-
After publication of the October 15, 2011, issue of the Utah State Bulletin, the Division of Administrative Rules became aware of a problem with the rule text published as part of the Notice of Proposed Rule for Rule R710-9 (DAR No. 35296) on page 39. Specifically, in Section R710-9-11, the word " glycerin" which already exists in the text of the effective rule was not printed in subsections 11.1, 11.2, and 11.3. The complete, properly marked text was filed with the Division by the State Fire Marshal's Office. As near as the Division has been able to determine, the omission in the PDF edition of the Bulletin was caused by a sequence of codes used to mark the text to show amendments. This sequence of codes appears to have been misinterpreted by the software the Division uses to produce the Bulletin.
This error affects only the PDF publication. The web publication of the rule is correct (see http://www.rules.utah.gov/publicat/bulletin/2011/20111015/35296.htm).
The text filed with the Division appears below:
R710-9-11. Amendments and Additions.
The following amendments and additions are hereby adopted by the Board for application statewide:
11.1 IFC, Chapter 9, Section 903.3.1.1 is amended by adding the following subsection: 903.3.1.1.2 Antifreeze Limitations. The use of antifreeze in new automatic sprinkler systems[
in new construction in the dwelling unit portion of an occupancy,] installed in accordance with NFPA 13, [is allowed up to 20 heads. The number of sprinkler heads can be expanded as allowed by the AHJ. The mixture of the antifreeze]shall be limited to a maximum concentration of [40]38% premixedpropylene glycol or [50]48% premixed glycerin and the capacity of the system shall not exceed 150 gallons.[The AHJ can allow the concentration of antifreeze to be increased due to temperature concerns.]11.2 IFC, Chapter 9, Section 903.3.1.2 is amended by adding the following subsection: 903.3.1.2.2Antifreeze Limitations. The use of antifreeze innewautomatic sprinkler systems [
in new construction in the dwellingunit portion of an occupancy,]installed in accordance with NFPA 13R, [is allowed up to 20 heads. The numberof sprinkler heads can be expanded as allowed by the AHJ.The mixture of the antifreeze]shall be limited to a maximumconcentration of [40]38% premixedpropylene glycol or [50]48%premixed glycerin and the capacity of the system shallnot exceed 150 gallons.[The AHJ can allow the concentrationof antifreeze to be increased due to temperatureconcerns.]11.3 IFC, Chapter 9, Section 903.3.1.3is amended by adding the following subsection: 903.3.1.3.1Antifreeze Limitations. The use of antifreeze in new automatic sprinkler systems [
in new construction]installed in accordance with NFPA 13D, [is allowed up to 20 heads. The numberof sprinkler heads can be expanded as allowed by the AHJ.The mixture of the antifreeze]shall be limited to a maximumconcentration of [40]38% premixed propylene glycol or [50]48% premixed glycerin and the capacity of the system shallnot exceed 150 gallons.[The AHJ can allow the concentration of antifreeze to be increased due to temperatureconcerns.]The Division regrets any confusion caused bythis publication error. Questions can be directed to NancyLancaster, Publications Editor, at 801-538-3218 or by email at nllancaster@utah.gov
Document Information
- Publication Date:
- 11/15/2011
- Agencies:
- Administrative Services,Administrative Rules
- DAR File No.:
- ed151756