b)(iii) of this section.

    (ii) Challenge Testing. The membrane used by the system must undergo challenge testing to evaluate removal efficiency, and the system must report the results of challenge testing to the Executive Secretary. Challenge testing must be conducted according to the criteria in paragraphs (b)(ii)(A) through (G) of this section. Systems may use data from challenge testing conducted prior to January 5, 2006 if the prior testing was consistent with the criteria in paragraphs (b)(ii)(A) through (G) of this section.

    (A) Challenge testing must be conducted on either a full-scale membrane module, identical in material and construction to the membrane modules used in the system's treatment facility, or a smaller-scale membrane module, identical in material and similar in construction to the full-scale module. A module is defined as the smallest component of a membrane unit in which a specific membrane surface area is housed in a device with a filtrate outlet structure.

    (B) Challenge testing must be conducted using Cryptosporidium oocysts or a surrogate that is removed no more efficiently than Cryptosporidium oocysts. The organism or surrogate used during challenge testing is referred to as the challenge particulate. The concentration of the challenge particulate, in both the feed and filtrate water, must be determined using a method capable of discretely quantifying the specific challenge particulate used in the test; gross measurements such as turbidity may not be used.

    (C) The maximum feed water concentration that can be used during a challenge test is based on the detection limit of the challenge particulate in the filtrate and must be determined according to the following equation: Maximum Feed Concentration = 3.16 x 106 x (Filtrate Detection Limit).

    (D) Challenge testing must be conducted under representative hydraulic conditions at the maximum design flux and maximum design process recovery specified by the manufacturer for the membrane module. Flux is defined as the throughput of a pressure driven membrane process expressed as flow per unit of membrane area. Recovery is defined as the volumetric percent of feed water that is converted to filtrate over the course of an operating cycle uninterrupted by events such as chemical cleaning or a solids removal process (i.e., backwashing).

    (E) Removal efficiency of a membrane module must be calculated from the challenge test results and expressed as a log removal value according to the following equation: LRV = LOG10(Cf) [x]- LOG10(Cp) Where: LRV = log removal value demonstrated during the challenge test; Cf = the feed concentration measured during the challenge test; and Cp = the filtrate concentration measured during the challenge test. Equivalent units must be used for the feed and filtrate concentrations. If the challenge particulate is not detected in the filtrate, the term Cp is set equal to the detection limit for the purpose of calculating the LRV. An LRV must be calculated for each membrane module evaluated during the challenge test.

    (F) The removal efficiency of a membrane filtration process demonstrated during challenge testing must be expressed as a log removal value (LRVC-Test). If fewer than 20 modules are tested, then LRVC-Test is equal to the lowest of the representative LRVs among the modules tested. If 20 or more modules are tested, then LRVC-Test is equal to the 10th percentile of the representative LRVs among the modules tested. The percentile is defined by (i/(n+1)) where i is the rank of n individual data points ordered lowest to highest. If necessary, the 10th percentile may be calculated using linear interpolation.

    (G) The challenge test must establish a quality control release value (QCRV) for a non-destructive performance test that demonstrates the Cryptosporidium removal capability of the membrane filtration module. This performance test must be applied to each production membrane module used by the system that was not directly challenge tested in order to verify Cryptosporidium removal capability. Production modules that do not meet the established QCRV are not eligible for the treatment credit demonstrated during the challenge test.

    (H) If a previously tested membrane is modified in a manner that could change the removal efficiency of the membrane or the applicability of the non-destructive performance test and associated QCRV, additional challenge testing to demonstrate the removal efficiency of, and determine a new QCRV for, the modified membrane must be conducted and submitted to the Executive Secretary.

     

    . . . . . . .

     

    (19) Inactivation toolbox components.

    (a) Calculation of CT values. (i) CT is the product of the disinfectant contact time (T, in minutes) and disinfectant concentration (C, in milligrams per liter). Systems with treatment credit for chlorine dioxide or ozone under paragraph (b) or (c) of this section must calculate CT at least once each day, with both C and T measured during peak hourly flow as specified in R309-200-4(3) and (4).

    (ii) Systems with several disinfection segments in sequence may calculate CT for each segment, where a disinfection segment is defined as a treatment unit process with a measurable disinfectant residual level and a liquid volume. Under this approach, systems must add the Cryptosporidium CT values in each segment to determine the total CT for the treatment plant.

    (b) CT values for chlorine dioxide and ozone. (i) Systems receive the Cryptosporidium treatment credit listed in this paragraph by meeting the corresponding chlorine dioxide CT value for the applicable water temperature, as described in paragraph (a) of this section.

    (i) CT values ((MG)(MIN)/L) for Cryptosporidium inactivation by Chlorine Dioxide listed by the log credit with inactivation listed by water temperature in degrees Celsius.

    (A) 0.25 Log Credit:

    (I) less than or equal to 0.5 degrees: 159;

    (II) 1 degree: 153;

    (III) 2 degrees: 140;

    (IV) 3 degrees: 128;

    (V) 5 degrees: 107;

    (VI) 7 degrees: 90;

    (VII) 10 degrees: 69;

    (VIII) 15 degrees: 45;

    (IX) 20 degrees: 29;

    (X) 25 degrees: 19; and

    (XI) 30 degrees: 12.

    (B) 0.5 Log Credit:

    (I) less than or equal to 0.5 degrees: 319;

    (II) 1 degree: 305;

    (III) 2 degrees: 279;

    (IV) 3 degrees: 256;

    (V) 5 degrees: 214;

    (VI) 7 degrees: 180;

    (VII) 10 degrees: 138;

    (VIII) 15 degrees: 89;

    (IX) 20 degrees: 58;

    (X) 25 degrees: 38; and

    (XI) 30 degrees: 24.

    (C) 1.0 Log Credit:

    (I) less than or equal to 0.5 degrees: 637;

    (II) 1 degree: 610;

    (III) 2 degrees: 558;

    (IV) 3 degrees: 511;

    (V) 5 degrees: 429;

    (VI) 7 degrees: 360;

    (VII) 10 degrees: 277;

    (VIII) 15 degrees: 179;

    (IX) 20 degrees: 116;

    (X) 25 degrees: 75; and

    (XI) 30 degrees: 49.

    (D) 1.5 Log Credit:

    (I) less than or equal to 0.5 degrees: 956;

    (II) 1 degree: 915;

    (III) 2 degrees: 838;

    (IV) 3 degrees: 767;

    (V) 5 degrees: 643;

    (VI) 7 degrees: 539;

    (VII) 10 degrees: 415;

    (VIII) 15 degrees: 268;

    (IX) 20 degrees: 174;

    (X) 25 degrees: 113; and

    (XI) 30 degrees: 73.

    (E) 2.0 Log Credit:

    (I) less than or equal to 0.5 degrees: 1275;

    (II) 1 degree: 1220;

    (III) 2 degrees: 1117;

    (IV) 3 degrees: 1023;

    (V) 5 degrees: 858;

    (VI) 7 degrees: 719;

    (VII) 10 degrees: 553;

    (VIII) 15 degrees: 357;

    (IX) 20 degrees: 232;

    (X) 25 degrees: 150; and

    (XI) 30 degrees: 98.

    (F) 2.5 Log Credit:

    (I) less than or equal to 0.5 degrees: 1594;

    (II) 1 degree: 1525;

    (III) 2 degrees: 1396;

    (IV) 3 degrees: 1278;

    (V) 5 degrees: 1072;

    (VI) 7 degrees: 899;

    (VII) 10 degrees: 691;

    (VIII) 15 degrees: 447;

    (IX) 20 degrees: 289;

    (X) 25 degrees: 188; and

    (XI) 30 degrees: 122.

    (G) 3.0 Log Credit:

    (I) less than or equal to 0.5 degrees: 1912;

    (II) 1 degree: 1830;

    (III) 2 degrees: 1675;

    (IV) 3 degrees: 1534;

    (V) 5 degrees: 1286;

    (VI) 7 degrees: 1079;

    (VII) 10 degrees: 830;

    (VIII) 15 degrees: 536;

    (IX) 20 degrees: 347;

    (X) 25 degrees: 226; and

    (XI) 30 degrees: 147.

    (F) Systems may use this equation to determine log credit between the indicated values above: Log credit = (0.001506 x (1.09116) Temp) x CT.

    (ii) Systems receive the Cryptosporidium treatment credit listed in this paragraph[table] by meeting the corresponding ozone CT values for the applicable water temperature, as described in paragraph (a) of this section. CT values ((MG)(MIN)/L) for Cryptosporidium inactivation by Ozone listed by the log credit with inactivation listed by water temperature in degrees Celsius.

    (A) 0.25 Log Credit:

    (I) less than or equal to 0.5 degrees: 6.0;

    (II) 1 degree: 5.8;

    (III) 2 degrees: 5.2;

    (IV) 3 degrees: 4.8;

    (V) 5 degrees: 4.0;

    (VI) 7 degrees: 3.3;

    (VII) 10 degrees: 2.5;

    (VIII) 15 degrees: 1.6;

    (IX) 20 degrees: 1.0;

    (X) 25 degrees: 0.6[0.3]; and

    (XI) 30 degrees: 0.39.

    (B) 0.5 Log Credit:

    (I) less than or equal to 0.5 degrees: 12;

    (II) 1 degree: 12;

    (III) 2 degrees: 10;

    (IV) 3 degrees: 9.5;

    (V) 5 degrees: 7.9;

    (VI) 7 degrees: 6.5;

    (VII) 10 degrees: 4.9;

    (VIII) 15 degrees: 3.1;

    (IX) 20 degrees: 2.0;

    (X) 25 degrees: 1.2; and

    (XI) 30 degrees: 0.78.

    (C) 1.0 Log Credit:

    (I) less than or equal to 0.5 degrees: 24;

    (II) 1 degree: 23;

    (III) 2 degrees: 21;

    (IV) 3 degrees: 19;

    (V) 5 degrees: 16;

    (VI) 7 degrees: 13;

    (VII) 10 degrees: 9.9;

    (VIII) 15 degrees: 6.2;

    (IX) 20 degrees: 3.9;

    (X) 25 degrees: 2.5; and

    (XI) 30 degrees: 1.6.

    (D) 1.5 Log Credit:

    (I) less than or equal to 0.5 degrees: 36;

    (II) 1 degree: 35;

    (III) 2 degrees: 31;

    (IV) 3 degrees: 29;

    (V) 5 degrees: 24;

    (VI) 7 degrees: 20;

    (VII) 10 degrees: 15;

    (VIII) 15 degrees: 9.3;

    (IX) 20 degrees: 5.9;

    (X) 25 degrees: 3.7; and

    (XI) 30 degrees: 2.4.

    (E) 2.0 Log Credit:

    (I) less than or equal to 0.5 degrees: 48;

    (II) 1 degree: 46;

    (III) 2 degrees: 42;

    (IV) 3 degrees: 38;

    (V) 5 degrees: 32;

    (VI) 7 degrees: 26;

    (VII) 10 degrees: 20;

    (VIII) 15 degrees: 12;

    (IX) 20 degrees: 7.8;

    (X) 25 degrees: 4.9; and

    (XI) 30 degrees: 3.1.

    (F) 2.5 Log Credit:

    (I) less than or equal to 0.5 degrees: 60;

    (II) 1 degree: 58;

    (III) 2 degrees: 52;

    (IV) 3 degrees: 48;

    (V) 5 degrees: 40;

    (VI) 7 degrees: 33;

    (VII) 10 degrees: 25;

    (VIII) 15 degrees: 16;

    (IX) 20 degrees: 9.8;

    (X) 25 degrees: 6.2; and

    (XI) 30 degrees: 3.9.

    (G) 3.0 Log Credit:

    (I) less than or equal to 0.5 degrees: 72;

    (II) 1 degree: 69;

    (III) 2 degrees: 63;

    (IV) 3 degrees: 57;

    (V) 5 degrees: 47;

    (VI) 7 degrees: 39;

    (VII) 10 degrees: 30;

    (VIII) 15 degrees: 19;

    (IX) 20 degrees: 12;

    (X) 25 degrees: 7.4; and

    (XI) 30 degrees: 4.7.

    (F) Systems may use this equation to determine log credit between the indicated values: Log credit = (0.0397 [x]x (1.09757)Temp) x CT.

     

    . . . . . . .

     

    (21) Recordkeeping requirements.

    (a) Systems must keep results from the initial round of source water monitoring under R309-215-15(2)(a) and the second round of source water monitoring under R309-215-15(2)(b) until 3 years after bin classification under R309-215-15(11) for filtered systems [or determination of the mean Cryptosporidium level under R309-215-15(11) for unfiltered systems ]for the particular round of monitoring.

    (b) Systems must keep any notification to the Executive Secretary that they will not conduct source water monitoring due to meeting the criteria of R309-215-15(2)(d) for 3 years.

    (c) Systems must keep the results of treatment monitoring associated with microbial toolbox options under R309-215-15(15) through R309-215-15(19) for 3 years.

    (22) Requirements for Sanitary Surveys Performed by EPA. Requirements to respond to significant deficiencies identified in sanitary surveys performed by EPA.

    (a) A sanitary survey is an onsite review of the water source (identifying sources of contamination by using results of source water assessments where available), facilities, equipment, operation, maintenance, and monitoring compliance of a PWS to evaluate the adequacy of the PWS, its sources and operations, and the distribution of safe drinking water.

    (b) For the purposes of this section, a significant deficiency includes a defect in design, operation, or maintenance, or a failure or malfunction of the sources, treatment, storage, or distribution system that EPA determines to be causing, or has the potential for causing the introduction of contamination into the water delivered to consumers.

    (c) For sanitary surveys performed by EPA, systems must respond in writing to significant deficiencies identified in sanitary survey reports no later than 45 days after receipt of the report, indicating how and on what schedule the system will address significant deficiencies noted in the survey.

    (d) Systems must correct significant deficiencies identified in sanitary survey reports according to the schedule approved by EPA, or if there is no approved schedule, according to the schedule reported under paragraph (c) of this section if such deficiencies are within the control of the system.

     

    KEY: drinking water, surface water treatment plant monitoring, disinfection monitoring, compliance determinations

    Date of Enactment or Last Substantive Amendment: May 21[March 6], 2007

    Notice of Continuation: May 16, 2005

    Authorizing, and Implemented or Interpreted Law: 19-4-104; 63-46b-4

     

Document Information

Effective Date:
5/8/2007
Publication Date:
04/01/2007
Filed Date:
03/14/2007
Agencies:
Environmental Quality,Drinking Water
Rulemaking Authority:

Sections 19-4-104 and 63-46b-4, and 40 CFR 141 and 142

Authorized By:
Ken Bousfield, Acting Director
DAR File No.:
29645
Related Chapter/Rule NO.: (1)
R309-215. Monitoring and Water Quality: Treatment Plant Monitoring Requirements.