No. 27653 (Amendment): R710-4-3. Amendments and Additions  

  • DAR File No.: 27653
    Filed: 01/14/2005, 09:18
    Received by: NL

     

    RULE ANALYSIS

    Purpose of the rule or reason for the change:

    The Utah Fire Prevention Board met on January 11, 2005, in a regularly scheduled Board meeting, and voted by motion to make amendments to Rule R710-4 by reorganizing and redefining the Fire Alarm Systems section of the rule and adding a new section to the rule that would expand the allowances for specialized door locking systems in certain occupancies under certain conditions.

     

    Summary of the rule or change:

    The proposed amendments to Rule R710-4 are as follows: 1) in Subsection R710-4-3(3.7), the Board proposes to rewrite the Fire Alarm System requirements for those buildings under the jurisdiction of the Board; this rewrite provides better wording, removes unnecessary rule amendments that are already in the adopted incorporated references, and redefines some rule requirements making them easier to understand; and 2) in Subsection R710-4-3(3.11.3), the Board proposes to add a new rule amendment that would allow certain door latching systems in occupancies where patients require specialized security.

     

    State statutory or constitutional authorization for this rule:

    Section 53-7-204

     

    Anticipated cost or savings to:

    the state budget:

    There is no aggregate anticipated cost or savings to the state budget because these proposed amendments do not affect the state budget.

     

    local governments:

    There is no aggregate anticipated cost or savings to local government because these proposed amendments do not affect local government.

     

    other persons:

    There is no anticipated cost to other persons because these proposed amendments do not affect other persons with an anticipated aggregate cost. There is an aggregate anticipated savings to other persons with regard to being allowed to secure the doors with specialized security. The aggregate anticipated savings is impossible to predict due to the unknown number of these systems that would be installed and the number of lives that would be saved or protected with the installation of these doors.

     

    Compliance costs for affected persons:

    There is no compliance cost for affected persons with the enactment of this rule amendment.

     

    Comments by the department head on the fiscal impact the rule may have on businesses:

    There is no fiscal impact on businesses for the enactment of these rule amendments.

     

    The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at:

    Public Safety
    Fire Marshal
    5272 S COLLEGE DR
    MURRAY UT 84123-2611

     

    Direct questions regarding this rule to:

    Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at bhallada@utah.gov

     

    Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on:

    03/03/2005

     

    This rule may become effective on:

    03/04/2005

     

    Authorized by:

    Gary A. Wise, State Fire Marshal

     

     

    RULE TEXT

    R710. Public Safety, Fire Marshal.

    R710-4. Buildings Under the Jurisdiction of the State Fire Prevention Board.

    R710-4-3. Amendments and Additions.

    3.1 Administration

    3.1.1 IFC, Chapter 1, Section 102.3 is deleted and rewritten and follows: No change shall be made in the use or occupancy of any structure that would place the structure in a different division of the same group or occupancy or in a different group of occupancies, unless such structure maintains a reasonable level of fire and life safety and the change to use or occupancy does not create a distinct hazard to life or property as determined by the AHJ.

    3.1.2 IFC, Chapter 1, Section 102.4 is deleted and rewritten as follows: The design and construction of new structures shall comply with the International Building Code. Repairs, alterations and additions to existing structures are allowed when such structure maintains a reasonable level of fire and life safety and the change does not create a distinct hazard to life or property as determined by the AHJ.

    3.1.3 IFC, Chapter 1, Section 102.5 is deleted and rewritten as follows: The construction, alteration, repair, enlargement, restoration, relocation or movement of existing buildings or structures that are designated as historic buildings are allowed when such historic structures maintains a reasonable level of fire and life safety and the change does not create a distinct hazard to life or property as determined by the AHJ.

    3.2 Definitions

    3.2.1 IFC, Chapter 2, Section 202, Educational Group E, Day care is amended as follows: On line three delete the word "five" and replace it with the word "four".

    3.2.2 IFC, Chapter 2, Section 202, Institutional Group I-1 is amended to add the following:

    On line nine add "type 1" in front of the words "assisted living facilities".

    3.2.3 IFC, Chapter 2, Section 202, Institutional Group I-2 is amended as follows: On line three delete the word "five" and replace it with the word "three". On line eight after the words "detoxification facilities" delete the rest of the paragraph, and add the following: "ambulatory surgical centers with two or more operating rooms where care is less than 24 hours and type 2 assisted living facilities. Type 2 assisted living facilities with five or fewer persons shall be classified as a Group R-4. Type 2 assisted living facilities with at least six and not more than 16 residents shall be classified as a Group I-1 facility.

    3.2.4 IFC, Chapter 2, Section 202, Institutional Group I-2, Child care facility is amended as follows: On line two delete the word "five" and replace it with the word "four".

    3.2.5 IFC, Chapter 2, Section 202, Institutional Group I-4 day care facilities, Child care facility is amended as follows: On line three delete the word "five" and replace it with the word "four". Also on line two of the Exception delete the word "five" and replace it with the word "four".

    3.3 Fire Drills

    3.3.1 IFC, Chapter 4, Section 405.2, Table 405.2, is amended to add the following footnotes:

    c. Secondary schools in Group E occupancies shall have a fire drill conducted at least every two months, to a total of four fire drills during the nine-month school year. The first fire drill shall be conducted within the first two weeks of the school year.

    d. A-3 occupancies in academic buildings of institutions of higher learning are required to have one fire drill per year, provided the following conditions are met:

    1. The building has a fire alarm system in accordance with Section 907.2.

    2. The rooms classified as assembly, shall have fire safety floor plans as required in Section 404.3.2(4) posted.

    3. The building is not classified a high-rise building.

    4. The building does not contain hazardous materials over the allowable quantities by code.

    3.4 Door Closures

    3.4.1 IFC, Chapter 7, Section 703.2. Add the following Exception. In Group E Occupancies, where the corridor serves an occupant load greater than 30 and the building does not have an automatic fire sprinkler system installed, the door closures may be of the friction hold-open type on classrooms doors with a rating of 20 minutes or less only.

    3.5 Automatic Fire Sprinkler Systems and Commercial Cooking Operations

    3.5.1 Inspection and Testing of Automatic Fire Sprinkler Systems

    The owner or administrator of each building shall insure the inspection and testing of water based fire protection systems as required in IFC, Chapter 9, Section 901.6.

    3.5.2 IFC, Chapter 9, Section 903.2.9 is amended to add the following: Exception: Group R-4 fire areas not more than 4500 gross square feet and not containing more than 16 residents, provided the building is equipped throughout with an approved fire alarm system that is interconnected and receives its primary power from the building wiring and a commercial power system.

    3.5.3 IFC, Chapter 9, Section 903.6 is amended to add the following subsection: 903.6.2 Commercial cooking operation suppression. Automatic fire sprinkler systems protecting commercial kitchen exhaust hood and duct systems with appliances that generate appreciable depth of cooking oils shall be replaced with a UL300 listed system by May 1, 2004.

    3.5.4 Water Supply Analysis

    3.5.4.1 For proposed construction in both sprinklered and unsprinklered occupancies, the owner or architect shall provide an engineer's water supply analysis evaluating the available water supply.

    3.5.4.2 The owner or architect shall provide the water supply analysis during the preliminary design phase of the proposed construction.

    3.5.4.3 The water analysis shall be representative of the supply that may be available at the time of a fire as required in NFPA, Standard 13, Appendix A-9-2.1.

    3.6 Alternative Automatic Fire-Extinguishing Systems

    3.6.1 IFC, Chapter 9, Section 903.6 is amended to add the following subsection: 903.6.3 Dry chemical hood system suppression. Existing automatic fire-extinguishing systems using dry chemical that protect commercial kitchen exhaust hood and duct systems shall be removed and replaced with a UL300 listed system by January 1, 2006 or before that date when any of the following occurs: 1) Six year internal maintenance service; 2) Recharge; 3) Hydrostatic test date as indicated on the manufacturers date of the cylinders; or 4) Reconfiguring of the system piping.

    3.6.2 IFC, Chapter 9, Section 903.6 is amended to add the following subsection: 903.6.4 Wet chemical hood system suppression. Existing wet chemical fire-extinguishing systems not UL300 listed and protecting commercial kitchen exhaust hood and duct systems shall be removed, replaced or upgraded to a UL300 listed system by January 1, 2006 or before that date when any of the following occurs: 1) Six year internal maintenance service; 2) Recharge; 3) Hydrostatic test date as indicated on the manufacturers date of the cylinder; or 4) Reconfiguration of the system piping.

    3.7 Fire Alarm Systems[

    3.7.1 General Provisions

    3.7.1.1 Fire alarm system construction documents submitted to the AHJ shall include those items required in IFC, Chapter 9, Section 907.1.1.]

    3.7.[2]1 Required Installations[

    3.7.2.1 Fire alarm systems shall be provided as required in IFC, Chapter 9, Section 907, and LSC Chapters as adopted, and in other rules promulgated by the Board.]

    3.7.[2.2]1.1 All state-owned buildings, college and university buildings, other than institutional, with an occupant load of [100]300 or more, all schools with an occupant load of 50 or more, shall have an approved fire alarm system with the following features:

    3.7.[2.2.]1.1.1 [Products-of-combustion s]Smoke detectors shall be installed throughout all corridors and spaces open to the corridor at the maximum prescribed spacing of thirty feet on center and no more than fifteen feet from the walls or smoke detectors shall be installed as required in NFPA, Standard 72, Section 5.3.

    3.7.[2.2]1.1.2 In [other than fully]non or partially fire sprinklered buildings, automatic detectors shall be installed in each enclosed space, other than corridors, at maximum prescribed spacing as specified in [NFPA, Standard 72,]Section 3.7.1.1.2 for smoke detectors or by [their]the manufacturer's listing for heat detectors.

    3.7.[2.2]1.1.3 Manual fire alarm boxes shall be provided as required. In public and private elementary and secondary schools, manual fire alarm boxes shall be provided in the boiler room, kitchen, and main administrative office of each building, and any other areas as determined by the AHJ.[

    3.7.2.2.4 The fire alarm system shall be connected to a proprietary panel, where provided within the complex.]

    3.7.[3]2 Main Panel

    3.7.[3]2.1 An approved key plan drawing and operating instructions shall be posted at the main fire alarm panel which displays the location of all alarm zones and if applicable, device addresses.

    3.7.[3]2.2 The main panel shall be located in a normally attended area such as the main office or lobby. Location of the Main Panel other than as stated above, shall require the review and authorization of the SFM. Where location as required above is not possible, an electronically supervised remote annunciator from the main panel shall be located in a supervised area of the building. The remote annunciator shall visually indicate system power status, alarms for each zone, and give both a visual and audible indication of trouble conditions in the system. All indicators on both the main panel and remote annunciator shall be adequately labeled.

    3.7.[4]3 System Wiring, Class and Style

    3.7.[4]3.1 Fire alarm [S]system [W]wiring shall be designated and installed as a Class A circuit in accordance with the following style classifications:

    3.7.[4]3.1.1 The [I]initiating [D]device circuits[ (IDC)] shall be designated and installed Style D as defined in NFPA, Standard 72.

    3.7.[4]3.1.2 The [Indicating]notification [A]appliance circuits[ (IAC)] shall be designated and installed Style Z as defined in NFPA, Standard 72.

    3.7.[4]3.1.3 Signaling line circuits shall be designated and installed Style 6 or 7 as defined in NFPA, Standard 72.[

    3.7.4.2 All junction boxes shall be adequately identified as part of the fire alarm system. Covers for the concealed boxes shall be painted red.

    3.7.5 System Devices

    All equipment and devices shall be listed and/or labeled by a nationally recognized testing laboratory for fire alarm use.]

    3.7.[6]4 Fan Shut Down

    3.7.[6]4.1 The fan shut down relay(s) in the air handling equipment shall be normally energized, and connected through and controlled by a normally closed contact in the fire alarm panel, or a normally closed contact of a remote relay under supervision by the main panel. The relays will transfer on alarm, and shall not restore until the panel is reset.

    3.7.[6]4.2 Duct detectors required by the IMC, shall be interconnected, and compatible with the fire alarm system.[

    3.7.7 Inspection and Testing

    The owner or administrator of each building shall insure maintenance and testing of fire alarm systems as required in IFC, Chapter 9, Section 901.6. A written log, verifying these tests, shall be kept on file for inspection by the AHJ.]

    3.8 Retroactive Installation of Automatic Fire Alarm Systems

    3.8.1 IFC, Chapter 9, Sections 907.3.1.1, 907.3.1.2, 907.3.1.3, 907.3.1.4 and 907.3.1.9 [is]are deleted.

    3.9 Fireworks

    3.9.1 IFC, Chapter 33, Section 3301.1.3, Exception 4 is amended to add the following sentence: Fireworks are permitted as allowed in UCA 53-7-220 and UCA 11-3-1.

    3.10 Flammable and Combustible Liquids

    3.10.1 IFC, Chapter 34, Section 3406.1 is amended to add the following special operation: 8. Sites approved by the AHJ.

    3.10.2 IFC, Chapter 34, Section 3406.2 is amended to add the following: On line two after the word "sites" add the words "and sites approved by the AHJ". On line five after the words "borrow pits" add the words "and sites approved by the AHJ".

    3.11 Health Care Facilities

    3.11.1 LSC Chapters 18, 19, 20 and 21, Sections 18.1.2.4, 19.1.2.4, 20.1.2.2 and 21.1.2.2 (Exiting Through Adjoining Occupancies) exception is deleted.

    3.11.2 LSC Chapter 19, Section 19.3.6.1, (Rooms Allowed open to Corridor) exceptions No. 1, No. 5, No. 6, and No. 8 are deleted.

    3.11.3 IFC, Chapter 10, Section 1008.1.8.3 is amended to add the following: 5. Doors in Group I-1 and I-2 occupancies, where the clinical needs of the patients require specialized security, approved access controlled egress may be installed when all the following are met: 5.1 The controlled egress doors shall unlock upon activation of the automatic fire sprinkler system or the automatic fire detection system. 5.2 The facility staff can unlock the controlled egress doors by either sensor or keypad. 5.3 The controlled egress doors shall unlock upon loss of power. 6. Doors in Group I-1 and I-2 occupancies, where the clinical needs of the patients require approved, listed delayed egress locks, they shall be installed on doors as allowed in IFC, Section 1008.1.8.6.

    3.12 Time Out and Seclusion Rooms

    3.12.1 Time Out and Seclusion Rooms are allowed in occupancies fully protected by an automatic fire sprinkler system and fire alarm system.

    3.12.2 A vision panel shall be provided in the room door for observation purposes.

    3.12.3 Time Out and Seclusion Room doors may be fitted with a lock which is not releasable from the inside provided the lock automatically releases by the operation of the fire alarm system or power outage.

    3.12.4 Time Out and Seclusion Rooms shall be located where a responsible adult can maintain visual monitoring of the person and room.

     

    KEY: fire prevention, public buildings

    [May 5, 2004]March 4, 2005 Notice of Continuation June 12, 2002

    53-7-204

     

     

     

     

Document Information

Effective Date:
3/4/2005
Publication Date:
02/01/2005
Filed Date:
01/14/2005
Agencies:
Public Safety,Fire Marshal
Rulemaking Authority:

Section 53-7-204

 

Authorized By:
Gary A. Wise, State Fire Marshal
DAR File No.:
27653
Related Chapter/Rule NO.: (1)
R710-4-3. Amendments and Additions.