-
DAR File No.: 29078
Filed: 01/18/2007, 11:13
Received by: NLRULE ANALYSIS
Purpose of the rule or reason for the change:
Following a public rule hearing conducted on 11/15/2006, the Division and the Uniform Building Code Commission are proposing these additional changes. At the public hearing, comments were made that the proposed rule amendment needed some further technical clarification regarding the requirement for closed parking garages and that the requirement to have a sprinkler system in all open parking garages over 5,000 square feet seemed to be unnecessary and expensive overkill in many instances. The reason for the original rule amendment was explained that many parking garages do not have adequate fire department vehicle or equipment access to fight a fire that may occur in a vehicle. It was suggested that the sprinkler requirements be imposed only in open parking garages which do not have reasonable access to fire department equipment rather than to all garages over 5,000 square feet. The Uniform Building Code Commission and their fire committee agreed to this change in the proposed rule amendment. This change in proposed rule amendment changes the requirement that the sprinkler system be required if the open parking garage is over 5,000 square feet to only require the sprinkler in open garages if the fire department does not have reasonable access (within 150 feet from any point in the garage) or if the building does not have a Class 1 standpipe. This change in proposed rule amendment also clarifies the requirement for a sprinkler system which is required in all parking garages that are enclosed. This is not a change from prior requirements but the newly added language seemed to confuse the requirement for closed garages. This change in proposed rule amendment incorporates changes in the fire code requirements that are also being proposed by the State Fire Marshal. The Uniform Building Code Commission does not have authority over the fire codes; however, the Commission does correlate building codes to fire code requirements to eliminate confusion of what may be allowed in a building. (DAR NOTE: This change in proposed rule has been filed to make additional changes to a proposed amendment that was published in the October 15, 2006, issue of the Utah State Bulletin, on page 10. Underlining in the rule below indicates text that has been added since the publication of the proposed rule mentioned above; strike out indicates text that has been deleted. You must view the change in proposed rule and the proposed amendment together to understand all of the changes that will be enforceable should the agency make this rule effective.)
Summary of the rule or change:
Subsections R156-56-704(23) and R156-56-704(24) regarding Sections (F)903.2.9 and (F)903.2.9.1 are amended consistent with the reasons expressed above to change the requirement for automatic sprinkler systems in open garages which do not have adequate access to fire fighting resources and to coordinate with requirements proposed by the State Fire Marshal. In Subsection R156-56-704(51), the reference to Section 2306.1.5 is corrected. The remaining subsection numbers in the rule have been renumbered to reflect the addition of subsections (23) and (24) regarding the parking garage amendments.
State statutory or constitutional authorization for this rule:
Section 58-56-1 and Subsections 58-1-106(1)(a), 58-1-202(1)(a), 58-56-4(2), and 58-56-6(2)(a)
Anticipated cost or savings to:
the state budget:
No additional costs or savings are anticipated beyond those previously identified in the original proposed rule amendment filing as a result of this change in proposed rule amendment. This change may, however, result in substantially lower costs than originally proposed.
local governments:
No additional costs or savings are anticipated beyond those previously identified in the original proposed rule amendment filing as a result of this change in proposed rule amendment. This change may, however, result in substantially lower costs than originally proposed.
other persons:
No additional costs or savings are anticipated beyond those previously identified in the original proposed rule amendment filing as a result of this change in proposed rule amendment. This change may, however, result in substantially lower costs than originally proposed.
Compliance costs for affected persons:
No additional costs or savings are anticipated beyond those previously identified in the original proposed rule amendment filing as a result of this change in proposed rule amendment. This change may, however, result in substantially lower costs than originally proposed.
Comments by the department head on the fiscal impact the rule may have on businesses:
This change in proposed rule contains an amendment regarding sprinklers in parking garages over 5,000 square feet. The State Fire Marshal's office intends to make a similar rule filing. Other than a cost in building these parking garages, no additional fiscal impact to businesses is anticipated. Francine A. Giani, Executive Director
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:
Commerce
Occupational and Professional Licensing
HEBER M WELLS BLDG
160 E 300 S
SALT LAKE CITY UT 84111-2316Direct questions regarding this rule to:
Dan S. Jones at the above address, by phone at 801-530-6720, by FAX at 801-530-6511, or by Internet E-mail at dansjones@utah.gov
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:
03/19/2007
This rule may become effective on:
03/27/2007
Authorized by:
F. David Stanley, Director
RULE TEXT
R156. Commerce, Occupational and Professional Licensing.
R156-56. Utah Uniform Building Standard Act Rules.
R156-56-704. Statewide Amendments to the IBC.
The following are adopted as amendments to the IBC to be applicable statewide:
. . . . . . .
(22) In Section F903.2.8 condition 2 is deleted and replaced with the following:
2. Where a Group S-1 fire area is located more than three stories above the lowest level of fire department vehicle access; or
([
20]23) [In]Section (F)903.2.9 [the exception]is deleted and replaced with the following:(F)903.2.9 Group S-2. An automatic sprinkler system shall be provided throughout buildings classified as parking garages in accordance with Section 406.4 or where located beneath other groups.
Exception 1: [
Enclosed p]Parking garages of less than 5,000 square feet (464 m2)located beneath Group R-3 occupancies.Exception 2: Open parking garages not located beneath other groups if one of the following conditions is met:
a. Access is provided for fire fighting operations to within 150 feet (45,720 mm) of all portions of the parking garage as measured from the approved fire department vehicle access; or
b. Class I standpipes are installed throughout the parking garage.
([
21]24) In Section (F)903.2.9.1 [is deleted and replaced with the following:(F)903.2.9.1 Parking garages. An automatic sprinkler system shall be provided throughout buildings used for parking or storage of vehicles]the last clause" where the fire area exceeds 5,000 square feet (464 m2)" is deleted.([
23]25) Section (F)904.11 and Subsections (F)904.11.3, (F)904.11.3.1, (F)904.11.4 and (F)904.11.4.1 are deleted and replaced with the following:(F)904.11 Commercial cooking systems. The automatic fire-extinguishing system for commercial cooking systems shall be of a type recognized for protection of commercial cooking equipment and exhaust systems of the type and arrangement protected. Pre-engineered automatic extinguishing systems shall be tested in accordance with UL 300 and listed and labeled for the intended application. The system shall be installed in accordance with this code, its listing and the manufacturer's installation instructions. Automatic fire-extinguishing systems shall be installed in accordance with the referenced standard for wet-chemical extinguishing systems, NFPA 17A.
Exception: Factory-built commercial cooking recirculating systems that are tested in accordance with UL 710B and listed, labeled and installed in accordance with Section 304.1 of the International Mechanical Code.
(Subsections (F)904.11.1 and (F)904.11.2 remain unchanged.
([
24]26) Section (F)907.2.10 is deleted and replaced with the following:(F)907.2.10 Single- and multiple-station alarms. Listed single- and multiple-station smoke alarms complying with U.L. 217 shall be installed in accordance with the provision of this code and the household fire-warning equipment provision of NFPA 72. Listed single- and multiple-station carbon monoxide detectors shall comply with U.L. 2034 and shall be installed in accordance with the provisions of this code and NFPA 720.
(F)907.2.10.1 Smoke alarms. Single- or multiple-station smoke alarms shall be installed in the locations described in Sections (F)907.2.10.1.1 through (F)907.2.10.1.3.
(F)907.2.10.1.1 Group R-1. Single- or multiple-station smoke alarms shall be installed in all of the following locations in Group R-1:
1. In sleeping areas.
2. In every room in the path of the means of egress from the sleeping area to the door leading from the sleeping unit.
3. In each story within the sleeping unit, including basements. For sleeping units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.
(F)907.2.10.1.2 Groups R-2, R-3, R-4 and I-1. Single- or multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4 and I-1, regardless of occupant load at all of the following locations:
1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms.
2. In each room used for sleeping purposes.
3. In each story within a dwelling unit, including basements and cellars but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.
(F)907.2.10.1.3 Group I-1. Single- or multiple-station smoke alarms shall be installed and maintained in sleeping areas in occupancies in Group I-1.
Exception: Single- or multiple-station smoke alarms shall not be required where the building is equipped throughout with an automatic fire detection system in accordance with Section (F)907.2.6.
(F)907.2.10.2 Carbon monoxide alarms. Carbon monoxide alarms shall be installed on each habitable level of a dwelling unit or sleeping unit in Groups R-2, R-3, R-4 and I-1 equipped with fuel burning appliances.
(F)907.2.10.3. Power source. In new construction, required alarms shall receive their primary power from the building wiring where such wiring is served from a commercial source and shall be equipped with a battery backup. Alarms shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than as required for overcurrent protection.
Exception: Alarms are not required to be equipped with battery backup in Group R-1 where they are connected to an emergency electrical system.
(F)907.2.10.4 Interconnection. Where more than one alarm is required to be installed with an individual dwelling unit in Group R-2, R-3, or R-4, or within an individual sleeping unit in Group R-1, the alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed. Approved combination smoke and carbon-monoxide detectors shall be permitted.
(F)907.2.10.5 Acceptance testing. When the installation of the alarm devices is complete, each detector and interconnecting wiring for multiple-station alarm devices shall be tested in accordance with the household fire warning equipment provisions of NFPA 72 and NFPA 720, as applicable.
([
25]27) In Section 1008.1.8.3, a new subparagraph (5) is added as follows:(5) Doors in Group I-1 and I-2 occupancies, where the clinical needs of the patients require specialized security measures for their safety, approved access controlled egress may be installed when all the following are met:
5.1 The controlled egress doors shall unlock upon activation of the automatic fire sprinkler system or automatic fire detection system.
5.2 The facility staff can unlock the controlled egress doors by either sensor or keypad.
5.3 The controlled egress doors shall unlock upon loss of power.
([
26]28) In Section 1009.3, Exception #4 is deleted and replaced with the following:4. In Group R-3 occupancies, within dwelling units in Group R-2 occupancies, and in Group U occupancies that are accessory to a Group R-3 occupancy, or accessory to individual dwelling units in Group R-2 occupancies, the maximum riser height shall be 8 inches (203 mm) and the minimum tread depth shall be 9 inches (229 mm). The minimum winder tread depth at the walk line shall be 10 inches (254 mm), and the minimum winder tread depth shall be 6 inches (152 mm). A nosing not less than 0.75 inch (19.1 mm) but not more than 1.25 inches (32 mm) shall be provided on stairways with solid risers where the tread depth is less than 10 inches (254 mm).
([
27]29) In Section 1009.10 Exception 6 is added as follows:6. In occupancies in Group R-3, as applicable in Section 101.2 and in occupancies in Group U, which are accessory to an occupancy in Group R-3, as applicable in Section 101.2, handrails shall be provided on at least one side of stairways consisting of four or more risers.
([
28]30) Section 1012.3 is amended to include the following exception at the end of the section:Exception. Non-circular handrails serving an individual unit in a Group R-1, Group R-2 or Group R-3 occupancy with a perimeter greater than 6 1/4 inches (160 mm) shall provide a graspable finger recess area on both sides of the profile. The finger recess shall begin within a distance of 3/4 inch (19 mm) measured vertically from the tallest portion of the profile and achieve a depth of at least 5/16 inch (8 mm) within 7/8 inch (22 mm) below the widest portion of the profile. This required depth shall continue for at least 3/8 inch (10 mm) to a level that is not less than 1 3/4 inches (45 mm) below the tallest portion of the profile. The minimum width of the handrail above the recess shall be 1 1/4 inches (32 mm) to a maximum of 2 3/4 inches (70 mm). Edges shall have a minimum radius of 0.01 inch (0.25 mm).
([
29]31) In Section 1013.2 Exception 3 is added as follows:3. For occupancies in Group R-3 and within individual dwelling units in occupancies in Group R-2, as applicable in Section 101.2, guards shall form a protective barrier not less than 36 inches (914 mm) in height.
([
30]32) In Section 1015.2.2 the following sentence is added at the end:Additional exits or exit access doorways shall be arranged a reasonable distance apart so that if one becomes blocked, the others will be available.
([
31]33) A new Section 1109.7.1 is added as follows:1109.7.1 Platform (wheelchair) lifts. All platform (wheelchair) lifts shall be capable of independent operation without a key.
([
32]34) In Section 1208.4 subparagraph 1 is deleted and replaced with the following:1. The unit shall have a living room of not less than 165 square feet (15.3 m2) of floor area. An additional 100 square feet (9.3 m2) of floor area shall be provided for each occupant of such unit in excess of two.
([
33]35) Section 1405.3 is deleted and replaced with the following:1405.3 Flashing. Flashing shall be installed in such a manner so as to prevent moisture from entering the wall or to redirect it to the exterior. Flashings shall be installed at the perimeters of exterior door and window assemblies, penetrations and terminations of exterior wall assemblies, exterior wall intersections with roofs, chimneys, porches, decks, balconies and similar projections and at built-in gutters and similar locations where moisture could enter the wall. Flashing with projected flanges shall be installed on both sides and the ends of copings, under sills and continuously above projected trim. A flashing shall be installed at the intersection of the foundation to stucco, masonry, siding or brick veneer. The flashing shall be on an approved corrosion-resistant flashing with a 1/2" drip leg extending past exterior side of the foundation.
([
34]36) In Section 1605.2.1, the formula shown as "f2 = 0.2 for other roof configurations" is deleted and replaced with the following:f2 = 0.20 + .025(A-5) for other configurations where roof snow load exceeds 30 psf
f2 = 0 for roof snow loads of 30 psf (1.44kN/m2) or less.
Where A = Elevation above sea level at the location of the structure (ft/1000).
([
35]37) In Section 1605.3.1 and section 1605.3.2, Exception number 2 in each section is deleted and replaced with the following:2. Flat roof snow loads of 30 pounds per square foot (1.44 kNm2) or less need not be combined with seismic loads. Where flat roof snow loads exceed 30 pounds per square foot (1.44 kNm2), the snow loads may be reduced in accordance with the following in load combinations including both snow and seismic loads. Ws as calculated below, shall be combined with seismic loads.
Ws = (0.20 + 0.025(A-5))Pf is greater than or equal to 0.20 Pf
Where
Ws = Weight of snow to be included in seismic calculations;
A = Elevation above sea level at the location of the structure (ft/1000)
Pf = Design roof snow load, psf
For the purpose of this section, snow load shall be assumed uniform on the roof footprint without including the effects of drift or sliding. The Importance Factor, I, used in calculating Pf may be considered 1.0 for use in the formula for Ws.
([
36]38) In Table 1607.1 number 9 is deleted and replaced with the following:TABLE 1607.1 NUMBER 9
Occupancy or Use Uniform Concentrated
(psf) (lbs)
9. Decks, except residential Same as occupancy
servedh
9.1 Residential decks 60 psf([
37]39) Section 1608.1 is deleted and replaced with the following:1608.1 General. Except as modified in section 1608.1.1, 1608.1.2, and 1608.1.3 design snow loads shall be determined in accordance with Section 7 of ASCE 7, but the design roof load shall not be less than that determined by Section 1607.
([
38]40) Section 1608.1.1 is added as follows:1608.1.1 Section 7.4.5 of Section 7 of ASCE 7 referenced in Section 1608.1 of the IBC is deleted and replaced with the following:
Section 7.4.5 Ice Dams and Icicles Along Eaves. Where ground snow loads exceed 75 psf, eaves shall be capable of sustaining a uniformly distributed load of 2pf on all overhanging portions. No other loads except dead loads shall be present on the roof when this uniformly distributed load is applied. All building exits under down-slope eaves shall be protected from sliding snow and ice.
([
39]41) Section 1608.1.2 is added as follows:1608.1.2 Utah Snow Loads. The ground snow load, Pg, to be used in the determination of design snow loads for buildings and other structures shall be determined by using the following formula: Pg = (Po2 + S2(A-Ao)2)0.5 for A greater than Ao, and Pg = Po for A less than or equal to Ao.
WHERE
Pg = Ground snow load at a given elevation (psf)
Po = Base ground snow load (psf) from Table No. 1608.1.2(a)
S = Change in ground snow load with elevation (psf/100 ft.) From Table No. 1608.1.2(a)
A = Elevation above sea level at the site (ft./1000)
Ao = Base ground snow elevation from Table 1608.1.2(a) (ft./1000)
The building official may round the roof snow load to the nearest 5 psf. The ground snow load, Pg, may be adjusted by the building official when a licensed engineer or architect submits data substantiating the adjustments. A record of such action together with the substantiating data shall be provided to the division for a permanent record.
The building official may also directly adopt roof snow loads in accordance with Table 1608.1.2(b), provided the site is no more than 100 ft. higher than the listed elevation.
Where the minimum roof live load in accordance with section 1607.11 is greater than the design roof snow load, such roof live load shall be used for design, however, it shall not be reduced to a load lower than the design roof snow load. Drifting need not be considered for roof snow loads less than 20 psf.
([
40]42) Table 1608.1.2(a) and Table 1608.1.2(b) are added as follows:TABLE NO. 1608.1.2(a)
STATE OF UTAH - REGIONAL SNOW LOAD FACTORS
COUNTY Po S Ao
Beaver 43 63 6.2
Box Elder 43 63 5.2
Cache 50 63 4.5
Carbon 43 63 5.2
Daggett 43 63 6.5
Davis 43 63 4.5
Duchesne 43 63 6.5
Emery 43 63 6.0
Garfield 43 63 6.0
Grand 36 63 6.5
Iron 43 63 5.8
Juab 43 63 5.2
Kane 36 63 5.7
Millard 43 63 5.3
Morgan 57 63 4.5
Piute 43 63 6.2
Rich 57 63 4.1
Salt Lake 43 63 4.5
San Juan 43 63 6.5
Sanpete 43 63 5.2
Sevier 43 63 6.0
Summit 86 63 5.0
Tooele 43 63 4.5
Uintah 43 63 7.0
Utah 43 63 4.5
Wasatch 86 63 5.0
Washington 29 63 6.0
Wayne 36 63 6.5
Weber 43 63 4.5TABLE NO. 1608.1.2(b)
RECOMMENDED SNOW LOADS FOR SELECTED UTAH CITIES AND TOWNS(2)
Roof Snow Ground Snow
Load (PSF) Load (PSF)
Beaver County
Beaver 5920 ft. 43 62
Box Elder County
Brigham City 4300 ft. 30 43
Tremonton 4290 ft. 30 43
Cache County
Logan 4530 ft. 35 50
Smithfield 4595 ft. 35 50
Carbon County
Price 5550 ft. 30 43
Daggett County
Manila 5377 ft. 30 43
Davis County
Bountiful 4300 ft. 30 43
Farmington 4270 ft. 30 43
Layton 4400 ft. 30 43
Fruit Heights 4500 ft. 40 57
Duchesne County
Duchesne 5510 ft. 30 43
Roosevelt 5104 ft. 30 43
Emery County
Castledale 5660 ft. 30 43
Green River 4070 ft. 25 36
Garfield County
Panguitch 6600 ft. 30 43
Grand County
Moab 3965 ft. 25 36
Iron County
Cedar City 5831 ft. 30 43
Juab County
Nephi 5130 ft. 30 43
Kane County
Kanab 5000 ft. 25 36
Millard County
Millard 5000 ft. 30 43
Delta 4623 ft. 30 43
Morgan County
Morgan 5064 ft. 40 57
Piute County
Piute 5996 ft. 30 43
Rich County
Woodruff 6315 ft. 40 57
Salt Lake County
Murray 4325 ft. 30 43
Salt Lake City 4300 ft. 30 43
Sandy 4500 ft. 30 43
West Jordan 4375 ft. 30 43
West Valley 4250 ft. 30 43
San Juan County
Blanding 6200 ft. 30 43
Monticello 6820 ft. 35 50
Sanpete County
Fairview 6750 ft. 35 50
Mt. Pleasant 5900 ft. 30 43
Manti 5740 ft. 30 43
Ephraim 5540 ft. 30 43
Gunnison 5145 ft. 30 43
Sevier County
Salina 5130 ft. 30 43
Richfield 5270 ft. 30 43
Summit County
Coalville 5600 ft. 60 86
Kamas 6500 ft. 70 100
Park City 6800 ft. 100 142
Park City 8400 ft. 162 231
Summit Park 7200 ft. 90 128
Tooele County
Tooele 5100 ft. 30 43
Uintah County
Vernal 5280 ft. 30 43
Utah County
American Fork 4500 ft. 30 43
Orem 4650 ft. 30 43
Pleasant Grove 5000 ft. 30 43
Provo 5000 ft. 30 43
Spanish Fork 4720 ft. 30 43
Wasatch County
Heber 5630 ft. 60 86
Washington County
Central 5209 ft. 25 36
Dameron 4550 ft. 25 36
Leeds 3460 ft. 20 29
Rockville 3700 ft. 25 36
Santa Clara 2850 ft. 15 (1) 21
St. George 2750 ft. 15 (1) 21
Wayne County
Loa 7080 ft. 30 43
Hanksville 4308 ft. 25 36
Weber County
North Ogden 4500 ft. 40 57
Ogden 4350 ft. 30 43
NOTES
(1) The IBC requires a minimum live load - See 1607.11.2.
(2) This table is informational only in that actual site
elevations may vary. Table is only valid if site elevation
is within 100 feet of the listed elevation.([
41]43) Section 1608.1.3 is added as follows:1608.1.3 Thermal Factor. The value for the thermal factor, Ct, used in calculation of pf shall be determined from Table 7.3 in ASCE 7.
Exception: Except for unheated structures, the value of Ct need not exceed 1.0 when ground snow load, Pg is calculated using Section 1608.1.2 as amended.
([
42]44) Section 1608.2 is deleted and replaced with the following:1608.2 Ground Snow Loads. The ground snow loads to be used in determining the design snow loads for roofs in states other than Utah are given in Figure 1608.2 for the contiguous United States and Table 1608.2 for Alaska. Site-specific case studies shall be made in areas designated CS in figure 1608.2. Ground snow loads for sites at elevations above the limits indicated in Figure 1608.2 and for all sites within the CS areas shall be approved. Ground snow load determination for such sites shall be based on an extreme value statistical analysis of data available in the vicinity of the site using a value with a 2-percent annual probability of being exceeded (50-year mean recurrence interval). Snow loads are zero for Hawaii, except in mountainous regions as approved by the building official.
([
43]45) In Section 1609.1.1 a new exception number 5 is added as follows:5. The wind design procedure as found in Section 1616 through 1624 of the 1997 Uniform Building Code may be used as an alternative wind design procedure provided that the building or component being designed meets the limits for the Simplified Method as defined in ASCE 6.4.1.1 and 6.4.1.2 of ASCE 7. The Importance Factor, I, shall be determined in accordance with Table 6-1 of ASCE 7.
([
44]46) Section 1613.7 is added as follows:1613.7 ASCE 12.7.2 and 12.14.18.1 of Section 12 of ASCE 7 referenced in Section 1613.1, Definition of W, Item 4 is deleted and replaced with the following:
4. Where the flat roof snow load, Pf, exceeds 30 psf, the snow load included in seismic design shall be calculated, in accordance with the following formula: Ws = (0.20 + 0.025(A-5))Pf is greater than or equal to 0.20 Pf
WHERE:
Ws = Weight of snow to be included in seismic calculations;
A = Elevation above sea level at the location of the structure (ft/1000)
Pf = Design roof snow load, psf
For the purposes of this section, snow load shall be assumed uniform on the roof footprint without including the effects of drift or sliding. The Importance Factor, I, used in calculating Pf may be considered 1.0 for use in the formula for Ws.
([
45]47) A new Section 1613.8 is added as follows:1613.8 ASCE 7, Section 13.5.6.2.2 paragraph (e) is modified to read as follows:
(e) Penetrations shall have a sleeve or adapter through the ceiling tile to allow for free movement of at least 1 inch (25 mm) in all horizontal directions.
Exceptions:
1. Where rigid braces are used to limit lateral deflections.
2. At fire sprinkler heads in frangible surfaces per NFPA 13.
([
46]48) Section 1805.5 is deleted and replaced with the following:1805.5 Foundation walls. Concrete and masonry foundation walls shall be designed in accordance with Chapter 19 or 21, respectively. Foundation walls that are laterally supported at the top and bottom and within the parameters of Tables 1805.5(1) through 1805.5(5) are permitted to be designed and constructed in accordance with Sections 1805.5.1 through 1805.5.5. Concrete foundation walls may also be constructed in accordance with Section 1805.5.8.
([
47]49) A new section 1805.5.8 is added as follows:1805.5.8 Empirical foundation design. Group R, Division 3 Occupancies three stories or less in height, and Group U Occupancies, which are constructed in accordance with Section 2308, or with other methods employing repetitive wood-frame construction or repetitive cold-formed steel structural member construction, shall be permitted to have concrete foundations constructed in accordance with Table 1805.5(6).
([
48]50) Table 1805.5(6) is added as follows:Table 1805.5(6), entitled "Empirical Foundation Walls, dated January 1, 2007, published by the Department of Commerce, Division of Occupational and Professional Licensing is hereby adopted and incorporated by reference. Table 1805.5(6) identifies foundation requirements for empirical walls.
([
49]51) A new section 2306.1.[4]5 is added as follows:2306.1.[
4]5 Load duration factors. The allowable stress increase of 1.15 for snow load, shown in Table 2.3.2, Frequently Used Load Duration Factors, Cd, of the National Design Specifications, shall not be utilized at elevations above 5,000 feet (1524 M).([
50]52) In Section 2308.6 the following exception is added:Exception: Where foundation plates or sills are bolted or anchored to the foundation with not less than 1/2 inch (12.7 mm) diameter steel bolts or approved anchors, embedded at least 7 inches (178 mm) into concrete or masonry and spaced not more than 32 inches (816 mm) apart, there shall be a minimum of two bolts or anchor straps per piece located not less than 4 inches (102 mm) from each end of each piece. A properly sized nut and washer shall be tightened on each bolt to the plate.
([
51]53) Section 2506.2.1 is deleted and replaced with the following:2506.2.1 Other materials. Metal suspension systems for acoustical and lay-in panel ceilings shall conform with ASTM C635 listed in Chapter 35 and Section 13.5.6 of ASCE 7-05, as amended in Section 1613.8, for installation in high seismic areas.
([
52]54) In Section 2902.1, the title for Table 2902.1 is deleted and replaced with the following and footnote e is added as follows: Table 2902.1, Minimum Number of Required Plumbing Facilitiesa, e.FOOTNOTE: e. When provided, in public toilet facilities there shall be an equal number of diaper changing facilities in male toilet rooms and female toilet rooms.
([
53]55) Section 3006.5 Shunt Trip, the following exception is added:Exception: Hydraulic elevators and roped hydraulic elevators with a rise of 50 feet or less.
([
54]56) A new section 3403.2.4 is added as follows:3403.2.4 Parapet bracing, wall anchors, and other appendages. Buildings constructed prior to 1975 shall have parapet bracing, wall anchors, and appendages such as cornices, spires, towers, tanks, signs, statuary, etc. evaluated by a licensed engineer when said building is undergoing reroofing, or alteration of or repair to said feature. Such parapet bracing, wall anchors, and appendages shall be evaluated in accordance with 75% of the seismic forces as specified in Section 1613. When allowed by the local building official, alternate methods of equivalent strength as referenced in Subsection R156-56-701(2) will be considered when accompanied by engineer sealed drawings, details and calculations. When found to be deficient because of design or deteriorated condition, the engineer shall prepare specific recommendations to anchor, brace, reinforce, or remove the deficient feature.
EXCEPTIONS:
1. Group R-3 and U occupancies.
2. Unreinforced masonry parapets need not be braced according to the above stated provisions provided that the maximum height of an unreinforced masonry parapet above the level of the diaphragm tension anchors or above the parapet braces shall not exceed one and one-half times the thickness of the parapet wall. The parapet height may be a maximum of two and one-half times its thickness in other than Seismic Design Categories D, E, or F.
([
55]57) Section 3406.4 is deleted and replaced with the following:3406.4 Change in Occupancy. When a change in occupancy results in a structure being reclassified to a higher Occupancy Category (as defined in Table 1604.5), or when such change of occupancy results in a design occupant load increase of 100% or more, the structure shall conform to the seismic requirements for a new structure.
Exceptions:
1. Specific seismic detailing requirements of this code or ASCE 7 for a new structure shall not be required to be met where it can be shown that the level of performance and seismic safety is equivalent to that of a new structure. Such analysis shall consider the regularity, overstrength, redundancy and ductility of the structure within the context of the existing and retrofit (if any) detailing providing. Alternatively, the building official may allow the structure to be upgraded in accordance with referenced sections as found in Subsection R156-56-701(2).
2. When a change of use results in a structure being reclassified from Occupancy Category I or II to Occupancy Category III and the structure is located in a seismic map area where SDS is less than 0.33, compliance with the seismic requirements of this code and ASCE 7 are not required.
3. Where design occupant load increase is less than 25 occupants and the Occupancy Category does not change.
([
56]58) The exception in 3409.1 is deleted and replaced with the following:Exception: Type B dwelling or sleeping units required by section 1107 are not required to be provided in existing buildings and facilities, except when an existing occupancy is changed to R-2.
([
57]59) In Section 3409.4, number 7 is added as follows:7. When a change of occupancy in a building or portion of a building results in a Group R-2 occupancy as determined in section 1107.6.2, not less than 20 percent of the dwelling or sleeping units shall be Type B dwelling or sleeping units. These dwelling or sleeping units may be located on any floor of the building provided with an accessible route. Two percent, but not less than one, of the dwelling or sleeping units shall be Type A dwelling units.
([
58]60) The following referenced standard is added under NFPA in chapter 35:TABLE
Referenced in code
Number Title Section number
720-05 Recommended Practice for the 907.2.10, 907.2.10.5
Installation of Household Carbon
Monoxide (CO) Warning EquipmentKEY: contractors, building codes, building inspection, licensing
Date of Enactment or Last Substantive Amendment: [
January 1,]2007Notice of Continuation: May 16, 2002
Authorizing, and Implemented or Interpreted Law: 58-1-106(1)(a); 58-1-202(1)(a); 58-56-1; 58-56-4(2); 58-56-6(2)(a)
Document Information
- Effective Date:
- 3/27/2007
- Publication Date:
- 02/15/2007
- Filed Date:
- 01/18/2007
- Agencies:
- Commerce,Occupational and Professional Licensing
- Rulemaking Authority:
Section 58-56-1 and Subsections 58-1-106(1)(a), 58-1-202(1)(a), 58-56-4(2), and 58-56-6(2)(a)
- Authorized By:
- F. David Stanley, Director
- DAR File No.:
- 29078
- Related Chapter/Rule NO.: (1)
- R156-56-704. Statewide Amendments to the IBC.