DAR File No.: 26919
Filed: 01/27/2004, 05:23
Received by: NLRULE ANALYSIS
Purpose of the rule or reason for the change:
The Utah Fire Prevention Board met and determined that a 120-day (emergency) Rule amendment was in order to correct some errors made in the adoption of Rule R710-9 that went into effect on January 2, 2004. It was noted that the International Fire Code, 2003 edition, was adopted referencing the usage of an incorporated reference that was not adopted by the administrative rule or statute. The Board voted to make immediate amendments to the existing rule to correct this error. The Board will finalize these changes after complete and proper notice to all affected at the next scheduled Board meeting on March 9, 2004.
Summary of the rule or change:
The proposed amendments to Rule R710-9 are as follows: 1) in Section R710-9-2, it is proposed to add two definitions, "Appreciable Depth" and "Authority Having Jurisdiction", to the rule; and 2) in Subsections R710-9-6(6.1.1) through (6.1.3), it is proposed to eliminate the reference to the International Existing Building Code and add definitions to all three sections that ensure that changes to the structure maintains a reasonable level of fire and life safety and does not create and distinct hazard to life or property without referencing the International Existing Building Code.
State statutory or constitutional authorization for this rule:
Section 53-7-204
Anticipated cost or savings to:
the state budget:
There is no aggregate anticipated cost or savings to the state budget because these proposed changes do not effect the state.
local governments:
There is no aggregate anticipated cost or savings to local government because these proposed changes do not effect local government.
other persons:
There is also no aggregate anticipated cost or savings to other persons because these proposed changes do not affect other persons.
Compliance costs for affected persons:
There is no compliance cost for affected persons with the enactment of this rule amendment.
Comments by the department head on the fiscal impact the rule may have on businesses:
There is no fiscal impact on businesses for the enactment of these rule amendments.
Emergency rule reason and justification:
Regular rulemaking procedures would place the agency in violation of federal or state law.The 2003 edition of the International Fire Code was adopted by administrative rule on January 2, 2004. It was noted that the International Fire Code referenced the usage of the International Existing Building Code in three sections in Chapter 1. The International Existing Building Code was not adopted as an incorporated reference by the Utah Building Codes Commission or the Utah Fire Prevention Board for the State of Utah. The error of leaving this referenced code in the International Fire Code places the user in violation of the adopted standards of the State of Utah.
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:
Public Safety
Fire Marshal
5272 S COLLEGE DR
MURRAY UT 84123-2611Direct questions regarding this rule to:
Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at bhallada@utah.gov
This rule is effective on:
01/28/2004
Authorized by:
Gary A. Wise, State Fire Marshal
RULE TEXT
R710. Public Safety, Fire Marshal.
R710-9. Rules Pursuant to the Utah Fire Prevention Law.
R710-9-2. Definitions.
2.1 "Academy" means Utah Fire and Rescue Academy.
2.2 "Academy Director" means the Director of the Utah Fire and Rescue Academy.
2.3 "Administrator" means Fire Service Education Administrator.
2.4 "Appreciable Depth" means a depth greater than 1/4 inch.
2.5 "Authority Having Jurisdiction (AHJ)" means the State Fire Marshal, his authorized deputies, or the local fire enforcement authority.
2.[
4]6 "Board" means Utah Fire Prevention Board.2.[
5]7 "Certification Council" means Utah Fire Service Certification Council.2.[
6]8 "Coordinator" means Fire Education Program Coordinator.2.[
7]9 "Division" means State Fire Marshal.2.[
8]10 "ICC" means International Code Council, Inc.2.[
9]11 "IFC" means International Fire Code.2.[
10]12 "Institutional occupancy" means asylums, mental hospitals, hospitals, sanitariums, homes for the aged, residential health care facilities, children's homes or institutions, or any similar institutional occupancy.2.[
11]13 "LFA" means Local Fire Authority.2.[
12]14 "NFPA" means National Fire Protection Association.2.[
13]15 "Place of assembly" means where 50 or more people gather together in a building, structure, tent, or room for the purpose of amusement, entertainment, instruction, or education.2.[
14]16 "Plan" means Fire Academy Strategic Plan.2.[
15]17 "SFM" means State Fire Marshal or authorized deputy.2.[
16]18 "Standards Council" means Fire Service Standards and Training Council.2.[
17]19 "Sub-Committee" means Fire Prevention Board Budget Sub-Committee or Amendment Sub-Committee.2.[
18]20 "UCA" means Utah Code Annotated, 1953.R710-9-6. Amendments and Additions.
The following amendments and additions are hereby adopted by the Board for application statewide:
6.1 Administration
6.1.1 IFC, Chapter 1, Section 102.3 is deleted and rewritten as follows: No change shall be made in the use or occupancy of any structure that would place the structure in a different division of the same group or occupancy or in a different group of occupancies, unless such structure maintains a reasonable level of fire and life safety and the change to use or occupancy does not create a distinct hazard to life or property as determined by the AHJ.
6.1.2 IFC, Chapter 1, Section 102.4 is deleted and rewritten as follows: The design and construction of new structures shall comply with the International Building Code. Repairs, alterations and additions to existing structures are allowed when such structure maintains a reasonable level of fire and life safety and the change does not create a distinct hazard to life or property as determined by the AHJ.
6.1.3 IFC, Chapter 1, Section 102.5 is deleted and rewritten as follows: The construction, alteration, repair, enlargement, restoration, relocation or movement of existing buildings or structures that are designated as historic buildings are allowed when such historic structures maintains a reasonable level of fire and life safety and the change does not create a distinct hazard to life or property as determined by the AHJ.
6.1.[
1]4 IFC, Chapter, 1, Section 102.4 is amended as follows: On line three after the words "Building Code." add the following sentence: "The design and construction of detached one- and two-family dwellings and multiple single-family dwellings (town houses) not more than three stories above grade plane in height with a separate means of egress and their accessory structures shall comply with the International Residential Code."6.1.[
2]5 IFC, Chapter 1, Section 109.2 is amended as follows: On line three after the words "is in violation of this code," add the following "or other pertinent laws or ordinances".6.2 Definitions
6.2.1 IFC, Chapter 2, Section 202, Educational Group E, Day care is amended as follows: On line three delete the word "five" and replace it with the word "four".
6.2.2 IFC, Chapter 2, Section 202, Institutional Group I, Group I-1 is amended to add the following: Add "Type 1" in front of the words "Assisted living facilities".
6.2.3 IFC, Chapter 2 Section 202, Institutional Group I, Group I-2 is amended as follows: On line three delete the word "five" and replace it with the word "three". After "Detoxification facilities" delete the rest of the paragraph, and add the following: "Ambulatory surgical centers with two or more operating rooms where care is less than 24 hours, Outpatient medical care facilities for ambulatory patients (accommodating more than five such patients in each tenant space) which may render the patient incapable of unassisted self-preservation, and Type 2 assisted living facilities. Type 2 assisted living facilities with five or fewer persons shall be classified as a Group R-4. Type 2 assisted living facilities with at least six and not more than 16 residents shall be classified as a Group I-1 facility.
6.2.4 IFC, Chapter 2, Section 202, Institutional Group I, Group I-4, day care facilities, Child care facility is amended as follows: On line three delete the word "five" and replace it with the word "four". Also on line two of the Exception after Child care facility delete the word "five" and replace it with the word "four".
6.2.5 IFC, Chapter 2, Section 202 General Definitions, Occupancy Classification, Residential Group R-1 is amended to add the following: Exception: Boarding houses accommodating 10 persons or less shall be classified as Residential Group R-3.
6.2.6 IFC, Chapter 2, Section 202 General Definitions, Occupancy Classification, Residential Group R-2 is amended to add the following: Exception: Boarding houses accommodating 10 persons or less shall be classified as Residential Group R-3.
6.3 General Precautions Against Fire
6.3.1 IFC, Chapter 3, Section 304.1.2 is amended to delete the following sentence: "Vegetation clearance requirements in urban-wildland interface areas shall be in accordance with the International Urban/Wildland Interface Code."
6.3.2 IFC, Chapter 3, Section 311.1.1 is amended as follows: On line ten delete the words "International Property Maintenance Code and the" from this section.
6.4 Elevator Recall and Maintenance
6.4.1 IFC, Chapter 6, Section 607.3 is deleted and rewritten as follows: Firefighter service keys shall be kept in a "Supra - Stor-a-key" elevator key box or similar box with corresponding key system that is adjacent to the elevator for immediate use by the fire department. The key box shall contain one key for each elevator and one key for lobby control.
6.5 Building Services and Systems
6.5.1 IFC, Chapter 6, Section 610.1 is amended to add the following: On line three after the word "Code" add the words "and NFPA 96".
6.6 Record Drawings
6.6.1 IFC, Chapter 9, Section 901.2.1 is amended to add the following: The code official has the authority to request record drawings ("as builts") to verify any modifications to the previously approved construction documents.
6.6.2 IFC, Chapter 9, Section 902.1 Definitions, RECORD DRAWINGS is deleted and rewritten as follows: Drawings ("as builts") that document all aspects of a fire protection system as installed.
6.7 Fire Protection Systems
6.7.1 Inspection and Testing of Automatic Fire Sprinkler Systems
The owner or administrator of each building shall insure the inspection and testing of water based fire protection systems as required in IFC, Chapter 9, Section 901.6.
6.7.2 IFC, Chapter 9, Section 903.2.7 Group R, is amended to add the following: Exception: Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) constructed in accordance with the International Residential Code for one- and two-family dwellings.
6.7.3 IFC, Chapter 9, Section 903.2.7 is amended to add the following: Exception: Group R-4 fire areas not more than 4500 gross square feet and not containing more than 16 residents, provided the building is equipped throughout with an approved fire alarm system that is interconnected and receives its primary power from the building wiring and a commercial power system.
6.7.4 IFC, Chapter 9, Section 903.6 is amended to add the following subsection: 903.6.2 Commercial cooking operation suppression. Automatic fire sprinkler systems protecting commercial kitchen exhaust hood and duct systems with appliances that generate appreciable depth of cooking oils shall be replaced with a UL300 listed system by May 1, 2004.
6.7.5 IFC, Chapter 9, Section 903.6 is amended to add the following subsection: 903.6.3 Dry chemical hood system suppression. Existing automatic fire-extinguishing systems using dry chemical that protect commercial kitchen exhaust hood and duct systems shall be removed and replaced with a UL300 listed system by January 1, 2006 or before that date when any of the following occurs: 1) Six year internal maintenance service; 2) Recharge; 3) Hydrostatic test date as indicated on the manufacturers date of the cylinders; or 4) Reconfiguration of the system piping.
6.7.6 IFC, Chapter 9, Section 903.6 is amended to add the following subsection: 903.6.4 Wet chemical hood system suppression. Existing wet chemical fire-extinguishing systems not UL300 listed and protecting commercial kitchen exhaust hood and duct systems shall be removed, replaced or upgraded to a UL300 listed system by January 1, 2006 or before that date when any of the following occurs: 1) Six year internal maintenance service; 2) Recharge; 3) Hydrostatic test date as indicated on the manufacturer date of the cylinder; or 4) Reconfiguration of the system piping.
6.7.7 IFC, Chapter 9, Section 903.6 is amended to add the following subsection: 903.6.5 Group A-2 occupancies. An automatic fire sprinkler system shall be provided throughout Group A-2 occupancies where indoor pyrotechnics are used.
6.8 Backflow Protection
6.8.1 The potable water supply to automatic fire sprinkler systems and standpipe systems shall be protected against backflow in accordance with the International Plumbing Code as amended in the Utah Administrative Code, R156-56-707.
6.9 Retroactive Installations of Automatic Fire Alarm Systems in Existing Buildings
6.9.1 IFC, Chapter 9, Sections 907.3.1.1, 907.3.1.2, 907.3.1.3, 907.3.1.4, 907.3.1.5, 907.3.1.6, 907.3.1.7, and 907.3.1.8 are deleted.
6.10 Smoke Alarms
6.10.1 IFC, Chapter 9, Section 907.3.2 is amended to add the following: On line three after the word "occupancies" add "and detached one- and two-family dwellings and multiple single-family dwellings (townhouses)".
6.10.2 IFC, Chapter 9, Section 907.3.2.3 is amended to add the following: On line one after the word "occupancies" add "and detached one- and two-family dwellings and multiple single-family dwellings (townhouses)".
6.11 Means of Egress
6.11.1 IFC, Chapter 10, Section 1009.3 is amended as follows: On line six of Exception 5 delete "7.75" and replace it with "8". On line seven of Exception 5 delete "10" and replace it with "9".
6.11.2 IFC, Chapter 10, Section 1009.11, Exception 4 is deleted and replaced with the following: 4. In occupancies in Group R-3, as applicable in Section 101.2 and in occupancies in Group U, which are accessory to an occupancy in Group R-3, as applicable in Section 101.2, handrails shall be provided on at least one side of stairways consisting of four or more risers.
6.11.3 IFC, Chapter 10, Section 1009.11.3 is amended to add the following: Exception: Non-circular handrails serving an individual unit in a Group R-1, Group R-2 or Group R-3 occupancy shall be permitted to have a maximum cross sectional dimension of 3.25 inches (83 mm) measured 2 inches (51mm) down from the top of the crown. Such handrail is required to have an indention on both sides between 0.625 inch (16mm) and 1.5 inches (38mm) down from the top or crown of the cross section. The indentation shall be a minimum of 0.25 inch (6mm) deep on each side and shall be at least 0.5 (13mm) high. Edges within the handgrip shall have a minimum radius of 0.0625 inch (2mm). The handrail surface shall be smooth with no cusps so as to avoid catching clothing or skin.
6.11.4 IFC, Chapter 10, Section 1012.2 is amended to add the following exception: 3. For occupancies in Group R-3 and within individual dwelling units in occupancies in Grouop R-2, as applicable in Section 101.2, guards shall form a protective barrier not less than 36 inches (914mm).
6.11.5 IFC, Chapter 10, Section 1027.2 is amended to add the following: On line five after the word "fire" add the words "and building".
6.12 Fireworks
6.12.1 IFC, Chapter 33, Section 3301.1.3 is amended to add the following Exception: 10. The use of fireworks for display and retail sales is allowed as set forth in UCA 53-7-220 and UCA 11-3-1.
6.13 Flammable and Combustible Liquids
6.13.1 IFC, Chapter 34, Section 3404.4.3 is amended as follows: Delete 3403.6 on line three and replace it with 3403.4.
6.14 Liquefied Petroleum Gas
6.14.1 IFC, Chapter 38, Section 3809.12, is amended as follows: Delete 20 from line three and replace it with 10.
R710-9-13. Utah Fire and Rescue Academy.
13.1 The fire service training school shall be known as the Utah Fire and Rescue Academy.
13.2 The Director of the Utah Fire and Rescue Academy shall report to the Administrator the activities of the Academy with regard to completion of the agreed academy contract.
13.3 The Academy Director may recommend to the Administrator or Coordinator new or expanded standards regarding fire suppression, fire prevention, public fire education, safety, certification, and any other items of necessary interest about the Academy.
13.4 The Academy shall receive approval from the Administrator, after being presented to the Standards and Training Council, any substantial changes in Academy training programs that vary from the agreed contract.
13.5 The Academy Director shall provide to the Coordinator by October 1st of each year, a numerical summary of those students attending the Academy in the following categories:
13.5.1 Those participating in the certification process and those who have received certification during the previous contract period.
13.5.2 Those working towards and those who have received an Associate in Fire Science in the previous contract period.
13.5.3 Those who have completed other Academy classes during the previous contract period.
13.6 The Academy Director shall provide to the Coordinator by October 1st of each year, a numerical comparison of the categories required in Section 13.5, comparing attendance in the previous contract period.
13.7 The Academy Director shall provide to the Coordinator by October 1st of each year, in accepted budgeting practices, a cost analysis of classes provided by the Academy, and the cost per student to the Academy to provide those classes.
13.8 The Academy Director shall provide to the Coordinator by October 1st of each year, a numerical summary of those students attending Academy courses in the following categories:
13.8.1 Non-fire service personnel enrolled in college courses.
13.8.2 Volunteer or career fire service personnel enrolled in college credit courses.
13.8.3 Volunteer or career fire service personnel enrolled in non-credit continuing education courses.
13.9 The Academy Director shall present to the Coordinator by January of each year, proposals to be incorporated in the Academy contract for the next fiscal year.
KEY: fire prevention, law
January 28, 2004
Notice of Continuation June 12,2002
Document Information
- Effective Date:
- 1/28/2004
- Publication Date:
- 02/15/2004
- Filed Date:
- 01/27/2004
- Agencies:
- Public Safety,Fire Marshal
- Rulemaking Authority:
Section 53-7-204
- Authorized By:
- Gary A. Wise, State Fire Marshal
- DAR File No.:
- 26919
- Related Chapter/Rule NO.: (1)
- R710-9. Rules Pursuant to the Utah Fire Prevention Law.